1、VIL-T-530bbB W 9999906 1990844 230 1 MIL-T-53066B 28 September 1994 SUPERSEDING MIL-T-53066A 8 May 1990 MILITARY SPECIFICATION TANK, FABRIC, COLLAPSIBLE, 5,000 BARREL, FUEL This specification is approved for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This s
2、pecification covers a 5,000 barrel capacity, collapsible, self-supporting, fuel storage tank, complete with fittings, accessories and emergency repair items. 2. APPLICABLE DOCUMENTS 2.1 Government documents. 2.1.1 Specifications, standards and handbooks. The following specifications, standards and h
3、andbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those listed in the issue of the Department of Defense Index of Specifications and Standards (DoDISS) and supplement thereto, cited in the solicitation (see 6.2) . SPEC
4、IFICATIONS FEDERAL A-A- 18 98 L-P-378 RR- C - 2 71 W-F-800 ww-v-35 ZZ-H-561 PPP-B-601 PPP-c-795 PPP-c-1797 PPP-T- 6 O Cushioning Material, Cellulosic, Packaging. Plastic, Sheet and Strip, Thin Gauge, Polyolefin. Chains and Attachments, Welded and Weldless. Fuel Oil, Diesel. lalve, Ball. Hose, Rubber
5、, and Hose Assemblies, Rubber, Smooth Bore, Water Suction and Discharge. Boxes, Wood, Cleated-Plywood. Cushioning Material, Packaging (Flexible Closed Cell Plastic Film for Long Shipping Cycle Applications). Cushioning Material, Resilient, Low Density, Unicellular, Polypropylene Foam. Tape: Packagin
6、g, Waterproof. I 1 Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be addressed to: US ARMY BELVOIR RDE CTR, ATTN AMSTA RBE, 10101 GRIDLEY RD STE 104, FT BELVOIR VA 22060-5818 by using the Standardization Docume
7、nt Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter. AMSC N/A FSC 5430 DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited. Licensed by Information Handling ServicesProvided by IHSNot for ResaleNo reproduction or networking permitted
8、 without license from IHS-,-,-MIL-T-53066B MILITARY MIL-C-104 MIL- P- 116 MIL-B-121 MIL-H- 370 MIL-T-5624 MIL-A-8625 MIL-T-22085 MIL-T-27730 MIL-F-46162 MIL-R-52255 MIL-V-58039 MIL-T-83133 STANDARDS - Crates, Wood: Lumber and Plywood Sheathed, Nailed and - Preservation, Methods of. - Barrier Materia
9、l, Greaseproofed, Waterproofed, Flexible. - Hose and Hose Assemblies, Nonmetallic: Rubber, Liquid - Turbine Fuel, Aviation, Grades JP-4, JP-5 and JP-5/JP-8 - Anodic Coatings, for Aluminum and Aluminum Alloys. - Tapes, Pressure-Sensitive, Adhesive, Preservation and - Tape, Antiseize, Polytetrafluoroe
10、thylene, with - Fuel, Diesel, Referee Grade. - Repair Kit and Repair Kit Components, for Collapsible - Valves, Gate, Rising Stem, Double Acting, Aluminum. - Turbine Fuels, Aviation, Kerosene Types, NATO F-34 Bolted. Fuel. ST. Sealing. Dispenser. Fabric Tanks, Drums, and Boats. (JP-8) and NATO F-35.
