ASTM E119-2016a 9592 Standard Test Methods for Fire Tests of Building Construction and Materials《建筑结构和材料防火试验的标准试验方法》.pdf

上传人:jobexamine331 文档编号:526893 上传时间:2018-12-04 格式:PDF 页数:36 大小:543.69KB
下载 相关 举报
ASTM E119-2016a 9592 Standard Test Methods for Fire Tests of Building Construction and Materials《建筑结构和材料防火试验的标准试验方法》.pdf_第1页
第1页 / 共36页
ASTM E119-2016a 9592 Standard Test Methods for Fire Tests of Building Construction and Materials《建筑结构和材料防火试验的标准试验方法》.pdf_第2页
第2页 / 共36页
ASTM E119-2016a 9592 Standard Test Methods for Fire Tests of Building Construction and Materials《建筑结构和材料防火试验的标准试验方法》.pdf_第3页
第3页 / 共36页
ASTM E119-2016a 9592 Standard Test Methods for Fire Tests of Building Construction and Materials《建筑结构和材料防火试验的标准试验方法》.pdf_第4页
第4页 / 共36页
ASTM E119-2016a 9592 Standard Test Methods for Fire Tests of Building Construction and Materials《建筑结构和材料防火试验的标准试验方法》.pdf_第5页
第5页 / 共36页
亲,该文档总共36页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、Designation: E119 16a An American National StandardStandard Test Methods forFire Tests of Building Construction and Materials1This standard is issued under the fixed designation E119; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision,

2、 the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.INTRODUCTIONThe performance of

3、walls, columns, floors, and other building members under fire-exposureconditions is an item of major importance in securing constructions that are safe, and that are not amenace to neighboring structures or to the public. Recognition of this is registered in the codes ofmany authorities, municipal a

4、nd other. It is important to secure balance of the many units in a singlebuilding, and of buildings of like character and use in a community; and also to promote uniformityin requirements of various authorities throughout the country. To do this it is necessary that thefire-resistive properties of m

5、aterials and assemblies be measured and specified according to a commonstandard expressed in terms that are applicable alike to a wide variety of materials, situations, andconditions of exposure.Such a standard is found in the test methods that follow. They prescribe a standard exposing fire ofcontr

6、olled extent and severity. Performance is defined as the period of resistance to standard exposureelapsing before the first critical point in behavior is observed. Results are reported in units in whichfield exposures can be judged and expressed.The test methods may be cited as the “Standard Fire Te

7、sts,” and the performance or exposure shallbe expressed as “2-h,” “6-h,” “12-h,” etc.When a factor of safety exceeding that inherent in the test conditions is desired, a proportionalincrease should be made in the specified time-classification period.1. Scope*1.1 The test methods described in this fi

8、re-test-responsestandard are applicable to assemblies of masonry units and tocomposite assemblies of structural materials for buildings,including loadbearing and other walls and partitions, columns,girders, beams, slabs, and composite slab and beam assembliesfor floors and roofs. They are also appli

9、cable to other assem-blies and structural units that constitute permanent integralparts of a finished building.1.2 It is the intent that classifications shall register compara-tive performance to specific fire-test conditions during theperiod of exposure and shall not be construed as havingdetermine

10、d suitability under other conditions or for use afterfire exposure.1.3 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat andflame under controlled conditions, but does not by itselfincorporate all factors required for fire hazard or fire riskasse

11、ssment of the materials, products or assemblies underactual fire conditions.1.4 These test methods prescribe a standard fire exposurefor comparing the test results of building construction assem-blies. The results of these tests are one factor in assessingpredicted fire performance of building const

12、ruction and assem-blies. Application of these test results to predict the perfor-mance of actual building construction requires the evaluationof test conditions.1.5 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI

13、units that are provided for information onlyand are not considered standard.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is the1These test methods are under the jurisdiction ofASTM Committee E05 on FireStandards and are the direct respo

14、nsibility of Subcommittee E05.11 on FireResistance.Current edition approved July 1, 2016. Published July 2016. Originally approvedin 1917. Last previous edition approved in 2016 as E119 16. DOI: 10.1520/E0119-16A.These test methods, of which the present standard represents a revision, wereprepared b

15、y Sectional Committee on Fire Tests of Materials and Construction, underthe joint sponsorship of the National Bureau of Standards, theANSI Fire ProtectionGroup, and ASTM, functioning under the procedure of the American NationalStandards Institute.*A Summary of Changes section appears at the end of t

16、his standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1responsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.7

