1、TECHNICAL REPORT ISA-TR20.00.01-2007Updated with 27 new specification forms in 2004-2006 Updated with 11 new specification forms in 2007Specification Forms for Process Measurement and Control Instruments Part 1: General ConsiderationsISATR20.00.012007Specification Forms for Process Measurement and C
2、ontrol Instruments Part 1: General Considerations ISBN: 978-1-93756-000-3Copyright 2011 by ISA. All rights reserved. Not for resale. Printed in the United States of America. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means (elec
3、tronic, mechanical, photocopying, recording, or otherwise), without the prior written permission of the Publisher. ISA67 Alexander Drive P. O. Box 12277 Research Triangle Park, North Carolina 27709 USA 3 ISATR20.00.012007Copyright 2011 ISA. All rights reserved. PrefaceThis preface, as well as all fo
4、otnotes and annexes, is included for information purposes and is not part of ISATR20.00.012007.The standards referenced within this document may contain provisions that, through reference in this text, constitute requirements of this document. At the time of publication, the editions indicated were
5、valid. All standards are subject to revision, and parties to agreements based on this document are encouraged to investigate the possibility of applying the most recent editions of the standards indicated within this document. Members of IEC and ISO maintain registers of currently valid Internationa
6、l Standards. ANSI maintain registers of currently valid U.S. National Standards. This document has been prepared as part of the service of ISAThe Instrumentation, Systems, and Automation Society, toward a goal of uniformity in the field of instrumentation. To be of real value, this document should n
7、ot be static but should be subject to periodic review. Toward this end, the Society welcomes all comments and criticisms and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549-84
8、11; Fax (919) 549-8288; E-mail: standardsisa.org. The ISA Standards and Practices Department is aware of the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. The Department
9、is further aware of the benefits to USA users of ISA standards of incorporating suitable references to the SI (and the metric system) in their business and professional dealings with other countries. Toward this end, this Department will endeavor to introduce SI-acceptable metric units in all new an
10、d revised standards, recommended practices, and technical reports to the greatest extent possible. Standard for Use of the International System of Units (SI): The Modern Metric System, published by the American Society for Testing b) to facilitate quoting, bid reviews, purchasing, receiving, calibra
11、tion, inspection, piping design, design audit, accounting, and ordering procedures by uniform display of information; c) to improve efficiency of instrumentation activities from initial concept to final commissioning and any subsequent reviews and revisions; and d) to provide standard data definitio
12、ns and field lengths adequate for electronic exchange of information. This page intentionally left blank. 13 ISATR20.00.012007Copyright 2011 ISA. All rights reserved. 1 Scope Instrument devices with dedicated functionality may be specified using data-sheet-type, approved ISA specification forms. Thi
13、s technical report does not address system specifications such as shared control and shared display devices, where extensive use of functionality or performance specifications is required. This technical report lists the ISA specification forms by form part category, measured or initiating variable,
14、 readout, or final control device categories, and form number. A form numbering system has been implemented that identifies the form categories, device function grouping, and page number. The form number, title, and development status is listed for each proposed or approved form. 2 Normative referen
15、ces ISA20.00.032001, Specification Forms for Process Measurement and Control Instruments, Part 3: Form Requirements and Development Guidelines. 3 Definitions For the purpose of this technical report, the following definition applies: 3.1 specification form: the document, or its electronic data equiv
16、alent, that details the statement of parameters or properties prescribing the design basis, construction, materials, and performance for an instrument to be supplied. 4 Application ISA specification forms may be used for the following different levels of device specification. 4.1 Operating parameter
17、s documentation Documentation of the operating parameters may be completed and endorsed independently of the hardware device selection and preliminary specification through the use of the separate form page. 4.2 Preliminary inquiry/quotation For a preliminary inquiry or quotation, the specifier and