11、FEDERAL FED-STD-191 - Textile Test Methods. FED-STD-595 - Colors Used in Government Procurement. MIL I TARY MIL-STD-129 - MIL-STD-209 - MIL-STD-1186 - MS9021 - MS27022 - MS2 702 3 - MS27024 - MS27026 - MS2 7 02 7 - MS2 7 02 8 - MS27029 - MS2 7 03 O - MS29513 - Marking for Shipment and Storage. Sling
12、ing and Tiedown Provisions for Lifting and Tying Down Military Equipment. Cushioning, Anchoring, Bracing, Blocking and Waterproofing; with Appropriate Test Methods. Packing, Preformed, l10l1 Ring. Coupling Half, Quick Disconnect, Cam-Locking Type, Male, External Pipe Thread, Type III. Coupling Half,
13、 Quick Disconnect, Cam-Locking Type, Male, Flanged, Type IV. Coupling Half, Quick Disconnect, Cam-Locking Type, Female, Internal Pipe Thread, Type V. Coupling Half, Quick Disconnect, Cam-Locking Type, Female, External Pipe Thread, Type VII. Coupling Half, Quick Disconnect, Cam-Locking Type, Female,
14、Flanged, Type VIII. Coupling Half, Quick Disconnect, Cam-Locking Type, Cap, Dust, Type IX. Coupling Half, Quick Disconnect, Cam-Locking Type, Plug, Dust, Type X. Gasket-Coupling Half, Quick Disconnect, Cam-Locking Type. Packing, Preformed, Hydrocarbon Fuel Resistant llOtl Ring. (Unless otherwise ind
15、icated, copies of federal and military specifications and standards are available from: STDZN DCMNT ORDER DESK, BLDG 4D, 700 ROBBINS AVE, PHILADELPHIA, PA 19111-5094.) 2.2 Non-Government publications. The following documents form a part of this document to the extent specified herein. Uhless otherwi
16、se specified, the issues of the documents which are DoD adopted are those listed in the issue of the DoDISS cited in the solicitation. Unless otherwise specified, the issues of documents not listed in the DoDISS are the issues of the documents cited in the solicitation (see 6.2) Provided by IHSNot f
17、or ResaleNo reproduction or networking permitted without license from IHS-,-,-. MIL-T-53066B AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) B16.14 - Ferrous Pipe Plugs, Bushings, and Locknuts with Pipe Threads. B16.15 - Cast Bronze Thread ed Fitting Class 125 and 250. B18.2.1 - Square and Hex Bolts an
18、d Screws Inch Series. B18.2.2 - Square and Hex Nuts (Inch Series). B18.21.1 - Lock Washers. B18.22.1 - Plain Washers. H35.1 - Alloy and Temper Designation Systems for Aluminum. (Application for copies should be addressed to the AMERICAN NATIONAL STANDARDS INSTITUTE, 11 W 42ND ST, NEW YORK, NY 10036.
19、) AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) A 153 B 26 B 85 B 108 D 381 D 412 D 413 D 429 D 471 D 750 D 751 D 975 D 1149 D 1655 D 1729 D 2000 D 2565 - Zinc Coating (Hot-Dip) on Iron and Steel Hardware. - Aluminum-Alloy Sand Castings. - Aluminum-Alloy Die Castings. - Aluminum-Alloy Permanent
20、Mold Castings. - Existent Gum in Fuels by Jet Evaporation. - Rubber Properties in Tension. - Rubber Property - Adhesion to Flexible Substrate. - Rubber Property - Adhesion to Rigid Substrates. - Rubber Property - Effect of Liquids. - Rubber Deterioration in Carbon-Arc or Weathering Apparatus. - Coat
21、ed Fabrics. - Diesel Fuel Oils. - Rubber Deterioration - Surface Ozone Cracking in a Chamber. - Aviation Turbine Fuels. - Visual Evaluation of Color Differences of Opaque Materials. - Rubber Products in Automotive Applications. - Operating Xenon Arc-Type (Water-cooled) Light-Exposure Apparatus With
22、and Without Water for Exposure of Plastics. (Application for copies of ASTM documents should be addressed to: AMERICAN SOCIETY FOR TESTING however, conformance with these requirements shall hot be construed as justification for failure to meet other performance requirements of this specification. 3.
