资源描述

1、ICS 13.220.50Brandverhalten von Baustoffen und Bauteilen Teil 8: KleinprfstandIn keeping with current practice in standards published by the International Organization for Standardization(ISO), a comma has been used throughout as the decimal marker.Ref. No. DIN 4102-8 : 2003-10English price group 05

2、 Sales No. 010508.04DEUTSCHE NORM October 2003 No part of this translation may be reproduced without the prior permission ofDIN Deutsches Institut fr Normung e.V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).Translation by DIN-Sp

3、rachendienst.In case of doubt, the German-language original should be consulted as the authoritative text.Fire behaviour of building materials and elementsPart 8: Small-scale test furnaceContinued on pages 2 to 4.SupersedesMay 1986 edition.4102-8ForewordThis standard has been prepared by Technical C

4、ommittee Brandverhalten von Baustoffen und Bauteilen Kleinprfstand of the Normenausschuss Bauwesen (Building and Civil Engineering Standards Committee).AmendmentsThis standard differs from the May 1986 edition in that details of the furnace have been changed and thestandard has been editorially revi

5、sed.Previous editionDIN 4102-8: 1986-05.All dimensions are in millimetres.ContentsPageForeword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6、. . . . . . . . . . . . . . 22 Normative references . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23.1 General . . . . . . . . . . . . . . . .

7、. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23.2 Fire chamber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23.3 Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8、. . . . . . 33.4 Measuring equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Test conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Page 2DIN 4102-8 : 2003-101 ScopeThis standard specifies a smal

9、l-scale furnace for determining specific fire protection properties (e.g. the heatreleased under test conditions, the thermal transmittance of mineral fibre inserts for fire barriers, fire behaviourof intumescent coatings) of building materials or elements. It does not cover test methods for classif

10、yingbuilding materials or elements.NOTE: Details of the type, dimensions, preparation and number of specimens, of their installation in the furnaceand of the test procedure are to be found in the standards or codes of practice in which the relevantrequirements are specified (e.g. DIN 4102-1, DIN 180

11、89-1, Richtlinien fr Prfung und Zulassung von dmm-schichtbildenden Brandschutzbeschichtungen auf Stahlbauteilen zum Nachweis der Feuerwiderstands-klasse F 30 nach DIN 4102-2 (Codes of practice for testing and approval of intumescent coatings for veri-fying conformance to DIN 4102-2, class F 30 fire

12、resistance).2 Normative referencesThis standard incorporates, by dated or undated reference, provisions from other publications. These norma-tive references are cited at the appropriate places in the text, and the titles of the publications are listed below.For dated references, subsequent amendment

13、s to or revisions of any of these publications apply to thisstandard only when incorporated in it by amendment or revision. For undated references, the latest edition ofthe publication referred to applies.DIN 4102-1 Fire behaviour of building materials and elements Classification of building materia

14、ls Require-ments and testingDIN 4102-2 Fire behaviour of building materials and elements Building elements Concepts, requirementsand testingDIN 4787-1 Atomizing oil burners Concepts, safety requirements, testing and markingDIN 18089-1 Fire barriers Mineral fibre slabs for use as inserts for fire doo

15、rs Requirements and testingDIN 43729 Measurement and control Electrical temperature sensors Connection heads for thermocouplethermometers and resistance thermometersDIN 51603-1 EL type fuel oils Requirements and testingDIN EN 590 Automotive fuels Diesel Requirements and test methodsRichtlinien fr Pr

16、fung und Zulassung von dmmschichtbildenden Brandschutzbeschichtungen auf Stahlbau-teilen zum Nachweis der Feuerwiderstandsklasse F 30 nach DIN 4102-21)Stahl-Eisen-Werkstoffblatt (Iron and steel material specification) 917 Keramische feuerfeste Werkstoffe Schamottesteine fr allgemeine industrielle Ei

17、nsatzzwecke (Steingruppe A bis 45% Al2O3) (Refractory materials Refractory bricks for industrial purposes (brick group A, containing up to 45% Al2O3)2)3 Furnace3.1 GeneralThe furnace consists of a fire chamber, a burner and measuring equipment, together with any additionalequipment required, such as

18、 a heating element (fitted opposite the burner). It shall be set up in an enclosedspace (test room).3.2 Fire chamberThe dimensions of the fire chamber and its floor, ceiling, walls and openings shall be as shown in figure 1. Itswalls shall be made of A353) refractory bricks having a density of 1,9 k

19、g/dm3to 2,1 kg/dm3, fitted in a steelframework. The ceiling and the floor shall be of refractory concrete having a density of 2 kg/dm3to 2,2 kg/dm3.The outside of the furnace may be clad with sheet steel about 2 mm thick, with thermal insulation beingoptionally provided between the furnace wall and

20、the cladding.There shall no be more than one opening for inserting a specimen in each longitudinal wall and in the ceiling.No more than two closable inspection openings, each having a maximum clear area of 100 cm2, may beprovided. The flue gas outlet shall be designed to produce a gauge pressure in

21、the fire chamber of up to 12 Paafter the first five minutes of testing.1) Issued by Deutsches Institut fr Bautechnik, Kolonnenstr. 30 L, 10829 Berlin, Germany.2) Issued by Verlag Stahleisen mbH, P.O. Box 105164, 40042 Dsseldorf, Germany.3) See Stahl-Eisen-Werkstoffblatt 917.Page 3DIN 4102-8 : 2003-1

22、01) View does not show either a cover plate or a thermocouple.Key1 To smoke extractor with butterfly valve2 Sheathed thermocouple3 Burner opening4 Pressure tapping, (15 t 5) mm inside diameterFigure 1: Diagram of furnace showing possible thermocouple arrangement3.4 Measuring equipmentA thermocouple

23、having a closed sheath, an outside diameter of 3 mm and a protective tube as shown in figure 2shall be used to measure the temperature in the furnace, the sheath and tube being steel not susceptible to scaleformation. It shall be inserted into the furnace so that the measuring point is at a distance

24、 of (100 t 5) mm fromthe centre of the specimen surface.A steel tube having an inside diameter of (15 t 5) mm and fitted as shown in sections A-A and C-C in figure 1shall be used to measure the static pressure in the furnace.3.3 BurnerThe burner used shall be an atomizing oil burner producing a cont

25、inuous flame (e.g. DIN 4787-1 burner).Section A ASection B BSection C C View X1)Page 4DIN 4102-8 : 2003-10Key1 Type A connection head as in DIN 437292 Threaded socket3 Protective tube4 Sheathed thermocouple with thermocouple insulated from sheath5 Insulating jacket of 16 mm outside diameter, 5 mm in

26、side diameter and 100 mm long made of ceramicinsulating material6 Mineral fibre cordFigure 2: Thermocouple4 Test conditionsOnly one specimen shall be inserted during each test, the other furnace openings being sealed with a refractoryconcrete block of the same thickness and density as the wall or ce

27、iling of the furnace.The temperature in the test room shall not drop below 15 C or exceed 25 C for at least 24 hours prior to thetest.The furnace shall be heated with EL type fuel oil as in DIN 51603-1 or diesel fuel as in DIN EN 590. After the firstfive minutes of testing, the temperature in the furnace shall not differ by more than t 15 K from the curve shownin the relevant application standard (e.g. from the standard time-temperature curve specified in DIN 4102-2).The test shall be performed at a gauge pressure of (10t 2) Pa reached after the first five minutes of testing.