ANSI ASHRAE 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners《计算机与数据处理间单体气调节器分级的测试方法》.pdf

上传人:bowdiet140 文档编号:431397 上传时间:2018-11-11 格式:PDF 页数:16 大小:1MB
下载 相关 举报
ANSI ASHRAE 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners《计算机与数据处理间单体气调节器分级的测试方法》.pdf_第1页
第1页 / 共16页
ANSI ASHRAE 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners《计算机与数据处理间单体气调节器分级的测试方法》.pdf_第2页
第2页 / 共16页
ANSI ASHRAE 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners《计算机与数据处理间单体气调节器分级的测试方法》.pdf_第3页
第3页 / 共16页
ANSI ASHRAE 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners《计算机与数据处理间单体气调节器分级的测试方法》.pdf_第4页
第4页 / 共16页
ANSI ASHRAE 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners《计算机与数据处理间单体气调节器分级的测试方法》.pdf_第5页
第5页 / 共16页
点击查看更多>>
资源描述

1、ANSI/ASHRAE Standard 127-2012(Supersedes ANSI/ASHRAE Standard 127-2007)Method of Testingfor Rating Computer andData Processing RoomUnitary Air ConditionersApproved by the ASHRAE Standards Committee on January 21, 2012; by the ASHRAE Board of Directors on January 25, 2012;and by the American National

2、 Standards Institute on February 24, 2012.ASHRAE Standards are scheduled to be updated on a five-year cycle; the date following the standard number is the year ofASHRAE Board of Directors approval. The latest edition of an ASHRAE Standard may be purchased on the ASHRAE Web site(www.ashrae.org) or fr

3、om ASHRAE Customer Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-mail:ordersashrae.org. Fax: 404-321-5478. Telephone: 404-636-8400 (worldwide) or toll free 1-800-527-4723 (for orders in US andCanada). For reprint permission, go to www.ashrae.org/permissions. 2012 ASHRAE ISSN 1041-2336SP

4、ECIAL NOTEThis American National Standard (ANS) is a national voluntary consensus standard developed under the auspices of ASHRAE.Consensus is defined by the American National Standards Institute (ANSI), of which ASHRAE is a member and which has approved thisstandard as an ANS, as “substantial agree

5、ment reached by directly and materially affected interest categories. This signifies the concurrenceof more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that aneffort be made toward their resolution.” Compliance with this

6、standard is voluntary until and unless a legal jurisdiction makes compliancemandatory through legislation.ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review.ASHRAE Standards are prepared by a Project Committee appointed s

7、pecifically for the purpose of writing the Standard. The ProjectCommittee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, allmust be technically qualified in the subject area of the Standard. Every effort is made to balance the concerne

8、d interests on all ProjectCommittees.The Manager of Standards of ASHRAE should be contacted for:a. interpretation of the contents of this Standard,b. participation in the next review of the Standard,c. offering constructive criticism for improving the Standard, ord. permission to reprint portions of

9、 the Standard.DISCLAIMERASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information andacceptedindustrypractices.However,ASHRAEdoesnotguarantee,certify,orassurethesafetyorperformanceofanyproducts,components,or systems tested, in

10、stalled, or operated in accordance with ASHRAEs Standards or Guidelines or that any tests conducted under itsStandards or Guidelines will be nonhazardous or free from risk.ASHRAE INDUSTRIAL ADVERTISING POLICY ON STANDARDSASHRAE Standards and Guidelines are established to assist industry and the publ

11、ic by offering a uniform method of testing for ratingpurposes,bysuggestingsafepracticesindesigningandinstallingequipment,byprovidingproperdefinitionsofthisequipment,andbyprovidingother information that may serve to guide the industry. The creation of ASHRAE Standards and Guidelines is determined by

12、the need for them,and conformance to them is completely voluntary.In referring to this Standard or Guideline and in marking of equipment and in advertising, no claim shall be made, either stated or implied,that the product has been approved by ASHRAE.ASHRAE Standard Project Committee 127Cognizant TC

13、: TC 9.9, Mission Critical Facilities, Technology Spaces and Electronic EquipmentSPLS Liaison: Craig P. Wray*Denotes members of voting status when the document was approved for publicationJ. Fred Stack, Chair* Gregory R. Jeffers* David V. Quirk*John H. Bean* Mukesh K. Khattar* Terry L. Rodgers*Donal

14、d L. Beaty* Geoffrey M. Lawler* Davis D. Wilson*Thomas A. Davidson David C. Meadows, IIASHRAE STANDARDS COMMITTEE 20112012Carol E. Marriott, Chair Krishnan Gowri Janice C. PetersonKenneth W. Cooper, Vice-Chair Maureen Grasso Douglas T. ReindlDouglass S. Abramson Cecily M. Grzywacz Boggarm S. SettyKa

