ARMY UFGS-09 83 13-2010 ACOUSTICAL WALL TREATMENT.pdf

上传人:花仙子 文档编号:449605 上传时间:2018-11-16 格式:PDF 页数:7 大小:30.90KB
下载 相关 举报
ARMY UFGS-09 83 13-2010 ACOUSTICAL WALL TREATMENT.pdf_第1页
第1页 / 共7页
ARMY UFGS-09 83 13-2010 ACOUSTICAL WALL TREATMENT.pdf_第2页
第2页 / 共7页
ARMY UFGS-09 83 13-2010 ACOUSTICAL WALL TREATMENT.pdf_第3页
第3页 / 共7页
ARMY UFGS-09 83 13-2010 ACOUSTICAL WALL TREATMENT.pdf_第4页
第4页 / 共7页
ARMY UFGS-09 83 13-2010 ACOUSTICAL WALL TREATMENT.pdf_第5页
第5页 / 共7页
亲,该文档总共7页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、*USACE / NAVFAC / AFCESA / NASA UFGS-09 83 13 (August 2010)-Preparing Activity: USACE SupersedingUFGS-09 83 13 (May 2009)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2010*SECTION TABLE OF CONTENTSDIVISION 09 - FINISHESSECTION 09 83 13ACOUSTICAL WALL TREATME

2、NT08/10PART 1 GENERAL1.1 REFERENCES1.2 SUBMITTALS1.3 SUSTAINABLE DESIGN CERTIFICATION1.4 DELIVERY, STORAGE, AND HANDLING1.5 WARRANTYPART 2 PRODUCTS2.1 FABRIC COVERED ACOUSTICAL WALL PANELS2.2 COLORPART 3 EXECUTION3.1 SURFACE CONDITIONS3.2 INSTALLATION3.3 CLEANING- End of Section Table of Contents -S

3、ECTION 09 83 13 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-09 83 13 (August 2010)-Preparing Activity: USACE SupersedingUFGS-09 83 13 (May 2009)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in ag

4、reement with UMRL dated July 2010*SECTION 09 83 13ACOUSTICAL WALL TREATMENT08/10*NOTE: This guide specification covers the requirements for fabric covered acoustical wall panel systems.Edit this guide specification for project specific requirements by adding, deleting, or revising text. For brackete

5、d items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of the

6、specification. A listing of technical proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to list the publications

7、 cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Arti

8、cle to automatically place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update SECTION 09 83 13 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-the issue dates.References not used in the text

9、 will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.*The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic

10、designation only.AMERICAN ASSOCIATION OF TEXTILE CHEMISTS AND COLORISTS (AATCC)AATCC TM 16 (1964; R 2004) Colorfastness to LightASTM INTERNATIONAL (ASTM)ASTM C 423 (2009a) Sound Absorption and Sound Absorption Coefficients by the Reverberation Room MethodASTM D 1117 (2001) Evaluating Nonwoven Fabric

11、sASTM D 5034 (2009) Breaking Strength and Elongation of Textile Fabrics (Grab Test)ASTM E 84 (2010) Standard Test Method for Surface Burning Characteristics of Building MaterialsGREENGUARD ENVIRONMENTAL INSTITUTE (GEI)GEI Greenguard Standards for Low Emitting ProductsINTERNATIONAL CODE COUNCIL (ICC)

12、ICC IBC (2009; Errata First Printing) International Building CodeSCIENTIFIC CERTIFICATION SYSTEMS (SCS)SCS Scientific Certification Systems (SCS)Indoor Advantage1.2 SUBMITTALS*NOTE: Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to

13、reflect only the submittals required for the project. Submittals should be kept to the minimum required for adequate quality control.A “G” following a submittal item indicates that the submittal requires Government approval. Some submittals are already marked with a “G”. Only delete an existing “G”

14、if the submittal item is not SECTION 09 83 13 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-complex and can be reviewed through the Contractors Quality Control system. Only add a “G” if the submittal is sufficiently important or complex in co

15、ntext of the project.For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the “G“ designation to indicate the approving authority. Codes for Army projects using the Resident Management System (RMS) are: “AE“ f

16、or Architect-Engineer; “DO“ for District Office (Engineering Division or other organization in the District Office); “AO“ for Area Office; “RO“ for Resident Office; and “PO“ for Project Office. Codes following the “G“ typically are not used for Navy, Air Force, and NASA projects.Choose the first bra

17、cketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects.*Government approval is required for submittals with a “G“ designation; submittals not having a “G“ designation are for Contractor Quality Control approval. information only. When used, a designa

18、tion following the “G“ designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:SD-02 Shop DrawingsApproved Detail Drawings; G; G, _SD-03 Product DataInstallationAcoustical Wall Panels; G; G, _C

19、ertificationSD-04 SamplesAcoustical Wall Panels; G; G, _SD-07 CertificatesAcoustical Wall Panels1.3 SUSTAINABLE DESIGN CERTIFICATIONProduct shall be third party certified by GEI Greenguard Indoor Air Quality Certified, SCS Scientific Certification Systems Indoor Advantage or equal. Certification sha

20、ll be performed annually and shall be current.1.4 DELIVERY, STORAGE, AND HANDLINGProtect materials delivered and placed in storage from the weather, humidity and temperature variations, dirt, dust, or other contaminants.SECTION 09 83 13 Page 4Provided by IHSNot for ResaleNo reproduction or networkin

21、g permitted without license from IHS-,-,-1.5 WARRANTYProvide manufacturers standard performance guarantees or warranties that extend beyond a one year period.PART 2 PRODUCTS2.1 FABRIC COVERED ACOUSTICAL WALL PANELS*NOTE: Drawings must show locations and dimensions of acoustical panels, details of jo

