1、2015 ASHRAE. All Rights reserved. ERRATA SHEET FOR ANSI/ASHRAE STANDARD 185.1-2015 Method of Testing UV-C Lights for Use in Air-Handling Units or Air Ducts to Inactivate Airborne Microorganisms July 19, 2017 The corrections listed in this errata sheet apply to all copies of ANSI/ASHRAE Standard 185.
2、1-2015. The first printing is identified on the outside back cover as “Product code: 86621 4/15”. The shaded items have been added since the previously published errata sheet dated December 15, 2015 was distributed. Page Erratum 4 6.1.1 Test Organisms. In the second sentence of Section 6.1.1 change
3、“(ATCC96916)” to “(ATCC36542)”. 6 7. Determination of Performance. Change Section 7 as shown below. (Note: Additions are shown in underline and deletions are shown in strikethrough.) 7. DETERMINATION OF PERFORMANCE The primary measure of performance within this test method is the single-pass bioaero
4、sol inactivation efficiency. This efficiency shall be characterized in terms of the percentage of A versicolor Aspergillus sydowii (ATCC36542) and M. Mycobacterium Parafortuitum (ATCC19686) that could not be cultured after UV-C radiation exposure.4,5,6,7 The single-pass bioaerosol inactivation efficiency, UVGI, shall be quantified by comparing the bioaerosol concentration upstream and downstream of the UV-C device using the following general equation: