1、ANSI C82.6-2005 Proposed Revision of ANSI C82.6-1985 American National Standard Approved: February 14, 2005 Secretariat: ANSLG National Electrical Manufacturers Association for lamp ballasts Ballasts for High-Intensity Discharge Lamps Methods of Measurement An American National Standard implies a co
2、nsensus of those substantially concerned with its scope and provisions. It is intended as a guide to aid the manufacturer, the consumer, and the general public. The existence of an American National Standard does not in any respect preclude anyone, whether he has approved the standard or not, from m
3、anufacturing, marketing, purchasing, or using products, processes, or procedures not conforming to the standards. Users are cautioned to obtain the latest editions. The American National Standards Institute does not develop standards and will in no circumstances give an interpretation of any America
4、n National Standard. Moreover, no person shall have the right or authority to issue an interpretation of an American National Standard in the name of the American National Standards Institute. CAUTION NOTICE: This American National Standard may be revised or withdrawn at any time. The procedures of
5、the American National Standards Institute require that action be taken periodically to reaffirm, revise, or withdraw this standard. Purchasers of American National Standards may receive current information on all standards by calling or writing the American National Standards Institute. 2005 America
6、n National Standard Lighting Group, in affiliation with NEMA Page 1 of 29 ANSI C82.6-2005 Proposed Revision of ANSI C82.6-1985 American National Standard Approval of an American National Standard requires verification by ANSI that the requirements for due process, consensus, and other criteria for a
7、pproval have been met by the standards developer. An American National Standard implies a consensus of those substantially concerned with its scope and provisions. Consensus is established when, in the judgment of the ANSI Board of Standards Review, substantial agreement has been reached by directly
8、 and materially affected interests. Substantial agreement means much more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that a concerted effort be made toward their resolution. The existence of an American National Standard
9、 does not in any respect preclude anyone, whether s/he has approved the standard or not, from manufacturing, marketing, purchasing, or using products, processes, or procedures not conforming to the standards. It is intended as a guide to aid the manufacturer, the consumer, and the general public. Th
10、e American National Standards Institute does not develop standards and will in no circumstances give an interpretation of any American National Standard. Moreover, no person shall have the right or authority to issue an interpretation of an American National Standard in the name of the American Nati
11、onal Standards Institute. Requests for interpretations should be addressed to the Committee Secretariat referred to on the title page. Printed and distributed by: Information Handling Services/Global Engineering Documents 15 Inverness Way East, Englewood, CO 80112-5776 Under Contract with National E
12、lectrical Manufacturers Association Copyright 2005 by American National Standard Lighting Group In Affiliation with National Electrical Manufacturers Association All rights reserved. No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without pr
13、ior written permission of the publisher. Printed in the United States of America 2005 American National Standard Lighting Group, in affiliation with NEMA Page 2 of 29 ANSI C82.6-2005 Proposed Revision of ANSI C82.6-1985 FOREWORD (This Foreword is not part of American National Standard C82.6-2005) Su
14、ggestions for improvement of this standard will be welcome. They should be sent to Secretariat C82 Committee, American National Standard Lighting Group, 1300 North 17 thStreet, Suite 1847, Rosslyn, VA 22209. This standard was processed and approved for submittal to ANSI by the Accredited Standards C
15、ommittee on Lamp Ballasts, C82, and its Working Group C82 WG 01. Approval of the standard does not necessarily imply that all working group members voted for its approval. This standard is a revision of ANSI C82.6-1985 and supercedes the aforementioned standard and all supplements. Information conce
16、rning the approval of this standard is based on the documents listed in the table below: CDV RV Revision CDV C82_m690 RV C82_m691 Howard Wolfman, Chair, ASC 82 Ernesto Mendoza, Technical Advisor Randolph Roy, ANSLG Secretariat Matt Clark, Senior Coordinating Editor 2005 American National Standard Li