22、ints, base, head, and mounting details.The same or similar acoustical benefits can possibly be obtained by other means such as wall covering, etc.Omit the following items that do not meet project requirements.*Provide acoustical wall panels consisting of prefinished, factory assembled, seamless fabr

23、ic covered, fiber glass or mineral fiber core system as described below manufactured to the dimensions and configurations shown on the approved detail drawings; submit drawings showing plan locations, elevations and details of method of anchorage, location of doors and other openings, base detail an

24、d shape and thickness of materials. Perimeter edges shall be non-reinforced. reinforced by either an aluminum frame or a formulated resin edge hardener. Acoustical wall panels installed in non-sprinklered areas shall comply with the requirements of ICC IBC, Standard 42-2. Comply with EPA requirement

25、s in accordance with Section 01 62 35 RECYCLED / RECOVERED MATERIALS. Submit manufacturers descriptive data and catalog cuts; fabric and vinyl swatches, minimum 450 mm 18 inches wide by 600 mm 24 inches long 3 _ samples of each color range specified; and certificates of compliance from an independen

26、t laboratory accredited by the National Laboratory Accreditation Program of the National Institute of Standards. A label or listing from the testing laboratory will be acceptable evidence of compliance. Wall panels shall conform to the following:a. Panel Width: Widths shall be 600 750 1200 1500 mm 2

27、4 30 48 60 inches End panels may vary in width as necessary to cover wall Panel width shall be as detailed.b. Panel Height: Heights shall be 2400 2700 3000 mm 96 108 120 inches. Panels shall be field measured for custom fit to ceiling. Tolerance at floor to be as detailed. Panel height shall be as d

28、etailed.c. Thickness: Panel thickness shall be as required to meet the indicated NRC range _.d. Fabric Covering: Seamless non-woven, embossed texture, needle punched 100 percent polyester, minimum 0.034 kg/linear meter 11 ounces/linear yard. Tear strength shall be minimum 110 N 25 pounds machine dir

29、ection and minimum 178 N 40 pounds cross-machine direction in accordance with ASTM D 1117. Tensile strength shall be minimum 220 N 50 pounds machine direction and minimum 330 N 75 pounds cross-machine direction in SECTION 09 83 13 Page 5Provided by IHSNot for ResaleNo reproduction or networking perm

30、itted without license from IHS-,-,-accordance with ASTM D 5034. plain woven 2-ply 100 percent polyester, minimum 0.47 kg/linear meter 15 ounces/linear yard. Tear strength shall be minimum 129 N 29 pounds. Tensile strength shall be 667 N 150 pounds minimum in accordance with ASTM D 5034. perforated v

31、inyl covering with fabric backing, minimum 0.62 kg/linear meter 20 ounces/linear yard total weight. Fabric covering shall be stretched free of wrinkles and then bonded to the edges and back or bonded directly to the panel face, edges, and back of panel a minimum distance standard with the manufactur

32、er. Light fastness (fadeometer) shall be approximately 40 hours in accordance with AATCC TM 16.e. Fire rating for the complete composite system: Class A, 200 or less smoke density and flame spread less than 25, when tested in accordance with ASTM E 84.f. Substrate: Fiber glass or mineral fiber.g. No

33、ise Reduction Coefficient (NRC) Range: 0.50-0.60 0.80-0.90 _ ASTM C 423.h. Edge Detail: Half bevel Bevel Radius Square Mitered _ edge.i. Core Type: Standard acoustical High impact acoustical Acoustical/tackable _ core.j. Mounting: Acoustical panels shall be mounted by manufacturers standard conceale

34、d spline mechanical fasteners magnetic fasteners hook and loop adhesive mounting _.2.2 COLOR*NOTE: Editing of color reference sentence(s) must be coordinated with the Government. Generally Section 09 06 90 COLOR SCHEDULE or drawing is used when the project is designed by an Architect or Interior des

35、igner. Select color from manufacturers standard colors or identified as a manufacturers color in this specification only when the project is very simple and has minimal finishes.When the Government directs that color be located in the drawings add a note that states: “Where color is shown as being s

36、pecific to one manufacturer, an equivalent color by another manufacturer may be submitted for approval. Manufacturers and materials specified are not intended to limit the selection of equal colors from other manufacturers. The word “color“ as used herein includes surface color and pattern.“Prior to

37、 specifying a custom color finish, research to determine if additional cost and lead time is feasible. Note there is often a minimum order requirement; this requirement will also affect future orders.When a manufacturers name, stock number, pattern, SECTION 09 83 13 Page 6Provided by IHSNot for Resa

38、leNo reproduction or networking permitted without license from IHS-,-,-and color is used, be certain that the product conforms to this specification, as edited.*Color shall be in accordance with Section 09 06 90 COLOR SCHEDULE as indicated on the drawings selected from manufacturers standard colors

39、_. Color listed is not intended to limit the selection of equal colors from other manufacturers.PART 3 EXECUTION3.1 SURFACE CONDITIONSWalls shall be clean, smooth, oil free and prepared in accordance with panel manufacturers instructions. Do not begin installation until all wet work, such as, plaste

40、ring, painting, and concrete are completely dry.3.2 INSTALLATIONPanel installation shall be by personnel familiar with and normally engaged in installation of acoustical wall panels. Apply panels in accordance with the manufacturers installation instructions. Submit manufacturers installation instru

41、ctions and recommended cleaning instructions.3.3 CLEANINGFollowing installation, dirty or stained panel surfaces shall be cleaned in accordance with manufacturers instructions and left free from defects. Panels that are damaged, discolored, or improperly installed shall be removed and new panels provided as directed.- End of Section -SECTION 09 83 13 Page 7Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ARMY

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1