17、The text of this standard references notes and footnoteswhich provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be consideredas requirements of the standard.2. Referenced Documents2.1 ASTM Standards:2C569 Test Method for Indentation Hardness of

18、PreformedThermal Insulations (Withdrawn 1988)3D6513 Practice for Calculating the Superimposed Load onWood-frame Walls for Standard Fire-Resistance TestsE176 Terminology of Fire StandardsE177 Practice for Use of the Terms Precision and Bias inASTM Test MethodsE691 Practice for Conducting an Interlabo

19、ratory Study toDetermine the Precision of a Test MethodE814 Test Method for Fire Tests of Penetration FirestopSystemsE2226 Practice for Application of Hose Stream3. Terminology3.1 DefinitionsFor definitions of terms found in this testmethod, refer to Terminology E176.4. Significance and Use4.1 These

20、 test methods are intended to evaluate the durationfor which the types of building elements noted in 1.1 contain afire, retain their structural integrity, or exhibit both propertiesduring a predetermined test exposure.4.2 The test exposes a test specimen to a standard firecontrolled to achieve speci

21、fied temperatures throughout aspecified time period. When required, the fire exposure isfollowed by the application of a specified standard fire hosestream applied in accordance with Practice E2226. The testprovides a relative measure of the fire-test-response of compa-rable building elements under

22、these fire exposure conditions.The exposure is not representative of all fire conditions becauseconditions vary with changes in the amount, nature anddistribution of fire loading, ventilation, compartment size andconfiguration, and heat sink characteristics of the compartment.Variation from the test

23、 conditions or test specimenconstruction, such as size, materials, method of assembly, alsoaffects the fire-test-response. For these reasons, evaluation ofthe variation is required for application to construction in thefield.4.3 The test standard provides for the following:4.3.1 For walls, partition

24、s, and floor or roof test specimens:4.3.1.1 Measurement of the transmission of heat.4.3.1.2 Measurement of the transmission of hot gasesthrough the test specimen.4.3.1.3 For loadbearing elements, measurement of the loadcarrying ability of the test specimen during the test exposure.4.3.2 For individu

25、al loadbearing members such as beamsand columns:4.3.2.1 Measurement of the load carrying ability under thetest exposure with consideration for the end support conditions(that is, restrained or not restrained).4.4 The test standard does not provide the following:4.4.1 Information as to performance of

26、 test specimensconstructed with components or lengths other than those tested.4.4.2 Evaluation of the degree by which the test specimencontributes to the fire hazard by generation of smoke, toxicgases, or other products of combustion.4.4.3 Measurement of the degree of control or limitation ofthe pas

27、sage of smoke or products of combustion through thetest specimen.4.4.4 Simulation of the fire behavior of joints betweenbuilding elements such as floor-wall or wall-wall, etc., connec-tions.4.4.5 Measurement of flame spread over the surface of testspecimens.4.4.6 The effect on fire-resistance of con

28、ventional openingsin the test specimen, that is, electrical receptacle outlets,plumbing pipe, etc., unless specifically provided for in theconstruction tested. Also see Test Method E814 for testing offire stops.5. Test Specimen5.1 The test specimen shall be representative of the con-struction that t

29、he test is intended to assess, as to materials,workmanship, and details such as dimensions of parts, andshall be built under conditions representative of those appliedin building construction and operation. The physical propertiesof the materials and ingredients used in the test specimen shallbe det

30、ermined and recorded.5.2 The size and dimensions of the test specimen specifiedherein shall apply for classifying constructions of dimensionswithin the range employed in buildings. When the conditionsof use limit the construction to smaller dimensions, thedimensions of the test specimen shall be red

31、uced proportion-ately for a test qualifying them for such restricted use.5.3 Test specimens designed with a built-up roof shall betested with a roof covering of 3-ply, 15-lb (6.8-kg) type felt,with not more than 120 lb (54 kg) per square (100 ft2(9 m2)ofhot mopping asphalt without gravel surfacing.