17、ghting Group, in affiliation with NEMA Page 3 of 29 ANSI C82.6-2005 Proposed Revision of ANSI C82.6-1985 CONTENTS 1.0 Scope. 6 2.0 Normative References.6 3.0 Definitions 7 4.0 General Conditions for Electrical Performance Tests. 7 5.0 Reference-Ballast Circuits.11 6.0 Ballast Measurements (Multiple-
18、Supply Type Ballasts)12 7.0 Mercury-Lamp Constant-Current Series-Supply-Type Transformer Measurements18 8.0 Leakage Current Measurement19 9.0 Temperature Rise Test (Bench Test).19 10.0 Dielectric Tests19 2005 American National Standard Lighting Group, in affiliation with NEMA Page 4 of 29 ANSI C82.6
19、-2005 Proposed Revision of ANSI C82.6-1985 FIGURES 1 Reference-Ballast Circuit for HID Lamps.22 2 Multiple-circuit Ballast Test Connections22 3 Current Slope (di/dt) and Off Time (OT)23 4 Overshoot (OS).23 5 Sustaining Voltage Measurement Wiring Diagram24 6 Sustaining Voltage (V ss )24 7 Crest Facto
20、r.25 8 Series-Type Transformer Test Connections.26 9 Impulse Test Circuit for Reactor Ballasts27 10 Impulse Test Circuit for Autotransformer Ballasts27 11 Impulse Test Circuit for Autotransformer Ballasts - Lead Type.28 12 Impulse Test Circuit for Capacitors Used for Power Factor Correction.28 13 Im
21、pulse Test Circuit for Insulated Winding Ballasts.29 2005 American National Standard Lighting Group, in affiliation with NEMA Page 5 of 29 ANSI C82.6-2005 AMERICAN NATIONAL STANDARD for lamp ballasts Ballasts for High-Intensity Discharge Lamps Methods of Measurement 1.0 SCOPE This standard describes
22、 the procedures to be followed and the precautions to be taken in measuring performance of ballasts for high-intensity discharge (HID) lamps. Deviations from the procedures given in this standard are permissible for production or other testing provided that the methods used give the results in subst
23、antial agreement with the method given herein. In case of doubt, reference shall be made to the specified methods to establish the validity of the results obtained by any alternate procedure. 2.0 NORMATIVE REFERENCES The following standards contain provisions, which, through reference in this text,
24、constitute provisions of this American National Standard. At the time of publication, the editions indicated were valid. All standards are subject to revision, and parties to agreements based on this American National Standard are encouraged to investigate the possibility of applying the most recent
25、 editions of the standards indicated below. ANSI C78.40-1992, Mercury Lamps Specifications ANSI C78.42-2004, High Pressure Sodium Lamps ANSI C78.43-2004 Single-Ended Metal-Halide Lamps ANSI C78.389-2004, High-Intensity Discharge Methods of Measuring Characteristics ANSI C82.4-2002, Ballasts for High
26、-Intensity Discharge and Low Pressure Sodium Lamps (Multiple Supply Type) ANSI C82.5-1990 , Reference Ballasts for High-Intensity Discharge Lamps ANSI C82.7-1983, Mercury Lamp Transformers Constant Current (Series) Supply Type ANSI C82.9-1996, Definitions for High-Intensity Discharge and Low Pressur
27、e Sodium Lamps, Ballasts, and Transformers ANSI C84.1-1995, for Electric Power System and Equipment, Voltage Ratings (60 Hz.) 2005 American National Standard Lighting Group, in affiliation with NEMA Page 6 of 29 ANSI C82.6-2005 ANSI C92.1-1982, Power Systems Insulation Coordination. ANSI/IEEE 100-19
28、84, Dictionary of Electrical and Electronic Terms. ANSI/UL 1029- 2001, High-Intensity Discharge Lamp Ballasts 3.0 DEFINITIONS Definitions of terms that apply specifically to the subject treated in this standard are given in ANSI C82.9 and C92.1. For additional definitions, see ANSI/IEEE 100. (1) Sti
29、ff Line: A stiff line is defined as a sine wave source that exhibits voltage regulation (change of rms voltage from no load to full load divided by rms voltage at full load) of no more than 0.5%. 4.0 GENERAL CONDITIONS FOR ELECTRICAL PERFORMANCE TESTS 4.1 Power supply. Except for the testing of ball
30、asts designed for use on constant- current supply circuits, the AC voltage supply at the input terminals to the ballast-and-lamp combination shall, throughout the full range of test requirements, have a wave shape such that the rms (root-mean-square) summation of the harmonic components will not exc
31、eed 3% of the fundamental component. The impedance of the power source, as measured at the point where the ballast-and-lamp combination is connected, shall not exceed 3% of the ballast impedance. Variable autotransformers or other voltage transformation devices used in the circuits shall have a powe
32、r rating at least five times the wattage of the lamp intended to be operated on the ballast under test. 4.2 Ballast Conditions. For normal operational tests, the ambient temperature and the temperature of the ballast under test shall be 25 C 5 C. 4.3 Lamp Position. The lamp position, both for the me
