ANSI NEIS 1-2015 Standard for Good Workmanship in Electrical Construction.pdf

上传人:eveningprove235 文档编号:437434 上传时间:2018-11-14 格式:PDF 页数:29 大小:1.80MB
下载 相关 举报
ANSI NEIS 1-2015 Standard for Good Workmanship in Electrical Construction.pdf_第1页
第1页 / 共29页
ANSI NEIS 1-2015 Standard for Good Workmanship in Electrical Construction.pdf_第2页
第2页 / 共29页
ANSI NEIS 1-2015 Standard for Good Workmanship in Electrical Construction.pdf_第3页
第3页 / 共29页
ANSI NEIS 1-2015 Standard for Good Workmanship in Electrical Construction.pdf_第4页
第4页 / 共29页
ANSI NEIS 1-2015 Standard for Good Workmanship in Electrical Construction.pdf_第5页
第5页 / 共29页
亲,该文档总共29页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、AN AMERICAN NATIONAL STANDARDNECA 1-2015Standard forGood Workmanshipin Electrical ConstructionPublished byNational Electrical Contractors AssociationStandard forGood Workmanshipin Electrical ConstructionNECA 1-2015An AmericanNational StandardPublished byNational Electrical Contractors Associationn i

2、iNOTICE OF COPYRIGHTThis document is copyrighted by NECAReproduction of these documents either in hard copy or soft (including posting on the web) is prohibited without copyright permission. For copyright permission to reproduce portions of this document, please contact NECA Standards also in a hori

3、zontal or vertical position as intended.b) All materials shall be firmly secured in place, adequately supported, and permanent. Materialsembedded in concrete or masonry or otherwise part of the structure are considered sufficiently supported. c) All hardware, fittings, and accessories shall be of a

4、type designed, intended and appropriate for use and complement the items with which they are used. d) All materials and equipment including hangers, supports, fasteners or fittings, and accessories shall have corrosion protection suitable for the atmosphere in which they are installed (whether locat

5、ed indoors or outdoors). Care shall be taken during the installation to assure the integrity of the corrosion protection. Damaged corrosion protection shall be repaired during or after installation.e) All screws, bolts, nuts, clamps, fittings or other fastening devices shall be made up tight in acco

6、rdance with manufacturers and/or listing instructions.f) Plans and specifications shall be carefully followed when installing equipment. NOTE: Local building codes may have seismic requirements that affect equipment installation. Installers shall consult these codes or coordinate with the general co

7、ntractor prior to installing equipment.3. General RequirementsFigure 1 (Courtesy of Cogburn Bros., Inc.)n 41. ScopePermanence and neat appearance, a part of good workmanship, require that consideration be given to the type of atmosphere surrounding anchors and fasteners. Anchors and fasteners shall

8、be non-corrosive or have adequate corrosion resistant coatings or treatment. Weather conditions must be considered for outdoor locations, but there are also indoor locations that may be wet or damp. Fumes from industrial processing also may cause corrosive atmospheres. The possibility of corrosion d

9、ue to incompatibility between dissimilar metals must also be considered. Corrosion and deterioration is addressed in Section 300.6 of the NEC.a) All anchors and fasteners shall be of a type designed for the purpose and rated capable of adequately and safely securing the item on the base material in

10、which the anchor or fastener is used. Selection shall be based on the amount and type of load, base material, safe working load and atmosphere.b) In addition to the weight of the material, consideration should also be given to vibration, such as with motors or fans; variable loading resulting from i

11、nternal or external forces, such as operation of safety switches or circuit breakers; and shock load, when possible (see Figure 2).c) Anchors or fasteners used shall be a type designed and intended for use in the base material to which the material or support is to be attached. Generally, screws are

12、 used on wood, masonry anchors on concrete or brick, toggle bolts or similar on hollow walls, machine screws, bolts or welded studs on steel. Nails are normally used only for temporary support or for light loads, such as nonmetallic outlet and device boxes, in wood frame construction.4. Anchors and

13、FastenersFigure 2 (Courtesy of IAEI)5 n1. ScopeThe weight of the hanger or support must be considered as part of the total load. The total load also includes the materials within an enclosure. For example, the weight of the conductors in a raceway or junction or pull box shall be added to the load o

14、f the raceway or box. External forces such as vibration, operation of equipment, such as switch handles, or possible shock load shall also be considered. Safe working load shall be determined by applying recognized safety factors to the rated strength of the complete assembly and shall be based on t

