1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 567 Emergency Breakaway Fittings, Swivel Connectors and Pipe-Connection Fittings for Petroleum Products and LP-Gas STANDARD FOR SAFETYUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRO
2、DUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Emergency Breakaway Fittings, Swivel Connectors and Pipe-Connection Fittings for Petroleum Products and LP-Gas, UL 5
3、67 Tenth Edition, Dated May 7, 2014 Summary of Topics These revisions to ANSI/UL 567 include the following: 1. Revision to the hydrostatic-strength test single-break emergency breakaway ttings The new and/or revised requirements are substantially in accordance with Proposal(s) on this subject dated
4、February 10, 2017, and June 9, 2017. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is
5、 without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost savings,
6、loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of such damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardles
7、s of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced w
8、hile purchaser is storing an electronic Standard on the purchasers computer system. JULY 28, 2017 UL 567 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL JULY 28, 2017 UL 567 tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED F
9、OR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MAY 7, 2014 (Title Page Reprinted: 7/28/2017) 1 UL 567 Standard for Emergency Breakaway Fittings, Swivel Connectors and Pipe- Connection Fittings for Petroleum Products and LP-Gas The rst through third editions were titled Pipe Conne
10、ctors for Flammable Liquids and LP-Gas. The fourth through seventh editions were titled Pipe Connectors for Flammable and Combustible Liquids and LP-Gas. The eighth edition was titled Pipe Connectors for Petroleum Products and LP-Gas. First Edition August, 1959 Second Edition March, 1971 Third Editi
11、on August, 1972 Fourth Edition May, 1978 Fifth Edition March, 1984 Sixth Edition March, 1989 Seventh Edition August, 1992 Eighth Edition June, 1996 Ninth Edition July, 2003 Tenth Edition May 7, 2014 This ANSI/UL Standard for Safety consists of the Tenth Edition including revisions through July 28, 2
12、017. The most recent designation of ANSI/UL 567 as an American National Standard (ANSI) occurred on July 27, 2017. ANSI approval for a standard does not include the Cover Page, Transmittal Pages, and Title Page. Comments or proposals for revisions on any part of the Standard may be submitted to UL a
13、t any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at https:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should be altered in any way. All of ULs Standards and all
14、 copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2017 UNDERWRITERS LABORATORIES INC. ANSI/UL 567-2017UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MAY 7, 2014 UL 56
15、7 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .4 2 General4 2.1 Components4 2.2 Units of measurement .5 2.3 Undated references .5 3 Glossary 5 4 Installation and Operating Instructions
16、.6 CONSTRUCTION 5 General 6 6 Materials.7 7 Swivel Connectors And Emergency Breakaway Fittings .7 8 Pipe-Connecting Fittings .8 9 End Connections .9 PERFORMANCE 10 General12 11 Electrical-Continuity Test .12 12 External Leakage Test .13 13 Seat Leakage Test 14 14 Operation Test 14 15 Endurance Test
17、.17 16 Abuse Test .17 17 Drop Test 18 18 Hydrostatic-Strength Test .18A 19 Pull Test 18A 19.1 Pipe-connecting ttings18A 19.2 Emergency breakaway tting .20 20 Tests of Synthetic Rubber Parts 20 20.1 General.20 20.2 Change-in-volume test .21 20.3 Weight-loss test .22 21 Low Temperature Test 22 22 Mark
18、ing Adhesion Test.23 23 Moist Ammonia-Air Stress Cracking Test .23 MANUFACTURING AND PRODUCTION TESTS 24 General24 MARKING 25 General24 MAY 7, 2014 UL 567 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 These requir
19、ements cover emergency breakaway ttings, swivel connectors and pipe-connecting ttings of the threadless compression type. Connectors and ttings covered by these requirements are intended only for the following services. 1.2 A swivel connector is either a hose swivel or joint swivel. The swivel conne
20、ctor will allow radial movement and shall be constructed for petroleum product, liqueed petroleum gas (LP-Gas) or anhydrous ammonia (NH3) service. 1.3 An emergency breakaway tting is used between the outlet of the dispensing device and the hose nozzle valve or lever-operated fuel transfer valve (LP-
