资源描述

1、AMSC N/A FSC 6250 INCH-POUND MIL-DTL-16377/81 18 December 2008 DETAIL SPECIFICATION SHEET FIXTURES, LIGHTING; BALLAST, FOR ONE 17-WATT T8 FLUORESCENT LAMP This specification is approved for use by the Naval Sea Systems Command, Department of the Navy, and is available for use by all Departments and

2、Agencies of the Department of Defense. The requirements for acquiring the product described herein shall consist of this specification sheet and MIL-DTL-16377. All dimensions in inches. For tolerances, other than specified herein, see 3.5.2 of MIL-DTL-16377. FIGURE 1. Ballast for one 17-watt T8 fluo

3、rescent lamp. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-16377/81 2 REQUIREMENTS: DESIGN: Electrical rating: 17 watts, 120 volts, 60 hertz. Power factor: 90 percent. Efficiency: 80 percent. Circuit design: Ballast circuit shall incorpora

4、te intergraded electronic starter for lamp per-heat starter circuit. Dimension and configurations: See figure 1. Assembly: The ballast shall consist of a laminated iron core and coil. Impregnating: Ballast circuitry shall be housed in thermoset plastic potting shell and potted with epoxy. DESIGNATIO

5、N AND MARKING: One Type I label, equipment identification, reference MIL-DTL-16377 figure 11, as shown in figure 1. EXAMINATIONS AND TESTS: Examinations and tests shall be as specified in MIL-DTL-16377 and the following: First article testing/inspection: See table II. Comparison inspection: See tabl

6、e II. Conformance inspection: See MIL-DTL-16377. Inspection of product for delivery: Examination See MIL-DTL-16377. Conformance test See MIL-DTL-16377. Examination for preparation of delivery See MIL-DTL-16377. GENERAL INFORMATION: Table I. Standard parts. Table II. First article tests. TABLE I. Sta

7、ndard parts. Name Military p/n or specification Remarks Ballast, 17-watt T8 fluorescent lamp, standard M16377/81-001 Thermoplastic insulation Ballast, 17-watt T8 fluorescent lamp, high temperature M16377/81-002 Silicone glass insulation Provided by IHSNot for ResaleNo reproduction or networking perm

8、itted without license from IHS-,-,-MIL-DTL-16377/81 3 TABLE II. First article tests and comparison inspection for ballast.1/Test Requirement Test method Remarks Examination 3.13 4.5 - Operation 3. 4.8.1 -Electromagnetic Interference 3.6.14 4.8.16 - Electrical equipment interface testing requirements

9、: MIL-STD-1399-300 MIL-STD-1399-300 MIL-STD-1399-300 2/,3/Dielectric withstanding voltage 3.6.15 4.8.2 4/ Insulation resistance 3.6.16 4.8.3 4/ Shock 3.5.12 4.8.7 4/ Vibration 3.5.13 4.8.8 4/ Dielectric withstanding voltage 3.6.15 4.8.2 4/ Insulation resistance 3.6.16 4.8.3 4/ Noise 3.5.14 4.8.9 - P

10、erformance a. Power output b. Regulation c. Voltage drop across ballast d. Ballast efficiency e. Ballast power factor 5/ 6/ 7/ NOTES: 1/Requirements and test methods use MIL-DTL-16377. 2/If less, then 1KVA exception not applicable for input waveform THD. 3/Solid state components shall be subject to

11、250 positive spikes and 250 negative spikes (500 total spikes), one spike per minute, using testing method identified in MIL-STD-1399-300. 4/Tests shall be performed in the order specified. 5/The performance of the ballast shall be in accordance with the requirements listed in the applicable paragra

12、ph of ANSI C82.2. 6/Test procedure for performance shall be as follows: a. Performance tests shall be made in accordance with ANSI C82.2. b. Fluorescent lamp reference ballasts shall be in accordance with ANSI C82.3. c. Lamp shall conform with ANSI C78.2. d. Voltage across starter terminals and acro

13、ss ballast, when supplying a reference lamp, shall be measured. 7/Sample lot size for inspection shall consist of five ballast units. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-16377/81 4 Custodians: Preparing Activity: Army CR4 Navy SH

14、Navy SH (Project 6250-2006-004) Air Force 99 Review Activities: Navy AS, CG Air Force 03 DLA GS2 GSA FAS NOTE: The activities listed above were interested in this document as of the date of this document. Since organizations and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at http:/assist.daps.dla.mil. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-