15、he weakest component member. a) Hangers and supports shall be used to properly and firmly support electrical materials or equipment in a safe and permanent manner. They may be standard manufactured items or fabricated in the shop or on the job site (see Figure 3). b) They shall be of a type designed

16、 or appropriate for the purpose, have a neat and finished appearance and complement the installation.c) Job fabricated hangers and supports shall be made from standard structural shapes and hardware or systems of shapes, fittings and hardware designed for the purpose. One example would be angle iron

17、s. d) All bolts, screws, nuts, and other threaded devices shall have standard threads and heads so that they do not require special tools and may be readily replaced when necessary unless required for tamper-proof installation.e) All threads shall be fully engaged (or covered) and all parts made up

18、tight.f) The selection of hangers and supports shall be based on the following criteria:1. Amount and type of load2. Safe working load3. Atmosphere4. Manufacturers recommendations5. Job specifications6. Listing for the application (where applicable)7. Spacing intervals required by the NEC (where app

19、licable).g) Hangers and supports, whether standard manufactured items or job fabricated, shall have corrosion protection suitable for the atmosphere in which they are installed (whether located indoors or outdoors). Care shall be taken during the installation to assure the integrity of corrosion pro

20、tection. Damaged corrosion protection shall be repaired during or after installation.h) When hangers and supports that have corrosion protection are field cut, the material shall be protected by field application of an approved zinc-enriched paint or similar sealant in accordance with 300.6.5. Hange

21、rs and SupportsFigure 3 (Courtesy of IAEI)n 6NECA 1 Standard for Good Workmanship in Electrical Constructioni) Care must be taken to prevent corrosion that might result from the use of dissimilar metals in damp or wet locations. Damaged corrosion protection coatings shall be repaired during or after

22、 installation.j) Hangers and supports shall be adequately and safely attached to the building structure or structural member.k) The equipment or materials to be supported shall be securely fastened to the supporting means with material suitable for the purpose.7 n1. Scopea) Outlet and device boxes s

23、hall be of a type designed for the use and location (see Figure 4). b) Outlet and device boxes shall be securely and rigidly attached or supported plumb, level, and true. c) Box supports, hangers or brackets, when used, shall be of a type designed or suitable for the type of box used and the buildin

24、g structural member to which they are attached. In determining the type of support or fastener, consider the total load caused by any device or equipment, such as lighting fixtures, which are in turn supported by the outlet box (see Figure 5).d) Outlet and device boxes and their covers shall have co

25、rrosion protection suitable for the atmosphere in which they are installed. Where necessary, gaskets shall be used to prevent the entrance of moisture. e) Installation of outlet and device boxes shall be coordinated with other trades, such as drywall and painting.f) Outlet and device boxes shall be

26、protected to prevent entrance of foreign matter. Plaster and debris shall be thoroughly cleaned from the box before the conductors are installed.g) Generally, single-gang outlet and device boxes for switches shall be mounted with the long axis vertical.h) Generally, boxes for receptacles shall be mo

27、unted either vertically or horizontally, but consistently throughout the structure.i) Boxes of three or more gangs shall be mounted with the long axis (dimension) horizontal. The boxes shall be located so that the cover or device plate will not span different types of building finishes either vertic

28、ally or horizontally.j) Boxes for switches near doors shall be located on the side opposite the hinge and close to the door trim. k) Covers for outlet boxes shall be of a type designed, intended and appropriate for the use and location, and have suitable corrosion protection. Plastic device plates s

29、hall not be used as covers for surface mounted boxes.6. Outlet BoxesFigure 4 (Courtesy of IAEI) Figure 5 (Courtesy of IAEI)n 81. Scopea) Junction and pull boxes shall be used where necessary to facilitate the pulling of wire or cable.Section 314.28(A) in the NEC provides minimum sizing requirements

30、for junction or pull boxes used in wiring systems containing conductors in sizes 4 AWG and larger (see Figures 6a and 6b).b) Consideration shall be given to the size and number of conductors, number of bends in the raceway, and the need for support of conductors in vertical raceways.c) Junction and

31、pull boxes shall be of a type intended or suitable for the use and location. They may be standard manufactured items or custom designed and fabricated to meet the particular requirements.d) Junction and pull boxes including hinges or screws used to fasten the cover shall have corrosion protection su

32、itable for the atmosphere in which they are installed.e) Junction and pull boxes shall be firmly and securely fastened to or supported from the building structure or structural member. In determining the type of fastener, hanger, or support, consideration must be given to the load caused by any cond