23、3 Materials. Materials shall be as specified in text and figures herein. 3.3.1 Material deterioration prevention and control. The tanks shall be fabricated from compatible materials, inherently deterioration resistant or treated to provide protection against the various forms of corrosion and deteri
24、oration that may be encountered in any of the applicable operating and storage environments to which the tanks may be exposed. 3.3.2 Recovered materials. For the purpose of this requirement, recovered materials are those materials which have been collected from solid waste and reprocessed to become
25、a source of raw materials, as distinguished from virgin raw materials. The metal components, pieces and parts incorporated in the tank may be newly fabricated from recovered materials to the maximum extent practicable, provided the tank produced meets all other requirements of this specification. Us
26、ed, rebuilt or remanufactured components, pieces and parts shall not be incorporated in the tanks. fabric shall have a retained breaking strength that is not less than 50 percent of its initial breaking strength, warp and fill. 3.3.3 Cloth. When tested as specified in 4.5.2.23, the cloth of the coat
27、ed 3.3.4 Coatins compounds. Elastomeric compound applied to the cloth and seam edge cover strips (if used) shall conform to the requirements of table I. . 4 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-flIL-T-530bbB 9999906 1990848 98b MIL-T-53066
28、B TABLE I. Characteristics of coatins compounds. I/ Test Property Original properties Tensile strength, initial Ultimate elongation Properties after fuel immersion in test fluid 2/ at 160 OF for 14 days Tensile strength retained Elongation retention Volume swell Properties after fuel extraction, dri
29、ed, and then immersed in distilled water at 160 OF for the following durations: a/ 14 days Tensile strength retention Elongation retention Volume swell 42 days Tensile strength retention Elongation retention Volume swell Resistance to light after 1500 hours accelerated weathering at 10% elongation A
30、/ Fuel contamination: !3/ Existent gum, unwashed Heptane washed gum Tensile strength retention Ozone resistance Requirements Test paragraph and ASTM test methods 1500 psi (min) 300% (min) D 412 D 412 80% (min) 80% (min) 25% (max) D 471 (para 14.1, 14.2, Ei 10. 1) 75% (min) 80% (min) io% (max) 70% (m
31、in) 75% (min) 10% (rnax) D 471 (para 14.1, 14.2, deionized water (20 t3 OC); cycle: 690 minutes light exposure, 30 minutes light and gray; black panel temperature 63 53 OC; relative humidity (45 15%). - 8/ Test method A specimen shall be conditioned for 14 days at a temperature of 104 13.6 OF (40 52
32、 OC) having a partial pressure of ozone of 50 milipascals. 3.3.5 Coated fabric. The processed coated fabric shall be free from blisters, pinholes, or signs of coating delamination. The processed coated fabric shall conform to the requirements of table II. TABLE II. Characteristics of coated fabric.
33、Test property Weight (oz/sq yd) Diffusion rate I/ fl oz/sq ft/24 hr, max. Tear strength, warp deionized water (20 13 OC); 690 minutes light exposure, 30 minutes light and gray; black panel temperature 63 +3 OC; relative humidity (45 15%). Coated fabric specimens shall have exterior coating (outside
34、of tank) facing the light. 5/ This requirement may be met by certification from the material manufacturer that the material provided has been subjected to, and passed the specified weather resistance test, and providing those test results for inclusion in the first article test report. 3.4 Tank cons
35、truction. The tank shall be fabricated from coated fabric as specified herein. The configuration and dimensions of the tank and the location of the fittings and handles shall be as shown in figure 1. Seams shall not coincide with tank fittings. The longitudinal seams of the tank top shall not coinci
36、de with the seams of the tank bottom at each end closure. Coated fabric panels may be spliced together; however, all splices shall be located on the bottom of the tank. All splices shall conform to requirements for seams as specified in 3.4.1. Splices in adjacent panels shall not coincide. On both t
