1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 1453 Electric Booster and Commercial Storage Tank Water Heaters STANDARD FOR SAFETYUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULU
2、L COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Electric Booster and Commercial Storage Tank Water Heaters, UL 1453 Sixth Edition, Dated March 29, 2016 Summary of Topics This revision of ANSI/UL 1453 is being issued
3、 to revise polymeric material and thermal insulation requirements and to add requirements for outdoor-use equipment. The new and revised requirements are substantially in accordance with Proposal(s) on this subject dated September 23, 2016, October 14, 2016 and December 16, 2016. Text that has been
4、changed in any manner or impacted by ULs electronic publishing system is marked with a vertical line in the margin. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recordin
5、g, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable for any special, incidental, cons
6、equential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of such damage. In no event shall ULs l
7、iability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, damage, claim, or judgment (includin
8、g reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standard on the purchasers computer system. MARCH 9, 2017 UL 1453 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MARCH
9、 9, 2017 UL 1453 tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL March 29, 2016 (Title Page Reprinted: March 9, 2017) 1 UL 1453 Standard for Electric Booster and Commercial Storage Tank Water Heaters First Edition Apr
10、il, 1979 Second Edition July, 1982 Third Edition February, 1988 Fourth Edition September, 1995 Fifth Edition June, 2004 Sixth Edition March 29, 2016 This ANSI/UL Standard for Safety consists of the Sixth edition including revisions through March 9, 2017. The most recent designation of ANSI/UL 1453 a
11、s an American National Standard (ANSI) occurred on March 9, 2017. ANSI approval for a standard does not include the Cover Page, Transmittal Pages and Title Page. Comments or proposals for revisions on any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Pr
12、oposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at https:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding thos
13、e Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2017 UNDERWRITERS LABORATORIES INC. ANSI/UL 1453-2017UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MARCH 9, 2017 UL 1453 2 No Text on This PageUL COPYRIGHTED MATERIA
14、L NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .6 2 Components 7 3 Units of Measurement .7 4 Undated References 7 5 Glossary .7 CONSTRUCTION 6 Frame and Enclosure 9 6.1 General .9 6.2 Enclosure materials 10 6.3 Emission of burning p
15、articles or molten metal .13 6.4 Accessibility of live parts .15 6.5 Ventilation openings .17 7 Heating Element Accessories .17 8 Doors and Covers .18 9 Mechanical Assembly 20 10 Corrosion Resistance .21 11 Supply Connections Permanent Connection 21 11.1 General .21 11.2 Wiring compartments .22 11.3
16、 Field wiring terminals and leads 23 12 Supply Connections Cord Connection .25 12.1 Supply cord .25 12.2 Bushings 26 12.3 Strain relief 26 12.4 Pin terminals .27 13 Current-Carrying Parts 28 14 Internal Wiring 28 14.1 General .28 14.2 Methods 29 15 Splices 30 16 Separation of Circuits .31 17 Barrier
17、s 32 18 Heating Elements .32 19 Electrical Insulation .32 20 Thermal Insulation .32A 20.1 General 32A 20.2 Polymeric foam .32A 21 Overcurrent Protective Devices .32B 22 Lampholders .35 23 Switches and Control Devices 35 24 Temperature-Limiting Controls 36 25 Temperature-Regulating Controls .39 26 Te
18、rminals and Sensing Elements of Temperature-Regulating and Temperature-Limiting Controls .41 27 Materials in Contact with Water .41 27.1 General .41 MARCH 9, 2017 UL 1453 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 27.2 Dip tubes 42 28
19、Spacings 42 29 Grounding .43 30 Motors .46 30.1 General .46 30.2 Motor overload protection .49 31 Low-voltage transformers General 52 REDUCTION OF RISK OF INJURY TO PERSONS 32 Reduction of Risk of Injury to Service Personnel 52 33 Enclosures and Guards 54 34 Switches and Controls .54 35 Surface Temp
20、erature 54 36 Pressure Vessels and Parts Subject to Pressure .54 37 Temperature and Pressure Relief Devices .54 PERFORMANCE 38 General 55 39 Test Installation for Alcove or Closet 55 40 Leakage Current Test .58 41 Grounding Continuity Test .62 42 Input Test 62 43 Temperature-Regulating and Temperatu