18、vendor may agree on a minimum level of information. In this case, the specifier may mark with an asterisk (*) in the revision column of the Operating Parameters or Device Specification forms, any lines that the recipient of the specification form is requested to complete. 4.3 Traditional specificati
19、on Documentation of operating parameters required for sizing or selection analysis, and identification of the instrument properties that are pertinent to the development of a manufacturers model number, should be the minimum data provided on specification forms used to purchase instruments. 4.4 Conf
20、orming specification A complete specification ideally should include all relevant information about the main device and associated secondary devices that has been agreed to by the purchaser and supplier. In this case, the fully completed specification form can be used for the final documentation of
21、the instrument specifications. ISATR20.00.012007 14 Copyright 2011 ISA. All rights reserved. 5 Requirements 5.1 Three form parts ISA specification forms are generally comprised of three form parts for the following information organization: a) Operating Parameters forms are developed to document the
22、 process application and design conditions for communication to instrument specifiers and manufacturers. b) Device Specification forms are developed to provide the information to initially size and select a main device and the information to identify requirements for attached and directly associated
23、 devices. c) General or Special Requirements forms are developed to provide means for the specifier to identify general or special requirements that are applicable to the device, but need additional space beyond that available in the other two types of forms. 5.2 Form numbers and titles for Operatin
24、g Parameters forms A common form is developed for all devices sharing the same measured variable or final control element. Table A.1, annex A, identifies assigned categories, ISA form numbers, and titles. 5.3 Form numbers and titles for Device Specification forms Device Specification forms are group
25、ed and numbered based upon a device category code, the form part number, and an instrument function subcategory sequential number. Table A.2, annex A, identifies assigned device categories, ISA form numbers, and titles. 5.4 Form numbers and titles for General or Special Requirements forms A single f
26、orm is provided for the initial page of the General or Special Requirements forms. Table A.3, annex A, identifies the assigned ISA form number and title. 6 General sections of ISA specification forms 6.1 Specification identification section Operating Parameters, Device Specification, and General or
27、Special Requirements forms utilize the same specification identification field prompts. 6.2 Endorsements Endorsement identifications and status inference, such as originator, checker, approver, and origin date, should be independent throughout each form type. 6.3 Revision chronicle Identification of
28、 the three most recent entries recorded in the revision chronicle should be independent throughout each form type. 15 ISATR20.00.012007Copyright 2011 ISA. All rights reserved. 6.4 Component identification Identification of the instrument, such as primary tag number, description, line/equipment numbe
29、r, and reference drawing number, should be identical throughout each form type. 7 Classification and designation Hardware specification forms are based on specific hardware types as classified in annex A. This page intentionally left blank. 17 ISATR20.00.012007Copyright 2011 ISA. All rights reserved
30、. Annex A (informative) Specification forms tables of contents Table A.1 Operating parameter device categories and form titles Form Number Form Title Development Status, ISA-SP20 20A1001 Analysis Device Approved (Annex B) 20A1002 Analysis Device Composition or Property Approved (Annex B) 20B1001 Bur
31、ner or Combustion Device 20C1001 Valve or Regulator Device Approved (Annex B) 20F1001 Flow Device Approved (Annex B) 20H1001 Hand Control Device 20L1001 Level Device Approved (Annex B) 20P1001 Differential Pressure Device Approved (Annex B) 20P1002 Pressure Safety Device Approved (Annex B)20P1003 Pr
32、essure Device Rev. 0 Approved (Annex B) 20R1001 Receiver Device20T1001 Temperature Device Approved (Annex B) 20U1001 Basic Engineering Design Data 20V1001 Vibration or Mechanical Analysis Device 20W1001 Weight or Force Device Approved (Annex B) 20X1001 Unclassified Device20Y1001 Relay or Compute or
33、Converter Device 20Z1001 Position DeviceTable A.2 Device specification categories and form titles Form Number Form Title Development Status, ISA-SP20 Analysis Devices 20A2101 Carbon Dioxide Monitor 20A2111 Combustible Gas Analyzer 20A2121 Flue & Stack Gas Analyzer 20A2141 Chromatograph Analyzer 20A2