15、rim Amrane Richard L. Hall James R. TaubyCharles S. Barnaby Rita M. Harrold James K. VallortHoy R. Bohanon, Jr. Adam W. Hinge William F. WalterSteven F. Bruning Debra H. Kennoy Michael W. WoodfordDavid R. Conover Jay A. Kohler Craig P. WraySteven J. Emmerich Frank Myers Eckhard A. Groll, BOD ExOAlla

16、n B. Fraser Ross D. Montgomery, COStephanie C. Reiniche, Manager of StandardsCONTENTSANSI/ASHRAE Standard 127-2012Method of Testing for Rating Computer and Data Processing RoomUnitary Air ConditionersSECTION PAGEForeword. 21 Purpose 22 Scope . 23 Definitions. 24 Classification 35 Rating Requirements

17、 36 Conformance 77 References . 7Normative Annex A: Tests Required 8Normative Annex B: Test Procedure for Measuring Airflow and Static Pressure on Downflow Units 9Informative Annex C: Climate Zone Bin Data with Population Weighting.10Informative Annex D: Comparison of Test Results (Simulated) .11 20

18、12 ASHRAE1791 Tullie Circle NEAtlanta, GA 30329www.ashrae.orgAll rights reserved.NOTEApproved addenda, errata, or interpretations for this standard can be downloaded free of charge from the ASHRAEWeb site at www.ashrae.org/technology. 2012 American Society of Heating, Refrigerating and Air-Condition

19、ing Engineers, Inc. (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission. 2 ANSI/ASHRAE Standard 127-2012(This foreword is not part of this standard. It is merelyinfor

20、mative and does not contain requirements necessaryfor conformance to the standard. It has not beenprocessed according to the ANSI requirements for astandard and may contain material that has not beensubject to public review or a consensus process.Unresolved objectors on informative material are noto

21、ffered the right to appeal at ASHRAE or ANSI.)FOREWORDANSI/ASHRAE Standard 127 was first published in1988 and revised in 2001 and 2007. This revision of the stan-dard makes some significant changes to the 2007 edition.The major revisions and the rationale for them are summa-rized in the following pa

22、ragraphs.DefinitionsThe previous terms sensible coefficient of performance(SCOP) and adjusted sensible coefficient of performance(ASCOP) have been replaced with the new terms net sensiblecoefficient of performance (NSenCOP) and integrated sensi-ble coefficient of performance (iNSenCOP) to remove the

23、confusion caused by the use of the prior terms being used inother ASHRAE documents with different definitions. Somecommon industry terms used within the standard have beenadded as well.Rating Requirements1. The standard has been modified to cover four differentproduct application classifications. Th

24、is reflects theindustry need to modify equipment to accept higherand higher return temperatures, thus increasing effi-ciency.2. The chilled-water conditions have been adjusted on thechilled-water air handlers to emphasize the highersystem efficiency when higher temperatures are used,even though the

25、specific units involved will appear to belower in capacity and efficiency.3. The paragraphs have been reorganized to minimize theconfusion between capacity ratings and efficiencyratings.4. A“normalized”or“weighted”efficiencyratinghasbeencreatedtoprovideasingleefficiencynumber,thussimpli-fying the co

26、mparison of similar units. The raw numberswere retained, however, so engineers can continue tocalculatetheunitsefficiencyatanygeographiclocation.5. The test points on water-cooled (evaporative) directexpansion (DX) units have been adjusted to correspondto AHRI 340/360 as well as a typical cooling to

27、werapproach.6. TheTestDvalueshavebeenadjustedtocorrespondtothevalues required in ANSI/ASHRAE/IES Standard 90.1 for100% free cooling.7. Normalizing values were provided for fluid coolers, fluidcooler pumps, and chilled-water-loop pumps so all tech-nologies could be more easily compared.1. PURPOSEThe

28、purpose of the standard is to establish a uniform setof requirements for rating computer and data processing roomunitary air conditioners (CDPR).2. SCOPEThis standard applies to classes of unitary equipment thatare used to air condition a computer room and data processingequipment. This standard doe

29、s not apply to the rating of indi-vidual assemblies, such as condensing units or direct expan-sion fan-coil units, for separate use.3. DEFINITIONScomputer and data processing room unitary air conditioner(CDPR): a computer and data processing room unitary airconditioner consisting of one or more fact

30、ory-made assem-blies, which include a DX evaporator or chilled-water coolingcoil, an air-moving device, and air-filtering devices. The airconditionermayincludeacompressor,condenser,humidifier,or reheating function. Where DX equipment is provided inmore than one assembly and the separate assemblies a

31、re to beused together, the requirements of rating outlined in this stan-dard are based upon the use of matched assemblies. The func-tions of a CDPR, either alone or in combination with a coolingand heating plant, are to provide air filtration, circulation,cooling, reheating, and humidity puter room

32、air conditioner (CRAC): generally refers tocomputer-room cooling units that utilize dedicated compres-sors and refrigerant cooling coils rather than chilled-puter room air handler (CRAH): generally refers tocomputer-room cooling units that utilize chilled-water coilsfor cooling rather than dedicated