21、Gas Service) and separates in the event that the coupling is subjected to an excessive pull force to safeguard against abnormally excessive pull force on the hose assembly and dispenser and prevent loss of liquid. An emergency breakaway tting shall be constructed for petroleum product, liqueed petro
22、leum gas (LP-Gas) or anhydrous ammonia (NH3) service. The ttings shall be of the single-break or reconnectable type. 1.4 Requirements for the installation and use of dispensing equipment handling petroleum products are included in the Flammable and Combustible Liquids Code, NFPA 30, and the Code for
23、 Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A. 1.5 Requirements for the installation and use of dispensing devices handling LP-Gas are included in the Liqueed Petroleum Gas Code, NFPA 58. 1.6 Requirements for the installation and use of dispensing equipment handling anhydrous ammoni
24、a are included in the Safety Requirements for the Storage and Handling of Anhydrous Ammonia, ANSI/CGA G-2.1 (ANSI K61.1). 1.7 A hose assembly provided with an integral swivel connector for petroleum product service shall comply with the applicable requirements in the Standard for Hose and Hose Assem
25、blies for Dispensing Flammable Liquids, UL 330. 2 General 2.1 Components 2.1.1 Except as indicated in 2.1.2, a component of a product covered by this standard shall comply with the requirements for that component. 2.1.2 A component is not required to comply with a specic requirement that: a) Involve
26、s a feature or characteristic not required in the application of the component in the product covered by this standard, or b) Is superseded by a requirement in this standard. MAY 7, 2014 UL 567 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM U
27、L 2.1.3 A component shall be used in accordance with its rating established for the intended conditions of use. 2.1.4 Specic components are incomplete in construction features or restricted in performance capabilities. Such components are intended for use only under limited conditions, such as certa
28、in temperatures not exceeding specied limits, and shall be used only under those specic conditions. 2.2 Units of measurement 2.2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory or approximate information. 2.3 Undated references 2.3.1 Any undated referen
29、ce to a code or standard appearing in the requirements of this standard shall be interpreted as referring to the latest edition of that code or standard. 3 Glossary 3.1 For the purposes of this standard the following denitions apply: 3.2 FITTING, PIPE-CONNECTING A tting of the threadless compression
30、 seal-ring type for use in the assembly of petroleum product dispensing devices to facilitate connection of piping or tubing. These ttings shall be made in the straight coupling style, as well as in the tee, ell, reducer, adapter, and other styles. 3.3 FITTING, RECONNECTABLE TYPE An emergency breaka
31、way tting designed such that upon separation it is intended to be reconnected and reused when it is not damaged. 3.4 FITTING, SINGLE-BREAK TYPE An emergency breakaway tting that, upon separation, is not intended to be reconnected and reused. 3.5 HOSE SWIVEL A swivel connector with one end attached t
32、o a hose and the other end to an appurtenance. The hose swivel will allow radial movement of the hose and/or appurtenance to prevent the hose from twisting or having torsional stress. 3.6 LIQUEFIED PETROLEUM GAS (LP-GAS OR LPG) Any material having a vapor pressure not exceeding that allowed for comm
33、ercial propane, as dened in Standard Specication for Liqueed Petroleum (LP) Gases, ASTM D1835, that is composed predominantly of the following hydrocarbons, either by themselves (excluding propylene) or as mixtures: propane, propylene, butane (normal butane or isobutane) and butylenes. 3.7 PETROLEUM
34、 PRODUCTS As used herein, means gasoline, gasoline/alcohol blends containing up to 15 percent alcohol, fuel oil, kerosene, and similar liquid motor or heating fuel products. 3.8 PRESSURE INDICATING DEVICE As used herein, the pressure indicating device means one of the following: a) An analog gauge h
35、aving a pressure range such that the test pressure is between 30 and 70 percent of the maximum scale reading of the gauge; b) A digital pressure transducer, or other digital gauge, that is calibrated over a range of pressure that includes the test pressure; or MAY 7, 2014 UL 567 5UL COPYRIGHTED MATE
