1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFebruary 10, 20151UL 2879Outline of Investigation for Nitrogen Generator Units for Use with Dry PipeSprinkler SystemsIssue No. 1February 10, 2015Summary of TopicsThis First Issue of the Outline o
2、f Investigation for Nitrogen GeneratorUnits for Use with Dry Pipe Sprinkler Systems, UL 2879, is being issued toadd requirements to cover nitrogen generator units intended to provide asource of nitrogen for pressuring dry type sprinkler systems in thestandby condition. These units include an air com
3、pressor, a means toseparate nitrogen from air, and the associated controls for operating theunit.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrigh
4、ts, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2015 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFEBRUARY 10, 2015UL 28792No Tex
5、t on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of Measurement .54 Undated References 5CONSTRUCTION5 General 5PERFORMANCE6 General 67 Nitrogen Concentration Test 68 30-Day Perfo
6、rmance and Operation Test 7MANUFACTURING AND PRODUCTION TESTS9 Air compressor and receiver 810 Nitrogen Generator Unit 8MARKING11 General .8INSTALLATION AND MAINTENANCE INSTRUCTIONS12 General .9FEBRUARY 10, 2015 UL 2879 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION
7、WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover nitrogen generator units for use in dry type fire sprinkler systems. Thisequipment is intended for installation in accordance with the manufacturers installation instructions andthe applicable requirements of the following sta
8、ndards:a) Standard for the Installation of Sprinkler Systems, ANSI/NFPA 13.b) Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies,ANSI/NFPA 13R.c) Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings andManufactured Homes. ANSI/NFPA 1
9、3Dd) National Electrical Code, ANSI/NFPA 70.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this Outline shall comply with therequirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteri
10、stic not required in the application of the component in theproduct covered by this Outline, orb) Is superseded by a requirement in this Outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomplete in constru
11、ction features or restricted in performance capabilities.Such components are intended for use only under limited conditions, such as temperatures not exceedingspecified limits, and shall be used only under those specific conditions.FEBRUARY 10, 2015UL 28794UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR
12、FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL3 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appearing in the requirem
13、ents of this Outline shall beinterpreted as referring to the latest edition of that code or standard.CONSTRUCTION5 General5.1 A nitrogen generator unit shall include the following equipment:a) Air compressor,b) A means to separate nitrogen from air using technology such as membrane or pressureswing
14、absorption and associated pre-filtering elements,c) Control units, andd) Air or nitrogen receiver or both an air and nitrogen receiver, if the nitrogen generatorcapacity is greater than 5.5 ft3/min (156 l/min) at 10 psig (0.7 bar).5.2 An air compressor shall be permitted to be shipped separately fro
15、m the equipment described in 5.1b) 5.1 d) where instructions are provided for proper assembly at the installation location. See 12.1.5.3 The air compressor and associated nitrogen generator equipment covered by this Outline shallcomply with the construction requirements of the Standard for Motor Ope
16、rated Compressors, VacuumPumps and Painting Equipment, ANSI/UL 1450 as applicable to use in sprinkler systems.5.4 Pressure vessels shall be permitted to comply with the applicable design requirements of the UnitedStates Department of Transportation or Canadian Transport Commission as a shipping cont
17、ainer in lieuof complying with the American Society of Mechanical Engineers (ASME) requirements referenced inANSI/UL 1450.5.5 Nitrogen generator control units covered by this Outline shall comply with the applicable constructionrequirements of the Standard for Industrial Control Panels, UL 508A.5.6
18、If the equipment to remove oxygen from air is within an enclosure, such as a control panel, a meansshall be provided to prevent the creation of an enriched oxygen concentration within the enclosure suchas the use of a ventilation fan or external discharge port.FEBRUARY 10, 2015 UL 2879 5UL COPYRIGHT