33、uctors supported by the box and any load that might be caused by external forces.f) Raceways shall be arranged to provide the longest sweep or radius for the conductors. g) Covers for large junction or pull boxes that are that are 1.8 m2(6 ft2) or larger should be hinged or sectionalized to facilita

34、te removal and replacement. When the cover is sectionalized, cross bracing shall be provided to fasten the sections of the cover at the seams.7. Junction and Pull BoxesFigure 6a Figure 6b9 n1. Scopea) Raceways shall be firmly and securely fastened to or supported from the building structure or a str

35、uctural member or embedded in concrete or masonry. Tables 1a and 1b (next page) list recommended spacing of supports for vertical and horizontal raceways.b) Hangers and supports shall be of a type compatible with and suitable for the intended use. They may be standard manufactured items or job fabri

36、cated. Consideration must be given to the weight of the enclosed conductors when selecting supports and fastening means.8. RacewaysTable 1a: Spacing of Conduit Supports*Conduit Trade No. of Conductors Location Maximum Support Size (inches) in Run Spacing (feet)HORIZONTAL RUNS12, 34 1 or 2 Flat ceili

37、ng or wall 5 12, 34 1 or 2 Where it is difficult to provide supports 7 except at intervals fixed by the building construction 12, 34 3 or more Any location 7 1 and larger 1 or 2 Flat ceiling or wall 6 1 and larger 1 or 2 Where it is difficult to provide supports 10 except at intervals fixed by the b

38、uilding construction 1 and larger 3 or more Any location 10 Any Concealed 10VERTICAL RUNS12, 34 Exposed 7 1, 114 Exposed 8 112 and larger Exposed 10 Up to 2 Shaftway 14 212 and larger Shaftway 28 Any Concealed 101. A support shall be provided for exposed or concealed raceway as close as practical to

39、 and not exceeding one foot from an unsupported box or access fitting. In horizontal runs, a support at a box or access fitting may be omitted when the box or access fitting is independently supported and the raceway terminal is not made with a Chase nipple or threadless box connector.2. In vertical

40、 runs, the load produced by the weight of the raceway and the enclosed conductors shall not be carried by the raceway terminals but shall be carried entirely by the conduit supports.* (The National Electrical Code did not provide specific requirements for the support of rigid metal conduit until the

41、 1965 Edition. The table of spacings in the Code applied to sizes 12” through 3” only and was expanded to cover up to 6” in the 1968 Edition. The spacing requirements of this standard were originally published by the National Electrical Contractors Association in 1928 as part of the “Electragist Sta

42、ndards for Wiring Installations.” They have been frequently quoted and included in handbooks on electrical installations. In some specifics they are more restrictive than the requirements of the National Electrical Code.) n 10NECA 1 Standard for Good Workmanship in Electrical Constructionc) Care sha

43、ll be taken to prevent the entrance of foreign matter into raceways and they shall be cleaned if necessary before pulling the conductors.d) Stub-ups shall be protected from damage and carefully re-bent where necessary. Bends and offsets shall be carefully made so that the inside diameter is not effe

44、ctively reduced. Unless otherwise required, the legs of a bend shall be in the same plane, and the straight legs of offsets shall be parallel.e) All raceway fittings shall be of a type compatible with the raceway and suitable for the use and location. f) Unless otherwise specified, concealed raceway

45、s Figure 7 (Courtesy of Cogburn Bothers, Inc.)Table 1b: Spacing of Conduit Supports*Conduit Trade Size No. of Conductors Location Maximum Support (metric designator) in Run Spacing (meters)HORIZONTAL RUNS16, 21 1 or 2 Flat ceiling or wall 1.5 16, 21 1 or 2 Where it is difficult to provide supports 2

46、.1 except at intervals fixed by the building construction 16, 21 3 or more Any location 2.1 27 and larger 1 or 2 Flat ceiling or wall 1.8 27 and larger 1 or 2 Where it is difficult to provide supports 3 except at intervals fixed by the building construction 27 and larger 3 or more Any location 3 Any

47、 Concealed 3VERTICAL RUNS16, 21 Exposed 2.1 27, 35 Exposed 2.5 41 and larger Exposed 3 Up to 53 Shaftway 4.3 63 and larger Shaftway 8.5 Any Concealed 31. A support shall be provided for exposed or concealed raceway as close as practical to and not exceeding one foot from an unsupported box or access