36、RIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL c) Other device that is equivalent to the devices in (a) or (b). 3.9 SWIVEL CONNECTOR A type of swivel categorized as either a hose swivel or swivel joint. 3.10 SWIVEL JOINT A swivel connector installed in a pipi
37、ng system with at least one end attached to a rigid pipe or other appurtenance that is rmly affixed. The swivel joint will allow radial movement of the pipe or other appurtenance attached to the swivel to prevent torsional stress. 4 Installation and Operating Instructions 4.1 A copy of the installat
38、ion and operating instructions shall be provided and shall be used as a guide in the examination and test of the device. For this purpose, a nal printed edition is not required. 4.2 The instructions shall include directions and information as deemed by the manufacturer to be adequate for proper and
39、safe installation, maintenance and use of the device. 4.3 Each emergency breakaway tting shall be provided with instructions that indicate how to determine that the maximum rated separation force will not damage the hose assembly or dispensing device. 4.4 Each swivel connector shall be provided with
40、 instructions that indicates if it is a hose swivel or swivel joint. CONSTRUCTION 5 General 5.1 A connector or tting for use with petroleum products shall be constructed for an operating pressure of not less than 50 pounds per square inch gauge (psig) (340 kPa) for the uid conning portion of the dev
41、ice and 0.5 psig (3.45 kPa) for the vapor conning portion of the device, when provided, and an ultimate rupture pressure of not less than ve times the design pressure. 5.2 A swivel connector or emergency breakaway tting for use with anhydrous ammonia or LP-Gas shall be designed for an operating pres
42、sure of not less than 350 psig (2413 kPa) and an ultimate rupture pressure of not less than ve times the design pressure. 5.3 An emergency breakaway tting shall be constructed to separate in the event that the coupling is subjected to a pull force not less than 100 pounds (445 N), and not to exceed
43、350 pounds (1557 N) for petroleum product service and 400 pounds (1779 N) for anhydrous ammonia or LP-Gas Service. MAY 7, 2014 UL 567 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 6 Materials 6.1 Materials in contact with the uid to be ha
44、ndled shall be inherently resistant to being adversely effected by such uid. 6.2 A synthetic rubber part shall not show any signs of cracking or other damage following exposure to minus 40F (minus 40C). See the Low Temperature Test, Section 21. 6.3 A part made of drawn-brass or machined from bass ro
45、d shall be capable of withstanding, without cracking, the Moist Ammonia-Air Stress Cracking Test, Section 23, for copper and copper alloys. 6.4 A copper or a copper-alloy part shall not be used where it is in contact with aluminum, unless one of the parts is coated with chromium or other equivalent
46、metallic coating to preclude electrolytic action. A coating shall have a thickness of not less than 0.0002 inch (0.0005 mm). 6.5 If atmospheric corrosion of a ferrous material part will interfere with the proper function of a connector or a tting, the part shall be provided with a corrosion-resistan
47、t protective coating. 6.6 A protective coating shall provide resistance against corrosion to a degree not less than that provided by the protective coatings specied in 6.7. 6.7 Cadmium plating shall have a thickness of not less than 0.0003 inch (0.0008 mm) and zinc plating shall have a thickness of
48、not less than 0.0005 inch (0.013 mm), except on parts where threads constitute the major portion of the area, in which case the thickness of the cadmium or the zinc plating shall not be less than 0.00015 inch (0.0038 mm). 6.8 Ammonia containing minute quantities of water reacts rapidly with cadmium,
49、 copper, zinc, and many alloys, especially those of copper base. Only iron, steel, and certain nonferrous alloys, determined to be satisfactory for ammonia service, are to be used in contact with anhydrous ammonia. 7 Swivel Connectors And Emergency Breakaway Fittings 7.1 A swivel connector or emergency breakaway tting for use with petroleum products shall provide electrical continuity from end-to-end across the one or more swivel joints, when provided, so that whe