1、*USACE / NAVFAC / AFCESA / NASA UFGS-10 22 19 (August 2010)-Preparing Activity: USACE SupersedingUFGS-10 22 19 (May 2009)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2010*SECTION TABLE OF CONTENTSDIVISION 10 - SPECIALTIESSECTION 10 22 19DEMOUNTABLE MOVABLE
2、PARTITIONS08/10PART 1 GENERAL1.1 REFERENCES1.2 SYSTEM DESCRIPTION1.2.1 Fire-Resistance Rating and Burning Characteristics1.2.2 Acoustical Performance1.2.3 Structural Performance1.2.3.1 Transverse-Load Capacity1.2.3.2 Load-Bearing Capability1.2.3.3 Non-Load Bearing Capability1.2.4 Electrical and Comm
3、unication Capability1.3 SUBMITTALS1.4 QUALITY ASSURANCE1.4.1 Manufacturer Qualifications1.4.2 Sustainable Design Certification1.5 DELIVERY, STORAGE, AND HANDLING1.6 PROJECT/SITE CONDITIONS1.7 WARRANTYPART 2 PRODUCTS2.1 PARTITION TYPE2.2 MATERIALS AND COMPONENTS2.2.1 Panels2.2.2 Framing System2.2.3 G
4、lass and Glazing2.2.4 Doors and Frames2.2.5 Door Hardware2.2.6 Windows2.2.7 Base Trim2.3 FINISHESPART 3 EXECUTION3.1 EXAMINATION3.2 PREPARATIONSECTION 10 22 19 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-3.3 INSTALLATION3.3.1 Doors and Wind
5、ows3.3.2 Wall Base3.4 ADJUSTMENTS3.5 CLEANING3.6 PROTECTION- End of Section Table of Contents -SECTION 10 22 19 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-10 22 19 (August 2010)-Preparing Activity: USAC
6、E SupersedingUFGS-10 22 19 (May 2009)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2010*SECTION 10 22 19DEMOUNTABLE MOVABLE PARTITIONS08/10*NOTE: This guide specification covers the requirements for demountable and movable partitions.Edit this guide specific
7、ation for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments and suggestions on thi
8、s guide specification are welcome and should be directed to the technical proponent of the specification. A listing of technical proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Reques
9、t (CCR).*PART 1 GENERAL*NOTE: Demountable and movable partitions should be used in areas susceptible to future partition rearrangement. Compared to traditional drywall construction, installation of these partitions are faster and eliminate the cost and mess of cutting and fitting carpet and ceilings
10、 around fixed walls. They offer maximum flexibility and reusability to accommodate frequent and quick relocation of work without loss of materials, damage or modification to panels or to adjoining structures such as ceilings, fixed walls and floors. Movable partitions and some demountable partitions
11、 are non-progressive allowing the removal of individual panels from any location without disturbing adjoining units. The partitions are point accessible meaning instant access of SECTION 10 22 19 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-
12、panels allows for electrical, telephone and communication lines to be installed quickly and easily. Furniture support is an optional added feature that makes these partition systems similar to furniture systems panels.Partition layouts on the drawings must show partition dimensions, nominal sizes fo
13、r doors, glazing panels, sound-resistance and fire-resistance when required, details and any other information pertinent to partition layouts. Partition layout should be based on module configuration to allow for maximum reusability.Designer should require materials, products, and innovative constru
14、ction methods and techniques which are environmentally sensitive, take advantage of recycling and conserve natural resources. Many manufacturers panels and components are 95 to 100 percent recyclable and reusable.*1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text
15、 of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatical
16、ly place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print
17、process.*The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.ASTM INTERNATIONAL (ASTM)ASTM C 1396/C 1396M (2009a) Standard Specification for Gypsum BoardASTM E 119 (2009c) Standard Te
18、st Methods for Fire Tests of Building Construction and MaterialsASTM E 413 (2004) Rating Sound InsulationSECTION 10 22 19 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ASTM E 72 (2005) Conducting Strength Tests of Panels for Building Construc
19、tionASTM E 84 (2010) Standard Test Method for Surface Burning Characteristics of Building MaterialsASTM E 90 (2009) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and ElementsBIFMA INTERNATIONAL (BIFMA)BIFMA X5.6 (2003) Panel SystemsGREENGU
20、ARD ENVIRONMENTAL INSTITUTE (GEI)GEI Greenguard Standards for Low Emitting ProductsNATIONAL FIRE PROTECTION ASSOCIATION (NFPA)NFPA 70 (2008; TIA 08-1) National Electrical CodeSCIENTIFIC CERTIFICATION SYSTEMS (SCS)SCS Scientific Certification Systems (SCS)Indoor AdvantageUNDERWRITERS LABORATORIES (UL
21、)UL 1286 (2008; R thru 2010) Office Furnishings1.2 SYSTEM DESCRIPTION*NOTE: Performance requirements listed below are optional choices for designer; edit accordingly.*1.2.1 Fire-Resistance Rating and Burning CharacteristicsFire-resistance rating for partitions shall be one-hour _ and in conformance
22、with ASTM E 119. Partition system shall have a Class A (under 25) Flame Spread Rating in conformance with ASTM E 84.1.2.2 Acoustical PerformanceSound-rated partition assemblies shall have a minimum Sound Transmission Coefficient (STC) of 36 42 _. STC range shall be determined in accordance with Soun
23、d Transmission Test by Two-Room Method and reported in accordance with ASTM E 90 and ASTM E 413 for frequency data. Tested assembly shall have been assembled in the same manner that the partitions will be installed on the project.SECTION 10 22 19 Page 5Provided by IHSNot for ResaleNo reproduction or
24、 networking permitted without license from IHS-,-,-1.2.3 Structural Performance1.2.3.1 Transverse-Load CapacityDemountable partitions shall be able to sustain a 1200 Pa 5 psf minimum transverse loading support the furniture systems components with panel deflection no greater than 1/120th of the vert