32、Tests with thiscovering do not preclude the field use of other coverings witha larger number of plys of felt, with a greater amount of asphaltor with gravel surfacing.5.4 Roofing systems designed for other than the use ofbuilt-up roof coverings shall be tested using materials anddetails of construct

33、ion representative of field application.6. Protection and Conditioning of Test Specimen6.1 Protect the test specimen during and after fabrication toensure its quality and condition at the time of test. The test2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Custo

34、mer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3The last approved version of this historical standard is referenced onwww.astm.org.E119 16a2specimen shall not be tested until its required strength h

35、as beenattained, and, until an air-dry condition has been achieved inaccordance with the requirements given in 6.2 6.4. Protectthe testing equipment and test specimen undergoing the fire-resistance test from any condition of wind or weather that iscapable of affecting results. The ambient air temper

36、ature at thebeginning of the test shall be within the range of 50 to 90F (10to 32C). The velocity of air across the unexposed surface ofthe test specimen, measured just before the test begins, shallnot exceed 4.4 ft (1.3 m/s), as determined by an anemometerplaced at right angles to the unexposed sur

37、face. When me-chanical ventilation is employed during the test, an air streamshall not be directed across the surface of the test specimen.6.2 Prior to the fire-resistance test, condition test specimenswith the objective of providing moisture condition within thetest specimen representative of that

38、in similar construction inbuildings. For purposes of standardization, this condition isestablished at equilibrium resulting from conditioning in anambient atmosphere of 50 % relative humidity at 73F (Note1).6.2.1 With some constructions it is difficult or impossible toachieve such uniformity. Where

39、this is the case, test specimensare tested when the dampest portion of the test specimen, or theportion at 6-in. (152-mm) depth below the surface of massiveconstructions, has achieved a moisture content correspondingto conditioning to equilibrium with air in the range of 50 to75 % relative humidity

40、at 73 6 5F (23 6 3C).6.2.2 When evidence is shown that test specimens condi-tioned in a heated building will fail to meet the requirements of6.2 after a 12-month conditioning period, or in the event thatthe nature of the construction is such that it is evident thatconditioning of the test specimen i

41、nterior is prevented byhermetic sealing, the moisture condition requirements of 6.2are permitted to be waived, and either 6.2.2.1 or 6.2.2.2 shallapply.6.2.2.1 Alternative conditioning methods are permitted tobe used to achieve test specimen equilibrium prescribed in 6.2(Note 2), or6.2.2.2 The speci

42、men tested when its strength is at leastequal to its design strength after a minimum 28 day condition-ing period.6.3 Avoid conditioning procedures that will alter the struc-tural or fire-resistance characteristics of the test specimen fromthose produced as the result of conditiong in accordance with

43、procedures given in 6.2.6.4 Information on the actual moisture content and distri-bution within the test specimen shall be obtained within 72 hprior to the fire. Include this information in the test report (Note3).NOTE 1Arecommended method for determining the relative humiditywithin a hardened concr

44、ete test specimen with electric sensing elements isdescribed in Appendix I of the paper by Menzel, C. A., “A Method forDetermining the Moisture Condition of Hardened Concrete in Terms ofRelative Humidity,” Proceedings,ASTM, Vol 55, 1955, p. 1085.Asimilarprocedure with electric sensing elements is pe

45、rmitted to be used todetermine the relative humidity within test specimens made with othermaterials.With wood constructions, the moisture meter based on the electricalresistance method can be used, when appropriate, as an alternative to therelative humidity method to indicate when wood has attained

46、the propermoisture content. Electrical methods are described on page 12-2 of the1999 edition of the Wood Handbook of the Forest Products Laboratory,U.S. Department of Agriculture. The relationships between relativehumidity and moisture content are given in Table 3-4 on p. 3-7. Thisindicates that woo

47、d has a moisture content of 13 % at a relative humidityof 70 % for a temperature of 70 to 80F (21 to 27C).NOTE 2An example where alternative conditioning may be employedis where concrete specimens are conditioned at elevated temperatures in a“heated building” to more rapidly obtain the conditions de

48、scribed in 6.2.In such cases, temperatures other than 73F are used to reach a maximum50 % relative humidity.NOTE 3If the moisture condition of the test specimen is likely tochange drastically from the 72-h sampling time prior to test, the samplingshould be made not later than 24 h prior to the test.

49、7. Control7.1 Fire-Resistance Test:7.1.1 Time-Temperature Curve:7.1.1.1 The furnace temperatures shall be controlled tofollow the standard time-temperature curve shown in Fig. 1.The points on the curve that determine its character are:1000F (538C) at 5 min1300F (704C) at 10 min1550F (843C) at 30 min1700F (927C) at 1 h1850F (1010C) at 2 h2000F (1093C) at 4 h2300F (1260C) at 8 h or over7.1.1.2 For a more detailed definition of the time-temperature curve, see Appendix X1.NOTE 4Recommendations for Recording Fuel Flow to FurnaceBurners The following provide

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ASTM

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1