1、Page 1 of 2 2015 ASHRAE. All rights reserved. ERRATA SHEET FOR ANSI/ASHRAE/USGBC/IES STANDARD 189.1-2014 Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings March 23, 2015 The corrections listed in this errata sheet apply to ANSI/ASHRAE/USGBC/IES Standar
2、d 189.1-2014. The first printing is identified on the outside back cover as “Product code: 86606 12/14”. The shaded items have been added since the previously published errata sheet dated January 30, 2015 was distributed. NOTICE: ASHRAE now has a list server for Standing Standard Project Committee 1
3、89.1 (SSPC 189.1). Interested parties can now subscribe and unsubscribe to the list server and be automatically notified via e-mail when activities and information related to the Standard is available. To sign up for the list server please visit Project Committee List Servers for Standard on the Tec
4、hnology / Standards section of the ASHRAE website at http:/www.ashrae.org/standards-research-technology/standards-guidelines/standards-activities/project-committee-list-servers. Page(s) Erratum 13 5.3.3.2 Greenfield Sites. Section 5.3.3.2 was inadvertently omitted in the 2014 edition of Standard 189
5、.1. Note that this section was added to the standard by Addendum u to 189.1-2011. (Note: Additions are shown in underline.) 5.3.3 Plants. 5.3.3.1 Invasive Plants. Invasive plants shall be removed from the building project site and destroyed or disposed of in a land fill. Invasive plants shall not be
6、 planted on the building project site. 5.3.3.2 Greenfield Sites. On a greenfield site: a. where more than 20% of the area of the predevelopment site has existing native plants or adapted plants, a minimum of 20% of the area of native plants or adapted plants shall be retained. b. where 20% or less o
7、f the area of the predevelopment site has existing native plants or adapted plants, a minimum of 20% of the site shall be developed or retained as vegetated area. Such vegetated areas include bioretention facilities, rain gardens, filter strips, grass swales, vegetated level spreaders, constructed w
8、etlands, planters, and open space with plantings. A minimum of 60% of such vegetated area shall consist of biodiverse planting of native plants and/or adapted plants other than turfgrass. 99 Table C1.1 Modifications and Additions to Tables G3.1 of Appendix G in ANSI/ASHRAE/IES Standard 90.1 (Continu
9、ed). (Note: Additions are shown in underline and deletions are shown in strikethrough.) 11. Service Hot-Water Systems In addition to the requirements in Table G3.1 (11), service hot-water usage is allowed to be lower in the proposed design than in the baseline building design if service hot-The serv
10、ice hot-water system in the baseline building design shall use the same energy source as the corresponding system in the proposed design and shall conform with the following conditions: a. Where a complete service hot water system exists, Errata Sheet for ANSI/ASHRAE/USGBC/IES Standard 189.1-2014 Pa
11、ge 2 of 2 2015 ASHRAE. All rights reserved. water use can be demonstrated to be less than that resulting from compliance with Sections 6.3.2, 6.4.2, and 6.4.3. the baseline building design shall reflect the actual system type using actual component capacities and efficiencies. b. Where a new service
12、 hot water system has been specified, the system shall be sized according to the provisions of Section 7.4.1 of ANSI/ ASHRAE/IES Standard 90.1 and the equipment shall match the minimum efficiency requirements in Section 7.4.4 under the standard renewables approach as described in Section 7.4.1.1.1 a
13、nd the super- market heat recovery requirements in Section 7.4.7.2 The equipment efficiency requirements in Section 7.4.4.1 do not apply to the baseline building design. Where the energy source is electricity, the heating method shall be electrical resistance. 1. In addition to the requirements in T
14、able G3.1 (11.b) and (11.c), service hot-water systems shall meet the requirements of Sections 7.4.4.1, 7.4.7.2, and 7.4.7.3. 2. In addition to the requirements in Table G3.1 (11.f), the baseline building design shall meet the requirements of Section 7.4.7.2. If a condenser heat recovery system meet
15、ing the requirements described in Section 7.4.7.2 cannot be modeled, the requirement for including such a system in the actual building shall be met as a prescriptive requirement and no heat-recovery system shall be included in the proposed design or baseline building design. 3. In addition to the requirements in Table G3.1 (11.i), the baseline building design shall meet the requirements of Sections 6.3.2 and 6.4.3.