25、ical span when tested in accordance with ASTM E 72.1.2.3.2 Load-Bearing CapabilityNot less than 136 kg 300 lb concentrated 0.041 kg/linear mm 3.2 lb/linear inch distributed _ proof load when tested according to BIFMA X5.6.1.2.3.3 Non-Load Bearing CapabilityWall system is designed for non-load bearin
26、g capability.1.2.4 Electrical and Communication CapabilityElectrical components, devices, and accessories shall meet requirements of UL 1286 and NFPA 70. The label or listing of Underwriters Laboratories, Inc. will be accepted as evidence that the material or equipment conforms to the applicable sta
27、ndards of that agency. In lieu of this label or listing, a statement from a nationally recognized, adequately equipped testing agency shall be submitted indicating that the items have been tested in accordance with he required procedures of UL and that the material and equipment comply with contract
28、 requirements. Electrical work shall conform to the requirements of Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM.1.3 SUBMITTALS*NOTE: Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the pr
29、oject. Submittals should be kept to the minimum required for adequate quality control.A “G” following a submittal item indicates that the submittal requires Government approval. Some submittals are already marked with a “G”. Only delete an existing “G” if the submittal item is not complex and can be
30、 reviewed through the Contractors Quality Control system. Only add a “G” if the submittal is sufficiently important or complex in context of the project.For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the
31、 “G“ designation to indicate the approving authority. Codes for Army projects using the Resident Management System (RMS) are: “AE“ for Architect-Engineer; “DO“ for District Office (Engineering Division or other organization in the District Office); “AO“ for Area Office; “RO“ for SECTION 10 22 19 Pag
32、e 6Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-Resident Office; and “PO“ for Project Office. Codes following the “G“ typically are not used for Navy, Air Force, and NASA projects.Choose the first bracketed item for Navy, Air Force and NASA projec
33、ts, or choose the second bracketed item for Army projects.*Government approval is required for submittals with a “G“ designation; submittals not having a “G“ designation are for Contractor Quality Control approval. information only. When used, a designation following the “G“ designation identifies t
34、he office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:SD-02 Shop DrawingsInstallationDrawings indicating plans and elevations of partitions, details of required supports, adjacent construction and finish trim, finis
35、h of miscellaneous components and accessories, and type of partition finish. Drawings shall include dimensions verifying conformance to life safety code and electrical switch, outlet, infeed and jumper placements.SD-03 Product DataPartition SystemWarrantyCertificationSD-04 SamplesPartition SystemThr
36、ee _ 200 x 200 mm 8 x 8 inch samples of partition showing partition construction and indication of materials proposed and method of attaching partition to walls, floor, and ceiling.Three _ color samples of all exposed finishes of panels and components.Mock-ups. After finish samples are approved, and
37、 prior to installation of panels, a minimum 2430 x 2430 mm 8 x 8 foot mock-up shall be provided for each color and type of panel. Once approved, the mock-up samples shall be used as a standard of workmanship within the facility. Remove mock-ups when directed. Approved mock-ups may become part of the
38、 completed work if approved by the Contracting Officer.SD-07 CertificatesFire-Resistance Rating and Burning CharacteristicsAcoustical PerformanceStructural PerformanceSECTION 10 22 19 Page 7Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-Test reports
39、 from an independent laboratory certifying that the partitions meet the specified fire-resistance rating and acoustical performance and structural performance.1.4 QUALITY ASSURANCE1.4.1 Manufacturer QualificationsManufacturer shall specialize in designing and manufacturing the type of partition spec
40、ified in this section, and shall have a minimum of 5 _ years of documented successful experience. Manufacturer shall have the facilities capable of meeting contract requirements, single-source responsibilities and warranty. Partition installer shall have a minimum of 5 _ years of documented successf
41、ul experience in the installation of partitions similar to the requirements of this section. When required by the manufacturer, panels shall be installed by an authorized dealer with a certified installation crew.1.4.2 Sustainable Design CertificationProduct shall be third party certified by GEI Gre
42、enguard Indoor Air Quality Certified, SCS Scientific Certification Systems Indoor Advantage or equal. Certification shall be performed annually and shall be current.1.5 DELIVERY, STORAGE, AND HANDLINGDeliver materials to project site in accordance with manufacturers instructions in original unopened
43、 and undamaged packages and stored in a clean, dry, and secure place free from damage during construction activities. Packages shall contain labels which indicate manufacturers name, brand name, size, finish and placement location.1.6 PROJECT/SITE CONDITIONSTemperature and humidity conditions within
44、 the area to receive partitions shall be maintained as close as possible to the final occupancy standards. A minimum of 16 degrees C 60 degrees F shall be maintained continuously. Installation shall not begin until the building envelope provides complete protection from the weather.1.7 WARRANTY*NOTE: When site assembled demountable partitions are specified, the following warranty paragraph may be deleted in lieu of being covered under the one year standard construction warranty.*Warrant the p