1、*USACE / NAVFAC / AFCESA / NASA UFGS-33 05 16 (August 2008)-Preparing Activity: NAVFAC SupersedingUFGS-33 05 16 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2008*SECTION TABLE OF CONTENTSDIVISION 33 - UTILITIESSECTION 33 05 16CONCRETE POLES08/0
2、8PART 1 GENERAL1.1 REFERENCES1.2 SUBMITTALS1.3 QUALITY ASSURANCE1.3.1 Concrete Poles1.3.2 Modification of References1.3.3 Design Requirement1.3.4 Certificates: Procedure RequirementPART 2 PRODUCTS2.1 CONCRETE2.2 CEMENT2.2.1 Fly Ash and Pozzolan2.2.2 Ground Iron Blast-Furnace Slag2.3 WATER2.4 AGGREGA
3、TES2.5 ADMIXTURES2.6 REINFORCEMENT2.6.1 Reinforcing Bars2.6.2 Ties and Spirals2.6.3 Prestressing SteelPART 3 EXECUTION3.1 PREPARATION3.2 INSTALLATION3.2.1 Pole Placement3.2.1.1 Driving Poles3.2.1.2 Augering3.2.1.3 Pole Foundation3.3 EXCAVATING, BACKFILLING, AND COMPACTING3.4 PROTECTION OF POLES- End
4、 of Section Table of Contents -SECTION 33 05 16 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-SECTION 33 05 16 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA /
5、NASA UFGS-33 05 16 (August 2008)-Preparing Activity: NAVFAC SupersedingUFGS-33 05 16 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2008*SECTION 33 05 16CONCRETE POLES08/08*NOTE: This guide specification covers the requirements for concrete poles
6、 to support the aboveground exterior steam distribution systems.Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in
7、 respective project, whether or not brackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of the specification. A listing of technical proponents, including their organization designation and telephone number, is on th
8、e Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*NOTE: This guide specification covers the requirements for providing new concrete poles specified under Section 33 63 13 EXTERIOR UNDERGROUND STEAM DISTRIBUTION and Section 33 63 23, EXTERIOR ABOVEGROUND
9、 STEAM DISTRIBUTION.*NOTE: The following information shall be shown on the project drawings:1. Location and spacing of poles.2. Pole foundations if not driven or augered.3. Top elevation.SECTION 33 05 16 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from
10、IHS-,-,-4. Length of poles.5. Details for precast concrete poles.6. Details of miscellaneous metal and hardware attachment to concrete poles.*PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred
11、 to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatically place the reference in the Reference Article. Also use
12、the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.*The publications listed below form a part of this
13、 specification to the extent referenced. The publications are referred to within the text by the basic designation only.ACI INTERNATIONAL (ACI)ACI 211.1 (1991; R 2002) Standard Practice for Selecting Proportions for Normal, Heavyweight, and Mass ConcreteACI 318M (2005) Metric Building Code Requireme
14、nts for Structural Concrete and CommentaryASTM INTERNATIONAL (ASTM)ASTM A 416/A 416M (2006) Standard Specification for Steel Strand, Uncoated Seven-Wire for Prestressed ConcreteASTM A 421/A 421M (2005) Standard Specification for Uncoated Stress-Relieved Wire for Prestressed ConcreteASTM A 615/A 615M
15、 (2008) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete ReinforcementSECTION 33 05 16 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ASTM A 706/A 706M (2006a) Standard Specification for Low-Alloy Steel Deformed and
16、 Plain Bars for Concrete ReinforcementASTM A 82/A 82M (2007) Standard Specification for Steel Wire, Plain, for Concrete ReinforcementASTM A 966/A 966M (2008) Standard Test Method for Magnetic Particle Examination of Steel Forgings Using Alternating CurrentASTM C 150 (2007) Standard Specification for
17、 Portland CementASTM C 260 (2006) Standard Specification for Air-Entraining Admixtures for ConcreteASTM C 33 (2007) Standard Specification for Concrete AggregatesASTM C 494/C 494M (2008) Standard Specification for Chemical Admixtures for ConcreteASTM C 595 (2008) Standard Specification for Blended H
18、ydraulic CementsASTM C 618 (2008) Standard Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in ConcreteASTM C 989 (2006) Standard Specification for Ground Granulated Blast-Furnace Slag for Use in Concrete and MortarsPRECAST/PRESTRESSED CONCRETE INSTITUTE (PCI)PCI MNL-116 (
19、1999) Manual for Quality Control for Plants and Production of Structural Precast Concrete ProductsPCI MNL-120 (2004) Design Handbook - Precast and Prestressed Concrete1.2 SUBMITTALS*NOTE: Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following li
20、st to reflect only the submittals required for the project. Submittals should be kept to the minimum required for adequate quality control.A “G” following a submittal item indicates that the submittal requires Government approval. Some submittals are already marked with a “G”. Only delete an existin
21、g “G” if the submittal item is not complex and can be reviewed through the Contractors Quality Control system. Only add a “G” if the SECTION 33 05 16 Page 5Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-submittal is sufficiently important or complex
22、 in context of the project.For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the “G“ designation to indicate the approving authority. Codes for Army projects using the Resident Management System (RMS) are:
23、“AE“ for Architect-Engineer; “DO“ for District Office (Engineering Division or other organization in the District Office); “AO“ for Area Office; “RO“ for Resident Office; and “PO“ for Project Office. Codes following the “G“ typically are not used for Navy, Air Force, and NASA projects.Choose the fir
24、st bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects.*Government approval is required for submittals with a “G“ designation; submittals not having a “G“ designation are for Contractor Quality Control approval.for information only. When used,
25、a designation following the “G“ designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:SD-05 Design DataConcrete mix designSD-07 CertificatesQuality control procedures1.3 QUALITY A
26、SSURANCE1.3.1 Concrete PolesProvide precast concrete poles or precast prestressed poles for use in overhead steam distribution systems. Precast prestressed concrete poles or precast concrete poles shall be the product of a manufacturer specializing in the production of precast concrete members. Pres
27、tressed concrete poles shall be designed in accordance with PCI MNL-120 or precast concrete poles shall be designed as indicated with section properties equivalent to those of the prestressed concrete poles. Produce poles in one piece, and in accordance with PCI MNL-116.1.3.2 Modification of Referen
28、cesIn the ACI publications, consider the advisory provisions to be mandatory, as though the word “shall“ had been substituted for “should“ wherever it appears. Interpret references to the “building official,“ “Structural Engineer,“ and “Architect/Engineer“ to mean the Contracting Officer.1.3.3 Desig
29、n RequirementAt least 30 calendar days prior to concrete placement, submit a mix design SECTION 33 05 16 Page 6Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-for each strength and type of concrete. Submit a complete list of materials including type;
30、 brand; source and amount of cement, fly ash, pozzolan, ground slag, and admixtures; and applicable reference specification. Submit copies of test reports showing that the mix has been successfully tested to produce concrete with the properties specified and is suitable for the job conditions. Furni
31、sh fly ash and pozzolan test results performed within 6 months of submittal date. Obtain approval before concrete placement. An identical concrete mix design previously approved within the past 12 months by the _ Division, Naval Facilities Engineering Command, may be used without further approval, i
32、f copies of the previous approval and fly ash and pozzolan test results are submitted. Obtain acknowledgement of receipt of test results prior to concrete placement. Submit additional data regarding concrete aggregates if the source of aggregate changes.1.3.4 Certificates: Procedure RequirementSubmi
33、t the precasting manufacturers quality control procedures established in accordance with PCI MNL-116.PART 2 PRODUCTS2.1 CONCRETEACI 211.1 or ACI 318M for Contractor furnished mix design. The minimum compressive strength of concrete at 28 days shall be 35 MPa _ 5000 psi _, unless otherwise indicated.
34、 Add air-entraining admixtures to produce between 4 and 6 percent air by volume.2.2 CEMENTASTM C 150, Type I, II, or III, or ASTM C 595, Type IP or IS blended cement, except as modified herein. The blended cement shall consist of a mixture of ASTM C 150 cement and one of the following materials: AST
35、M C 618pozzolan or fly ash, or ASTM C 989 ground iron blast-furnace slag. The pozzolan or fly ash content shall not exceed 25 percent by weight of the total cementitious material and the ground iron blast-furnace slag shall not exceed 50 percent by weight of total cementitious material.2.2.1 Fly Ash
36、 and PozzolanASTM C 618, Type N, F, or C, except that the maximum allowable loss on ignition shall be 6 percent for Types N and F.2.2.2 Ground Iron Blast-Furnace SlagASTM C 989, Grade 100 or 120.2.3 WATERProvide fresh, clean and potable water.2.4 AGGREGATESASTM C 33, Size 57, 67, or 7. Aggregates sh
37、all not contain any substance which may be deleteriously reactive with the alkalies in the cement.SECTION 33 05 16 Page 7Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.5 ADMIXTURESASTM C 494/C 494M, except that air entraining shall conform to ASTM
38、 C 260.2.6 REINFORCEMENT2.6.1 Reinforcing BarsASTM A 615/A 615M, Grade 400 Grade 60, ASTM A 966/A 966M Grade 400 Grade 60; ASTM A 966/A 966M Grade 400 Grade 60; or ASTM A 706/A 706M.2.6.2 Ties and SpiralsSteel, ASTM A 82/A 82M.2.6.3 Prestressing SteelSeven-wire stress-relieved strand conforming to A
39、STM A 416/A 416Mor stress-relieved wire conforming to ASTM A 421/A 421M, Type WA. The minimum ultimate strength shall be 1750 MPa 250,000 psi. Prestressing steel shall be free from grease, oil, wax, paint, soil, dirt, loose rust, kinks, bends, or other defects.PART 3 EXECUTION3.1 PREPARATIONPrior to
40、 installation of poles, check for damage, such as cracking, spalling, and honeycombing. Reject members which contain honeycombed sections deep enough to expose reinforcing steel. Reject structurally impaired prestressed members. Provide a PCI MNL-116 commercial grade finish.3.2 INSTALLATION3.2.1 Pol
41、e Placement*NOTE: Select the placement methods which are permitted for the project. Delete those that are not allowed.*3.2.1.1 Driving PolesDrive at the hammer manufacturers rated speed and without interruption to the indicated tip elevation. Pile hammer shall be air, steam, or diesel powered, with
42、a capacity at least equal to the hammer manufacturers recommendation for total weight of the pole and character of subsurface material to be encountered. Position a pile cap or drive cap between the pole and hammer. Place hammer cushion or cap block between the ram and the cap or drive cap.3.2.1.2 A
43、ugeringPoles shall be set in augered holes with a diameter 150 mm _ 6 inches _ larger than the concrete pole. Fill augered hole around pole with air-entrained concrete having a minimum compressive strength of 20 MPa 3000 psi at 28 days and finish in a dome. Cure concrete a minimum SECTION 33 05 16 P
44、age 8Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-of 72 hours before performing further work on poles.3.2.1.3 Pole FoundationProvide as indicated, with a cast-in-place dowel. Insert dowel into dowel pocket in bottom of pole and plumb pole. Backfill around pole with backfill and fill materials as specified in Section 31 00 00 EARTHWORK. Provide concrete under this section as specified in Section 03 30 00 CAST-IN-PLACE CONCRETE.3.3 EXCAVATING, B