33、 compressors.cooling system energy coefficient of performance (COP): aratio calculated by dividing the net total cooling capacity inwatts by the total power input in watts (excluding reheatersand humidifiers) at any given set of rating conditions. The nettotal cooling capacity is the total gross cap

34、acity minus theenergy dissipated into the cooled space by the blower sensible coefficient of performance (NSenCOP): a ratiocalculated by dividing the net sensible cooling capacity inwatts by the total power input in watts (excluding reheatersand humidifiers) at any given set of rating conditions. T

35、he netsensible cooling capacity is the gross sensible capacity minusthe energy dissipated into the cooled space by the fan system(further explained in Section 5.1).integrated sensible coefficient of performance (iNSen-COP): an NSenCOP value that provides a consistent evalua-tion of the energy effici

36、ency of a unit operated in differentambient temperatures. It is calculated by the method definedin Section 5.2.fluid economizer: a system configuration potentially avail-ablewhenanexternalfluidcoolerisutilizedforheatrejection.It utilizes a separate cooling coil within the unit for cooling 2012 Ameri

37、can Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission. ANSI/ASHRAE Standard 127-2012 3and the

38、 cooled fluid returning from the external fluid cooler toprovide cooling much like a chilled-water unit (i.e., withoutthe use of compressors). This process is sometimes referred toas free cooling.standard rating: a rating based on tests performed at standardrating conditions (see Section 5.1).applic

39、ation rating: a rating based on tests performed at appli-cation rating conditions (i.e., conditions other than standardratingconditions).Applicationratingsdonotrequireretestingbutcanbeextrapolatedfromstandardratingtests.Applicationratings are not required but may be published at the manufac-turers o

40、ption (see Section 5.8).rating conditions: any set of operating conditions underwhich a single level of performance results occurs, and whichcauses only that level of performance to occur.standardratingconditions:ratingconditionsusedasthebasisof comparison of performance characteristics.4. CLASSIFIC

41、ATION4.1 Normally, CDPR units within the scope of this standardcan be classified as shown below. There are five basic types ofunitary air conditioners:a. Single-Package Unit. A complete stand-alone unit.b. Condensing Unit with Separate Coil and Fan. Theremote part of this unit contains the compresso

42、r andcondenser while the indoor part of the unit is an evapo-rator and blower.c. Unit with Remote Condenser. The remote part of theunit is an air-cooled condenser only while the indoorpart of the unit contains the compressor(s), evaporatorcoils, and fan.d. Unit with Remote Air-Cooled Fluid Cooler or

43、 CoolingTower. The indoor part of the unit contains the compres-sor(s), evaporator coil, fan, and condenser. The heatrejection is by means of a remote device (a coolingtower or air-cooled fluid cooler) that uses water or gly-col to transfer the heat.e. Chilled-Water Unit. The indoor part of the unit

44、 is an airhandler with a water-cooled coil that is connected to thebuilding chilled-water system.Note: Any of the above types may utilize a second, ordual, cooling coil that provides cooling by means of a free-coolingliquideconomizeroraseparatebuildingchilled-watersystem.Anyoftheabovetypesmaycontain

45、aninternalhumid-ifier and/or reheat capabilities.5. RATING REQUIREMENTSSection 5 describes all of the testing and rating require-mentsforthisstandard.Asummarylistingofthetestsrequiredis provided in Normative Annex A.5.1 Cooling System Standard Capacity Ratings. Ratedcooling is defined as 100% of the

46、 units max capacity and issometimes referred to as standard rating. Standard ratingcapacity shall be established at the standard rating conditionsspecified in rated cooling Test A of Table 1 for each applica-tion class that applies for this equipment. Standard coolingcapacity shall be stated as sens

47、ible cooling capacity and shallbe net values, reflecting the effects of circulating fan heat.5.1.1 Value of Standard Capacity Ratings. These rat-ings shall be expressed in terms of kilowatts with three signif-icant digits (e.g., 10.2 kW and 105 kW).5.1.2 Standard Rating Conditions. The conditions of

48、test for standard ratings shall include the following.5.1.2.1 Standard Cooling System Rating Tempera-tures. All indoor and outdoor conditions for testing aredefined in Table 1. Also defined in Table 1 are the variousfluid temperatures that shall be used for heat rejection pur-poses on non-air-cooled

49、 systems. A unit shall be rated at all ofthe application classes that apply.5.1.2.2 Voltage and Frequency. Nameplate voltagesfor 60 Hz shall be one or more of the following utilizationvoltages: 115, 200, 208, 230, 265, 460, and/or 575. Standardrating tests shall be performed at the unit nameplate ratedvoltages and frequency. For air conditioners with dual voltageratings, standard rating tests shall be performed at both volt-ages or at the lower of the two voltages if only a single stan-dard rating is to be published. If desired, 50 Hz rati

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ANSI

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1