1、*USACE / NAVFAC / AFCESA / NASA UFGS-12 35 70 (August 2010)-Preparing Activity: USACE SupersedingUFGS-12 35 70 (February 2009)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2010*SECTION TABLE OF CONTENTSDIVISION 12 - FURNISHINGSSECTION 12 35 70MEDICAL AND DEN
2、TAL CASEWORK08/10PART 1 GENERAL1.1 REFERENCES1.2 SUBMITTALS1.3 SUSTAINABLE DESIGN CERTIFICATION1.4 DELIVERY, STORAGE, AND HANDLINGPART 2 PRODUCTS2.1 CASEWORK2.1.1 Medical Casework2.1.2 Dental Casework2.1.3 Dental Prosthetics Casework2.1.4 Countertops2.2 PLUMBING FIXTURESPART 3 EXECUTION3.1 INSTALLAT
3、ION3.1.1 Wall Hung Cabinets3.1.2 Floor Mounted Cabinets3.1.3 Countertops3.2 INSPECTION AND CLEANING- End of Section Table of Contents -SECTION 12 35 70 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-12 35 7
4、0 (August 2010)-Preparing Activity: USACE SupersedingUFGS-12 35 70 (February 2009)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2010*SECTION 12 35 70MEDICAL AND DENTAL CASEWORK08/10*NOTE: This guide specification covers the requirements for metal and wood ca
5、sework for medical and dental facilities.Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, wh
6、ether or not brackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of the specification. A listing of technical proponents, including their organization designation and telephone number, is on the Internet.Recommended
7、changes to a UFGS should be submitted as a Criteria Change Request (CCR).*PART 1 GENERAL*NOTE: This specification covers metal and wood casework, normally preassembled, for installation as fixed or built-in elements in medical and dental facilities. The “casework“ includes: Cabinets, singularly or i
8、n assemblies; treatment room units wardrobes; deck units; reagent racks; countertops and sink; plus their components; hardware and service fixture trim. All casework must be shown on the drawings.A schedule of casework, shown in alpha-numerical order, will be included on the drawings. Schedules will
9、 include the Joint Schedule Number (JSN) designator, and dimensions. The schedule or SECTION 12 35 70 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-elevations should indicate the number of shelves required. Joint Schedule Numbers (JSN) or the
10、 National Stock Numbers are specified in MIL-STD-1691. Any additional specially required casework items which are not covered by MIL-STD-1691 should be described herein and identified on the drawings and schedule.On the drawings, show:1. Sizes and spacing of casework units, plumbing fixtures and uti
11、lity outlets.2. Schedule of casework including all component parts and accessories.3. Details of connections and anchorage where special conditions exist. Size and spacing of anchors.*1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guide specification. T
12、he publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatically place the reference in the
13、Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.*The publications list
14、ed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.ASTM INTERNATIONAL (ASTM)ASTM C 920 (2008) Standard Specification for Elastomeric Joint SealantsGREENGUARD ENVIRONMENTAL INSTITUTE (GEI)GEI Greenguard S
15、tandards for Low Emitting ProductsSECTION 12 35 70 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-SCIENTIFIC CERTIFICATION SYSTEMS (SCS)SCS Scientific Certification Systems (SCS)Indoor AdvantageU.S. DEPARTMENT OF DEFENSE (DOD)MIL-STD-1691 (199
16、4; Rev F) Construction and Material Schedule for Military Medical and Dental Facilities1.2 SUBMITTALS*NOTE: Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the project. Submittals should be
17、 kept to the minimum required for adequate quality control.A “G” following a submittal item indicates that the submittal requires Government approval. Some submittals are already marked with a “G”. Only delete an existing “G” if the submittal item is not complex and can be reviewed through the Contr
18、actors Quality Control system. Only add a “G” if the submittal is sufficiently important or complex in context of the project.For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the “G“ designation to indicat
19、e the approving authority. Codes for Army projects using the Resident Management System (RMS) are: “AE“ for Architect-Engineer; “DO“ for District Office (Engineering Division or other organization in the District Office); “AO“ for Area Office; “RO“ for Resident Office; and “PO“ for Project Office. C
20、odes following the “G“ typically are not used for Navy, Air Force, and NASA projects.Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects.*Government approval is required for submittals with a “G“ designation; submittals not hav
21、ing a “G“ designation are for Contractor Quality Control approval. information only. When used, a designation following the “G“ designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:SD-02 Sho
22、p DrawingsApproved Detail Drawings; G; G, _Drawings showing layout of casework at 1:20 3/4 inch equals one SECTION 12 35 70 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-foot scale. Indicate details of construction and rough-in requirements.
23、Indicate whether cabinets are metal or wood, whether countertop is corrosion-resisting steel or plastic laminate, and whether sink is coated with modified epoxy resin polypropylene polyethylene or corrosion-resisting steel. Verify job condition affecting the work and obtain accurate field measuremen
24、ts for incorporation into drawings. Locate structural members, required utilities and services provided by other sections of this specification. Submit details and information necessary for fabrication and installation.SD-03 Product DataCaseworkManufacturers printed data, catalog cuts, and instructi
25、ons for installation and cleaning.SD-04 SamplesCasework; G; G, _Wall Hung Cabinets; G; G, _Floor Mounted Cabinets; G; G, _Countertops; G; G, _Laminated Plastic Sheets; G; G, _In lieu of individual samples, complete minimum size casework may be furnished as samples. Mock-up units are not acceptable.