37、he interior and exterior of the tank, all coated fabric, edges of seams, fabric flanges of fittings, and splices shall be covered to a thickness of not less than 10 mils with coating compound. All tank fittings shall be located a minimum of 8 inches away from any seam or splice. 3.4.1 Seams. All tan
38、k seams including the end closures, fabric flanges of fittings, fabric panel splices and the bonded areas of chafing and handle patches shall conform to the requirements of table III. Seams shall be designed and manufactured such that fluids cannot enter them during tank life. TABLE III. Characteris
39、tics of seams. Test Property Breaking strength: Initial, lb/in, min L/ After immersion in fuel 2/ at 160 OF for: 14 days, lb/in, min I/ After fuel extraction a/, dried, and immersed in distilled water at 160 OF for: 14 days, lb/in, min I/ 42 days, lb/in, min i/ I Reauirements * 600 450 450 400 Test
40、Paragraph or ASTM Test Method 4.5.2.15 and D 751 method B 4.5.2.15, D 751 method B, and D 471 (para. 15.2) 4.5.2.15, 4.5.2.19, D 751 method B, and D 471 (para 15.2) 4 -5.2.16 7 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-T-530bbB 999990b 1990
41、851 470 MIL-T-53066B TABLE III. Characteristics of seams. - (continued) Test Property Seam peel adhesion Initial, lb/in, min After immersion in fuel 2/ at 160 OF for: 14 days, lb/in, min After fuel extraction 3/, dried, and immersed in distilled water at 160 OF for: 14 days, lb/in, min 42 days, lb/i
42、n, min Resuirements 35 25 25 20 Test Paragraph or ASTM Test Method 4.5.2.15 and D 413 machine method 4.5.2.15, D 413 machine method, and D 471 (para 15.2) 4.5.2.15, 4.5.2.19, D 413 machine method, and D 471 (para 5.2) I/ All specimens must break in the coated fabric. Failure of any specimen in a sea
43、m area at any value shall constitute failure of this test. - 2/ Immersion test fluid shall be diesel fuel conforming to MIL-F-46162. - 3/ JP-5/JP-8 ST conforming to MIL-T-5624 will be used as extraction media. If JP-5/JP-8 ST is unavailable at a reasonable cost and within time constraints, the manuf
44、acturer can use JP-8 with enough BTX added to ensure aromatics equal or exceed 23 percent. 3.4.1.1 Lais joints and butt joints. Lap joints or butt joints shall be used to fabricate seams between adjacent panels and splices. Lap joints shall have a minimum overlap length of 3 inches. Lap joints shall
45、 have a gum strip or adhesive barrier centered over the inner and outer exposed coated fabric edge to prevent wicking through the fabric. Butt joints shall have a 3-inch wide (minimum) patch centered over the butt joint on both sides of the coated fabric. 3.4.2 Handles. Handles shall be bonded to th
46、e tank as shown in figure 1. The handles shall be U-shaped straps fabricated from nylon webbing or cloth and fastened to a coated fabric patch similar to the tank body material. The two ends of each strap shall be attached to each patch at points 12 inches 11 inch apart. The length of the strap betw
47、een the two points of attachment shall be 16 inches 11 inch. The patch and strap assembly shall be bonded to the bottom of the tank just below the peripheral fold line. The bonds between each handle patch assembly and the tank fabric shall be capable of withstanding perpendicular loads of 1,500 poun
48、ds without damage to the tank. They shall be approximately the same color as the tank. 3.4.3 Chafinq patches. The interior and exterior of the tank, opposite the location of each fitting shall be provided with bonded coated fabric chafing patches as shown in figure 1. The chafing patches shall be ma
49、de of the same coated fabric used to fabricate the tank. 3.4.4 Fittinqs 3.4.4.1 Fittinq type. The access door fitting and the vent and drain flange attachment shall be bonded to the coated fabric flange and shall be as specified herein and shall conform to the requirements of table IV. Fittings shall be compression type and shall be as shown in figures 3 and 6. The oval closure plate shall be as shown in figure 9. 8 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from