21、re-Limiting Control Operation Tests .62 43.1 Temperature-regulating controls 62 43.2 Temperature-limiting controls 63 44 Nonmetallic Dip Tube Tests 63 44.1 Deformation and weight loss .63 44.2 Resistance to crushing 64 44.3 Collapse 66 45 Temperature Tests 67 45.1 General .67 45.2 Continuous operati
22、on .69 45.3 Surface temperature 70 46 Hydrostatic Pressure Test .70 47 Enclosure Strength Test .70 48 Strain Relief Test .71 49 Push Back Relief Test .71 50 Knockout Test 71 51 Dielectric Voltage-Withstand Test .71 52 Heating Element Insulation Resistance Test .72 53 Electrical Disturbance Evaluatio
23、n of Foam Thermal Insulation 73 MANUFACTURING AND PRODUCTION TESTS 54 Dielectric Voltage-Withstand Test .73 55 Grounding Continuity Test .75 RATINGS 56 Details .75 MARCH 29, 2016 UL 1453 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MARKI
24、NGS 57 General 76 58 Cautionary Markings 80 INSTRUCTIONS 59 Details .81 OUTDOOR-USE EQUIPMENT 60 General 83 61 Enclosures .83 62 Field Wiring Connections 85 63 Wiring .85 64 Outdoor-Use Equipment Tests .86 64.1 Rain test 86 64.2 Accelerated aging tests - Gaskets 89 MARCH 9, 2017 UL 1453 5UL COPYRIGH
25、TED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 These requirements cover electric booster water heaters, electric commercial storage tank water heaters, and remote control assemblies for such heaters, rated 600 volts or less, t
26、o be employed in ordinary locations in accordance with the National Electrical Code, NFPA 70, and that meet at least one of the following conditions: a) Over 120 gallons (454 L) in capacity; b) Rated over 12 kilowatts; or c) Equipped with one or more temperature-regulating controls that permit a wat
27、er temperature of more than 85C (185F). 1.2 These heaters are intended for installation in accordance with model mechanical and plumbing codes. 1.3 An electric water heater not exceeding 120 gallons (454 L) capacity, rated no more than 12 kilowatts, and equipped with a temperature-regulating thermos
28、tat having no marked dial setting more than 77C (171F) and provided with a stop to prevent adjustment to a higher setting, shall be judged in accordance with the requirements in the Standard for Household Electric Storage Tank Water Heaters, UL 174. 1.4 These requirements do not cover electric boile
29、rs, commercial cooking appliances, medical and dental equipment, or other electric heating equipment or appliances that are covered in or as part of individual requirements that are separate from this standard. Electrode type boilers are not covered by these requirements. 1.5 In the following text,
30、a requirement that applies only to booster water heaters or to commercial storage-tank water heaters is so identied by a specic reference in that requirement to the equipment involved. Absence of such a specic reference or use of the term water heater indicates that the requirement applies to all of
31、 the equipment covered in this standard unless the context indicates otherwise. MARCH 29, 2016 UL 1453 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 2 Components 2.1 Except as indicated in this clause, a component of a product covered by
32、this standard shall comply with the requirements for that component. See the individual sections of this standard for component requirements. 2.2 A component is not required to comply with a specic requirement that: a) Involves a feature or characteristic not required in the application of the compo
33、nent in the product covered by this standard, or b) Is superseded by a requirement in this standard. 2.3 A component shall be used in accordance with its rating established for the intended conditions of use. 2.4 Specic components are incomplete in construction features or restricted in performance
34、capabilities. Such components are intended for use only under limited conditions, such as certain temperatures not exceeding specied limits, and shall be used only under those specic conditions. 3 Units of Measurement 3.1 Values stated without parentheses are the requirement. Values in parentheses a
35、re explanatory or approximate information. 3.2 Unless indicated otherwise, all voltage and current values mentioned in this standard are root mean square (rms). 4 Undated References 4.1 Any undated reference to a code or standard appearing in the requirements of this standard shall be interpreted as