33、asurement in the reference- ballast circuit and for the measurement of the commercial ballast being tested, shall be vertical base up unless otherwise designated by the lamp or commercial ballast manufacturer. The characteristics of lamps operating on reference ballasts have been established for ver
34、tical and or horizontal operation, the lamp positions most commonly used in ballast measurement work. When a lamp is operated in other than a vertical position the measurement becomes more complicated, and the method outlined in ANSI C78.389 should be followed carefully. 2005 American National Stand
35、ard Lighting Group, in affiliation with NEMA Page 7 of 29 ANSI C82.6-2005 4.4 Lamp Stabilization. 4.4.1. Lamp pre condition: The lamps used for ballast measurements shall, unless otherwise specified, have been seasoned a minimum of 100 hours prior to their use in the ballast tests. 4.4.2. Basic stab
36、ilization method: Before any measurements are taken, the lamp shall be operated within 3% of rated wattage in an ambient temperature of 25 o C 5 o C until the electrical parameters of the lamp cease to change. The lamp burning time required to achieve this lamp stabilization is a minimum of 30 minut
37、es. It could be as much as 6 hours or more for a metal-halide lamp if the lamp is moved while it is still hot or if its orientation is changed. After the stabilization process has begun, the lamp shall not be moved or repositioned until after the testing is complete. In order to avoid heating up the
38、 test ballast during lamp stabilization, causing resistance changes and therefore resulting in unrepeatable data, it is necessary to warm up the lamp on a standby ballast. This standby ballast should be a commercial ballast of a type similar to the test ballast in order to be able to switch a stabil
39、ized lamp to the test ballast without extinguishing the lamp. A fast-acting switch is recommended; however, a make-before-break switch may be required on a high-pressure-sodium lamp to prevent it from extinguishing during switchover. Once the lamp has been transferred to the test ballast circuit, re
40、-stabilization time is important and is typically 1 minute for mercury and high-pressure-sodium lamps and 3 minutes for metal-halide lamps. To avoid test ballast heat-up, measurements should be taken within 5 minutes after re-stabilization. If a HPS lamp ballast is under test the lamp wattage with a
41、 standby ballast should be adjusted to +/- 2% of the nominal lamp wattage, (see ANSI C78.42) if the ballast does not have a fixed power output design. (Informative Note: The effect of heat on ballast operation is under consideration by the ad hoc group.) 4.4.3. Alternative Stabilization method: Beca
42、use in some cases, such as low frequency electronic ballasts, the transfer from the reference ballast to the ballast under test is undefined, the following alternative method should be followed to ensure testing result reproducibility: 4.4.3.1. The lamp characteristics should be determined with a re
43、ference ballast and recorded for future comparison. 4.4.3.2. The same lamp will be driven by the ballast under test for 15 minutes. 4.4.3.3. The electrical measurements should be taken within 2 minutes after the 15- minute stabilization period. 2005 American National Standard Lighting Group, in affi
44、liation with NEMA Page 8 of 29 ANSI C82.6-2005 4.5 Instrumentation CAUTION: Certain instruments connected in parallel with the lamp may be damaged or destroyed when subjected to the starting pulse of ballasts that supply such pulses (such as those for high-pressure sodium and metal-halide pulse-star
45、t lamps). It is recommended that such instruments be connected after the lamp is started and that some arrangement be provided to remove the lamp ignitor from the circuit or otherwise prevent the ignitor from unexpectedly operating. (Note: digital instruments, that meet the requirements described in
46、 this standard, are preferred to analog instruments). 4.5.1 Accuracy. It is desirable that instruments be chosen so that the indications to be read will be in the upper third of the range. Instruments should be selected which have a guaranteed accuracy commensurate with the requirements of the test
47、and shall not have an accuracy less than the following: 4.5.1.1 Analog Instruments: Ammeters and voltmeters: 0.5% up to 800 Hertz Wattmeters: % up to 1000 Hertz for power factors of 50% to 100%; 0.5% up to 125 hertz for low-power-factor (0% to 20%) circuits. 4.5.1.2 Digital Instruments: Accuracy (X
48、percentage of the reading + Y percentage of the scale per instrument manufacturer specification.) DIGITAL INSTRUMENTATION REQUIREMENTS Equipment Digits Resolution Basic Accuracy a.c+d.c. True RMS 2kHz. Voltmeter 3 0.50% yes Ammeter 3 0.50% yes Wattmeter 3 0.50% yes 4.5.2 Impedance Limitations. It is necessary that the potential circuit impedance is high and the current impedance is low to reduce the disturbance of the circuit caused by the presence of