26、Samples shall be of sufficient size to show color, pattern, and method of assembly.a. Countertop and backsplash - One section, containing both.b. Door and drawer front - One of each, with hardware mounted.c. Melamine plastic color samples approximately 50 by 75 mm 2 by 3 inch size.d. Stain/color sam
27、ples shall be approximately 50 by 75 mm 2 by 3 inch size.SD-07 CertificatesCertificationCasework1.3 SUSTAINABLE DESIGN CERTIFICATIONProduct shall be third party certified by GEI Greenguard Indoor Air Quality Certified, SCS Scientific Certification Systems Indoor Advantage or equal. Certification sha
28、ll be performed annually and shall be current.1.4 DELIVERY, STORAGE, AND HANDLINGDeliver casework to the jobsite in the original individual containers, complete with screws, keys, and instructions. Mark each container with the manufacturers name and catalog number. Casework shall be stored in an ade
29、quately ventilated, dry location that is free of dust, water, or other SECTION 12 35 70 Page 5Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-contaminates and in a manner to permit access for inspection and handling. Casework shall be handled careful
30、ly to prevent damage to the surfaces. Replace damaged items that cannot be restored to like-new condition.PART 2 PRODUCTS2.1 CASEWORK*NOTE: Joint schedule numbers used in MIL-STD-1691 provide the Military Medical Services a uniform basis for identifying casework items in medical and dental facilitie
31、s. Any items required which are not covered by MIL-STD-1691 should be described appropriately and identified on the drawings with a new assigned number.*Provide casework as scheduled on the approved detail drawings. The casework shall be factory fabricated of manufacturers standard sizes and finishe
32、s and shall conform to MIL-STD-1691, and the requirements specified below. Supplementary ordering data are as follows: _. Casework items are identified on drawings with numbers preceded by the letters “C“ and “D“. These numbers are Joint Schedule Numbers in MIL-STD-1691. Material finish and color sh
33、all be in accordance with Section 09 06 90 COLOR SCHEDULE _.2.1.1 Medical Casework*NOTE: Plastic laminated casework may be used in non corrosive areas such as hospital rooms and nursing stations. Corrosion resisting steel should be specified for areas, such as laboratories, where highly corrosive ch
34、emicals are handled. Enameled carbon steel casework should be utilized to the maximum practicable extent in lieu of corrosion-resistant steel.*Medical casework shall be baked enamel carbon steel corrosion resisting steel wood core or carbon steel covered with laminated plastic sheets. Color of finis
35、h shall be _ in accordance with color schedule as indicated selected by the Contracting Officer from the manufacturers standard colors.2.1.2 Dental Casework*NOTE: When selection is to be made from manufacturers standard samples, specify whether solids or woodgrains are required.*Dental operator case
36、work shall be wood core carbon steel covered with laminated plastic sheets. Pattern, color and finish of decorative laminated plastic for exteriors of casework shall be _ in accordance with color schedule as indicated selected by the Contracting Officer from the manufacturers standard color woodgrai
37、n samples.SECTION 12 35 70 Page 6Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.1.3 Dental Prosthetics CaseworkDental prosthetics casework shall be baked enamel carbon steel corrosion resisting steel. Color of finish shall be _ in accordance with
38、color schedule as indicated selected by the Contracting Officer from the manufacturers standard colors.2.1.4 CountertopsCountertops shall be corrosion-resisting steel plastic laminate covered plywood plastic laminate covered particleboard modified epoxy resin or resin coated laminated pressed wood f
39、iber.2.2 PLUMBING FIXTURESProvide faucet, trap and drain fittings, gas, air and vacuum cocks as required. Provide connection conforming to the requirements specified in Section 22 00 70 PLUMBING, HEALTHCARE FACILITIES.PART 3 EXECUTION3.1 INSTALLATIONCasework shall be located as indicated. The instal
40、lation of the casework shall not damage the work of other trades. The casework shall be secured in place in true alignment, level, and plumb. Units shall be secured with screws through backs to cleats that have been anchored to building structure with toggle or expansion bolts.3.1.1 Wall Hung Cabine
41、tsInstall wall-hung cabinets to support the weight of the cabinets plus the normally expected weight of the contents of the cabinets. Space fasteners 300 mm 12 inch on center using at least three bolts in each 900 or 1200 mm 3 or 4 foot unit width. Adjoining cabinets in an assembly shall be joined t
42、ogether at top and bottom with inconspicuous bolts or clips. Joints between the casework and wall surfaces which are not larger than the joints between casework sections shall be sealed flush with sealant conforming to ASTM C 920, Type M, Grade NS, Class 25, Use NT. Larger joints shall be closed wit
43、h filler strips of the same material and finish as adjacent casework. Filler strips shall be cut to the contour of the wall surface and secured to the casework with concealed nails or screws. Width of filler strips shall not exceed 150 mm 6 inch in width.3.1.2 Floor Mounted CabinetsSet floor-mounted
44、 metal cabinets on a common metal base or integral base, in assemblies up to 1800 mm 6 feet in length in rooms having concrete or resilient flooring. Bolt cabinets to bases at cabinet corners. Face metal bases with resilient material to match wall base in space where the cabinets are located. Fasten together adjoining cabinets at t