36、 referring to the latest edition of that code or standard. 5 Glossary 5.1 For the purpose of this standard the following denitions shall apply. 5.2 BOOSTER WATER HEATER A water heater furnishing hot water from initially heated water, which is usually 60C (140F), with the minimum output water tempera
37、ture being 77C (171F). 5.3 ELECTRICAL CIRCUITS a) Line Voltage Circuit A circuit involving a potential of no more than 600 volts and having circuit characteristics in excess of those of a low voltage circuit. b) Low Voltage Circuit A circuit involving a potential of no more than 30 volts rms (42.4 v
38、olts peak) supplied by a battery or by a standard Class 2 transformer or other transforming device, or by a combination of transformer and xed impedance having output characteristics in compliance with requirements established for a Class 2 transformer. A circuit obtained by connecting resistance in
39、 series with a line voltage supply circuit as a means of limiting the voltage and current is not considered to be a low voltage circuit. MARCH 29, 2016 UL 1453 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 5.4 ENCLOSURE The part of an ele
40、ctric water heater that surrounds insulated and uninsulated current-carrying live parts and that is intended to contain a re resulting from an electrical fault. 5.5 FRAME A structure of angle or channel or a folded rigid section of sheet metal that is rigidly attached to and has essentially the same
41、 outside dimensions as the enclosure surface and that has sufficient torsional rigidity to resist the bending moments which may be applied via the enclosure surface when it is deected. 5.6 HEATING ELEMENT ACCESSORY An attachment to the water heater that will allow electrical rating modication. The h
42、eating element accessory consists of a heating element(s), a new rating label, and associated hardware to mount the element(s). 5.7 OPERATING CONTROL A control intended to start or regulate the appliance during normal operation. An example would be a water temperature-regulating control. An operatin
43、g control could provide Type 1 or Type 2 action. (See denitions 5.13 and 5.14.) 5.8 OUTER JACKET The part of the water heater that surrounds the storage tank and that is intended to provide mechanical protection for the tank and for thermal insulation when the insulation is provided. The outer jacke
44、t also serves as an enclosure of current-carrying parts and insulated conductors between heating elements in separate control or wiring compartments. 5.9 PROTECTIVE CONTROL A control intended to prevent the risk of electric shock, re, or injury to persons during abnormal operation of the appliance.
45、An example would be a water temperature limit control. A protective control always provides Type 2 action. (See denitions 5.13 and 5.14.) 5.10 QUALIFIED SERVICE PERSONNEL Persons having appropriate technical training and experience necessary to: a) Perform tasks in service access areas of the equipm
46、ent; and b) Be aware of risks of injury to which they are exposed in performing a task, and of measures to minimize these risks to themselves or other persons. 5.11 SAFETY CONTROL A control that is relied upon to reduce the risk of re, electric shock, or injury to persons for example, an interlock.
47、A safety control may include such devices as relays, switches, interlocks, and other auxiliary equipment used to form a safety control system. 5.12 TEMPERATURE-PRESSURE RELIEF VALVE An automatic resetting pressure relieving device actuated by water pressure or an integral thermal element that is in
48、contact with and responsive to the heated water. 5.13 TYPE 1 ACTION Automatic action for which the manufacturing deviation and the drift of its operating value, operating time, or operating sequence have not been declared and tested to the Standard for Automatic Electrical Controls for Household and
49、 Similar Use, Part 1: General Requirements, UL 60730-1. MARCH 29, 2016 UL 1453 8UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 5.14 TYPE 2 ACTION Automatic action for which the manufacturing deviation and the drift of its operating value, operating time, or operating sequence have been declared and tested to the Standard for Automatic Electrical Controls for Household and Similar Use, Part 1: General Requirem