1、 PAGE 1 OF 7 AMSC N/A FSC 6150 Distribution Statement A. Approved for public release, distribution is unlimited. INCH-POUND MIL-DTL-53126/4A 16 October 2012 SUPERSEDING MIL-E-53126(ME) 20 April 1992 DETAIL SPECIFICATION SHEET POWER DISTRIBUTION, ILLUMINATION SYSTEMS, ELECTRICAL DISTRIBUTION SYSTEM,
2、60 AMPS/PHASE (A/P) This specification is approved for use within US Army Research Development and Engineering Command, Communications and Electronics Research and Development Center, Product Realization Directorate, Department of the Army and is available for use by all Departments and Agencies of
3、the Department of Defense. The requirement for acquiring the product described herein shall consist of this specification sheet and MIL-DTL-53126. 1 SCOPE 1.1 Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type IV, m
4、odel: M60, NSN: 6150-01-307-9445. 2 APPLICABLE DOCUMENTS 2.1 Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation. DRAWING# NOMENCLATURE DRAWING # NOMENCLATURE CE
5、COM & PM-MEP Drawings - Cage Code: 97403 and 30554 13229E6352 Distribution System, Electrical, Single Phase, 60 Amperes/Phase 13229E6340 Connector Assembly 40 AMP/PH Input Plug (Copies of drawings required by contractors in connection with specific acquisition functions should be obtained from: PROJ
6、ECT MANAGER-MOBILE ELECTRIC POWER, 5850 Delafield Road, Bldg 324 FT BELVOIR VA 22060-5809.) Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-53126/4A PAGE 2 OF 7 3 REQUIREMENTS 3.1 Requirements. The M60, Type IV, PDISE shall be a self-containe
7、d, free-standing, man portable unit. The system shall be capable of distributing 60 Amps of current to all its outputs simultaneously, as specified herein. Type III 60 ampere distribution system 3.2 Design. The M60 PDISE shall be IAW TA13229E6352 and as specified herein. 3.2.1 Dimensions. The M60 PD
8、ISE shall not be greater than the following dimensions: Length (Inches) Width (Inches) Height (Inches) 24.00 21.00 18.00 3.2.2 Weight. The M60 PDISE shall weigh no more than 45 pounds. 3.2.3 M60 PDISE inputs. The M60 PDISE shall have a single phase input capable of handling 60 A/P. 3.2.3.1 Input cir
9、cuit interrupter. The input circuit for the M60 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit. 3.2.3.1.1 Input connector. The M60 PDISE shall have a 60 ampere, single phase, male, input recepta
10、cle IAW 13229E6340. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-53126/4A PAGE 3 OF 7 3.2.4 M60 PDISE outputs The M60 PDISE shall have the following output circuits and connectors: Quantity Output Rating Ouput Connector P/N* 1 60 Amp, 1 ph
11、ase M90556C32405P 6 20 Amp, 1 phase M3406D16-10S *Note: See 3.3.16.1 in MIL-DTL-53126. 3.2.4.1 Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker interrupter. The circuit breaker shall act as a switch to activate/deactivate the circuit. Provided b
12、y IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-53126/4A PAGE 4 OF 7 3.2.5 Type IV accessories. The unit shall be provided with the following accessories: Quantity Description Reference* 1 Input interface cable assembly, rated at 60 amperes 3.3.18.1* 1
13、 60 A/P cable assembly 3.3.18.5* 3 20 A/P cable assemblies (25 0.25 feet long) 3.3.18.6* 3 20 A/P cable assemblies (50 0.25 feet long) 3.3.18.6* 2 Transition cable assemblies 3.3.18.8* 6 Cinching Strap 3.3.19.1* 2 Double strap assemblies 3.3.19.3* 1 Receptacle assembly 3.3.17* 1 In-Line GFCI 3.3.18.
14、10* 1 Container 2.1 *Note: See requirement paragraph referenced MIL-DTL-53126. CARRYINGSTRAPSCINCHINGSTRAPSCARRYINGSTRAPSMARKING TAG(WHITE)JOININGSTRAP1.50 STK10.0027.754.75 3x 1.50JOININGSTRAPProvided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-5
15、3126/4A PAGE 5 OF 7 BB LINE NEUT BB BB GND G2 A N G1 J2 OUTPUT FEED THRU J2G6GND J2A4LINE J2N4NEUT J2G6GND 60 A 1 PHASE INPUT J1 J1G6GND J1N4NEUT J1A4CB1 G1 N A G2 J1G6GND CB1 CB14LINE 20 A 1 PHASE OUTPUT J3 J3C12GND J3B12NEUT J3A12CB3 C B A CB3 CB312LINE 20 A 1 PHASE OUTPUT J5 J5C12GND J5B12NEUT J5
16、A12CB5 C B A CB5 CB512LINE CB8 J8 C B A OUTPUT 20 A 1 PHASE J8C12GND J8B12NEUT J8A12CB8 CB812LINE CB6 A B C J6 OUTPUT 20 A 1 PHASE J6A12CB6 J6B12NEUT J6C12GND CB612LINE CB4 A B C J4 OUTPUT 20 A 1 PHASE J4A12CB4 J4B12NEUT J4C12GND CB412LINE DS1NBB DS1CB1 DS1 LIGHT BRACKET CIRCUIT BREAKER MOUNTING PAN
17、EL TOP COVER CHASSIS GROUND J7 OUTPUT 20 A 1 PHASE CB7 CB712LINE C B A J5C12GND J7B12NEUT J7A12CB7 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-53126/4A PAGE 6 OF 7 3.3 This specification sheet had no superseding “base”. The original publi
18、cation of this specification was a performance specification that was used in-house by CR4. Since this specification is now a detailed military specification, this specification sheet is deemed necessary to capture the unique characteristics desired in the end item. 3.4 Changes from previous issues:
19、 Marginal notations are not used in this revision to identify changes with respect to the previous issue because this detail specification sheet although a part of the base document, was not published because it was a document with limited circulation and coordination that was used essentially by CR
20、4. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-53126/4A PAGE 7 OF 7 Concluding Material Custodian: Preparing Activity: Army - CR4 Army - CR4 (Project 6150-2012-013) Review Activities: DLA GS Note: The activities listed above were interest
21、ed in this document as of the date of this document. Since organization and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at https:/assist.dla.mil. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-