48、 fitting. In horizontal runs, a support at a box or access fitting may be omitted when the box or access fitting is independently supported and the raceway terminal is not made with a Chase nipple or threadless box connector.2. In vertical runs, the load produced by the weight of the raceway and the

49、 enclosed conductors shall not be carried by the raceway terminals but shall be carried entirely by the conduit supports.* (The National Electrical Code did not provide specific requirements for the support of rigid metal conduit until the 1965 Edition. The table of spacings in the Code applied to sizes 12” through 3” only and was expanded to cover up to 6” in the 1968 Edition. The spacing requirements of this standard were originally published by the National Electrical Contractors Association in 1928 as part of the “Electragist Sta

展开阅读全文
相关资源
  • ANSI Z97 1-2009 American National Standard for Safety Glazing Materials used in Buildings - Safety Performance Specifications and Methods of Test《建筑物中窗用玻璃材料安全性用.pdfANSI Z97 1-2009 American National Standard for Safety Glazing Materials used in Buildings - Safety Performance Specifications and Methods of Test《建筑物中窗用玻璃材料安全性用.pdf
  • ANSI Z97 1 ERTA-2010 Re ANSI Z97 1 - 2009 Errata《修订版 美国国家标准学会Z97 1-2009标准的勘误表》.pdfANSI Z97 1 ERTA-2010 Re ANSI Z97 1 - 2009 Errata《修订版 美国国家标准学会Z97 1-2009标准的勘误表》.pdf
  • ANSI Z21 40 2a-1997 Gas-Fired Work Activated Air-Conditioning and Heat Pump Appliances (Same as CGA 2 92a)《燃气、工作激活空气调节和热泵器具(同 CGA 2 92a)》.pdfANSI Z21 40 2a-1997 Gas-Fired Work Activated Air-Conditioning and Heat Pump Appliances (Same as CGA 2 92a)《燃气、工作激活空气调节和热泵器具(同 CGA 2 92a)》.pdf
  • ANSI Z124 9-2004 American National Standard for Plastic Urinal Fixtures《塑料小便器用美国国家标准》.pdfANSI Z124 9-2004 American National Standard for Plastic Urinal Fixtures《塑料小便器用美国国家标准》.pdf
  • ANSI Z124 4-2006 American National Standard for Plastic Water Closet Bowls and Tanks《塑料抽水马桶和水箱用美国国家标准》.pdfANSI Z124 4-2006 American National Standard for Plastic Water Closet Bowls and Tanks《塑料抽水马桶和水箱用美国国家标准》.pdf
  • ANSI Z124 3-2005 American National Standard for Plastic Lavatories《塑料洗脸盆用美国国家标准》.pdfANSI Z124 3-2005 American National Standard for Plastic Lavatories《塑料洗脸盆用美国国家标准》.pdf
  • ANSI T1 659-1996 Telecommunications - Mobility Management Application Protocol (MMAP) RCF-RACF Operations《电信 可移动管理应用协议(MMAP) RCF-RACF操作》.pdfANSI T1 659-1996 Telecommunications - Mobility Management Application Protocol (MMAP) RCF-RACF Operations《电信 可移动管理应用协议(MMAP) RCF-RACF操作》.pdf
  • ANSI T1 651-1996 Telecommunications – Mobility Management Application Protocol (MMAP)《电信 可移动性管理应用协议》.pdfANSI T1 651-1996 Telecommunications – Mobility Management Application Protocol (MMAP)《电信 可移动性管理应用协议》.pdf
  • ANSI T1 609-1999 Interworking between the ISDN User-Network Interface Protocol and the Signalling System Number 7 ISDN User Part《电信 ISDN用户间网络接口协议和7号信令系统ISDN用户部分.pdfANSI T1 609-1999 Interworking between the ISDN User-Network Interface Protocol and the Signalling System Number 7 ISDN User Part《电信 ISDN用户间网络接口协议和7号信令系统ISDN用户部分.pdf
  • ANSI T1 605-1991 Integrated Services Digital Network (ISDN) - Basic Access Interface for S and T Reference Points (Layer 1 Specification)《综合服务数字网络(ISDN) S和T基准点的.pdfANSI T1 605-1991 Integrated Services Digital Network (ISDN) - Basic Access Interface for S and T Reference Points (Layer 1 Specification)《综合服务数字网络(ISDN) S和T基准点的.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > ANSI

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1