34、142 Chromatograph Analyzer Components 20A2151 In Situ Oxygen Analyzer 20A2161 Extractive Oxygen Analyzer 20A2162 Extractive Oxygen Analyzer Components ISATR20.00.012007 18 Copyright 2011 ISA. All rights reserved. Table A.2 Device specification categories and form titles (contd) Analysis Devices (con
35、td) 20A2171 Opacity Analyzer 20A2181 Toxic Gas Analyzer 20A2391 Entrained Holdup Gas Monitor Approved (Annex B) 20A2191 Dissolved Oxygen Analyzer 20A2192 Dissolved Oxygen/Ozone/CL2 Transmitter/Analyzer/Monitor Approved (Annex B) 20A2201 Infrared or Ultraviolet Analyzer 20A2202 Infrared or Ultraviole
36、t Analyzer Components 20A2301 Ion-Selective Analyzer 20A2311 Liquid Density or Specific Gravity Transmitter 20A2321 Nuclear-Type Density Transmitter 20A2331 Oil-In-Water Detector 20A2341 pH/ORP Sensor w/wo Insertion Assembly Approved (Annex B) 20A2342 pH/ORP/Conductivity/Resistivity Transmitter/Anal
37、yzer/Monitor Approved (Annex B) 20A2351 Turbidity or Suspended Solids Sensor w/wo Integral Transmitter Approved (Annex B) 20A2352 Turbidity or Suspended Solids Transmitter or Controller Approved (Annex B) 20A2361 Viscometer 20A2371 Moisture Analyzer 20A2372 Moisture Analyzer Components 20A2373 Humid
38、ity/Dewpoint Transmitter w/wo Switches Approved (Annex B) 20A2381 Conductivity Sensor w/wo Insertion Assembly Approved (Annex B) 20A2901 Sample Conditioning System w/wo Switches and Valves Burner or Combustion Devices 20B2001 Flame Detector 20B2101 Flame Monitor Valve or Regulator Devices 20C2001 Li
39、near Motion Type Control Valve Assembly Approved (Annex B) 20C2002 Linear Motion Type Control Valve Auxiliaries Approved (Annex B) 20C2011 Rotary Motion Type Control Valve Assembly Approved (Annex B) 20C2012 Rotary Motion Type Control Valve Auxiliaries Approved (Annex B) 20C2021 Severe Service Contr
40、ol Valve Assembly 20C2022 Severe Service Control Valve Auxiliaries 20C2031 Desuperheater Control Valve 20C2041 Linear Motion Type Motor-Operated Valve Assembly Approved (Annex B) 20C2042 Rotary Motion Type Motor Operated Valve Assembly Approved (Annex B) 19 ISATR20.00.012007Copyright 2011 ISA. All r
41、ights reserved. Table A.2 Device specification categories and form titles (contd) Valve or Regulator Devices (contd) 20C2043 Electric Actuator and Auxiliaries Approved (Annex B) 20C2101 Recirculation Control Valve 20C2111 Pressure Regulator with/without Pilot Valve Approved (Annex B) 20C2131 Tempera
42、ture Regulator Valve 20C2141 Air-Release or Air/Vacuum and Combination Air Valves Approved (Annex B) 20C2201 Power-Actuated Block Valve Assembly 20C2202 Power-Actuated Block Valve Auxiliaries 20C2211 Solenoid Valve 20C2221 Manual-Actuated Block Valve Assembly Flow Devices 20F2001 Anemometer Element
43、20F2011 Elbow Meter Approved (Annex B) 20F2021 Flow Nozzle w/wo Meter Tube Approved (Annex B) 20F2031 Orifice Plate Approved (Annex B) 20F2041 Orifice Plate Assembly w/wo Meter Tube Approved (Annex B) 20F2051 Multivariable Flow Transmitter Approved (Annex B) 20F2061 Paddle Flow Switch or Flowmeter A
44、pproved (Annex B) 20F2071 Pitot Tube w/wo Insertion Assembly Approved (Annex B) 20F2081 Segmental Wedge Flow Element Approved (Annex B) 20F2091 Target Flowmeter 20F2101 V-Shaped Cone Flow Element Approved (Annex B) 20F2111 Venturi or Flow Tube w/wo Meter Tube Approved (Annex B) 20F2211 Flume Flowmet
45、er 20F2221 Open Channel Flowmeter 20F2231 Rotameter Flowmeter 20F2241 Rotameter Transmitter 20F2251 Variable Area Flowmeter 20F2261 Weir Flowmeter 20F2321 Magnetic Flowmeter w/wo Integral Totalizer Indicator Approved (Annex B) 20F2331 Nuclear Type Flowmeter 20F2341 Ultrasonic Flowmeter w/wo Switches
46、 Approved (Annex B) 20F2351 Thermal Mass Flowmeter w/wo Switches Approved (Annex B) 20F2361 Thermal Mass Flow Switch Approved (Annex B) ISATR20.00.012007 20 Copyright 2011 ISA. All rights reserved. Table A.2 Device specification categories and form titles (contd) Flow Devices (contd) 20F2371 Turbine
47、 Flowmeter w/wo Totalizer Indicator 20F2381 Vortex or Swirl Flowmeter w/wo Totalizer Indicator Approved (Annex B) 20F2391 Sonic Flowmeter Approved (Annex B) 20F2411 Positive Displacement Flowmeter Direct-Reading Type Approved (Annex B) 20F2421 Positive Displacement Flowmeter w/ Transmitter or Access
48、ories Approved (Annex B) 20F2431 Variable Area Flow Switch 20F2511 Mass Type Flowmeter 20F2521 Coriolis Mass Flowmeter w/wo Totalizer Indicator Approved (Annex B) 20F2611 Sight Flow Indicator w/wo Illuminator Approved (Annex B) Hand Control Devices 20H2001 Instrument Valve20H2011 Instrument Manifold
49、 Valve Level Devices 20L2101 Capacitance or RF Admittance Level Transmitter w/wo Switches Approved (Annex B) 20L2111 Differential Pressure Level Transmitter - Flange Mounted Approved (Annex B) 20L2121 Displacer-Type Level Transmitter or Local Controller Approved (Annex B) 20L2131 Tape Level Gauge or Transmitter w/wo Switches 20L2141 Nuclear Radiation Level Transmitter w/wo Switches Approved (Annex B) 20L2151 Resistance-Tape Level Transmitter w/wo Switches Approved (Annex B) 20L2161 Radar Level Transmitter w/wo Switch