19、ED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULPERFORMANCE6 General6.1 The air compressor and associated nitrogen generator equipment covered by this Outline shallcomply with the applicable performance requirements of ANSI/UL 1450 as applicable to use in
20、 sprinklersystems.6.2 Pressure vessels shall be permitted to comply with the applicable performance requirements of theUnited States Department of Transportation or Canadian Transport Commission as a shipping containerin lieu of complying with the ASME requirements referenced in ANSI/UL 1450.6.3 Nit
21、rogen generator control units covered by this Outline shall comply with the applicable performancerequirements of the Standard for Industrial Control Panels, UL 508A.7 Nitrogen Concentration Test7.1 A nitrogen generator unit shall produce at least 98 percent nitrogen within 10 seconds after purgingo
22、f the downstream containment system when tested in accordance with 7.2 7.5.7.2 The nitrogen concentration test is to be conducted using a representative sample of each nitrogengenerator model in an ambient environment of 75 10F (24 5C), and within the manufacturersspecifications for the upstream and
23、 downstream pressures for the nitrogen separation element.7.3 A zirconium oxide analyzer, calibrated to measure oxygen or nitrogen concentrations within 0.2percent of actual concentration, shall be used to determine the nitrogen concentration. Prior to testing, themeasuring equipment shall be calibr
24、ated at both a nominal 2 percent and atmospheric oxygen (nominal20.9%) levels. Alternative nitrogen concentration measuring equipment shall be permitted to be used if itcan be demonstrated to provide equivalent accuracy.7.4 For nitrogen generators using membrane separation technology, the nitrogen c
25、oncentration is to bemeasured immediately downstream of the membrane. The unit is to be operated and provisions made forimmediate purging of the piping downstream of the membrane. The test is to be conducted for not lessthan 1 minute after purging. The pressures upstream and downstream of the membra
26、ne, and the time toachieve at least 98 percent nitrogen after purging, are to be recorded.7.5 For nitrogen generators using pressure swing absorption separation technology, the nitrogenconcentration is to be measured in a nitrogen receiver tank. The unit is to be operated and provisionsmade for full
27、y purging the nitrogen receiver tank. The test is to be conducted for not less than 1 minuteafter purging. The pressures upstream and downstream of the pressure swing absorption element, andthe time to achieve at least 98 percent nitrogen after purging are to be recorded.FEBRUARY 10, 2015UL 28796UL
28、COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL8 30-Day Performance and Operation Test8.1 During and after 30 days of operation, a nitrogen generator unit shall produce at least 98 percentnitrogen when tested in accordance with 8.2 8.5.8.2 The 3
29、0-day performance and operation test is to be conducted using a representative sample of eachnitrogen generator model in an ambient environment of 75 10F (24 5C) and a relative humidity of notless than 50 percent. The unit is to be operated under the following conditions:a) The inlet pressure to the
30、 nitrogen separation element shall be the maximum specified by themanufacturer.b) The pressure downstream of the nitrogen separation element shall be within the rangespecified by the manufacturer for system starting and shutoff. If the system is not provided witha nitrogen receiver tank, the downstr
31、eam pressure range is to be 30 psig (2 bar) to 40 psig (2.7bar).c) The duty cycle shall be not less than 50 percent.d) The average nitrogen generation rate generated during each period of operation shall not beless than the rate specified by the manufacturer for the unit.8.3 A zirconium oxide analyz
32、er calibrated to measure oxygen or nitrogen concentrations within 0.2percent of actual concentration shall be used to determine the nitrogen concentration. Prior to testing, themeasuring equipment shall be calibrated at both a nominal 2 percent and atmospheric oxygen (nominal20.9%) levels. Alternati
33、ve nitrogen concentration measuring equipment shall be permitted to be used if itcan be demonstrated to provide equivalent accuracy.8.4 For nitrogen generators using membrane separation technology, the nitrogen concentration is to bemeasured immediately downstream of the membrane. The unit is to be
34、operated with provisions made forpurging the downstream piping to facilitate unit cycling. The average nitrogen generation rate during theoperating cycle shall be determined and shall not be less than the rate specified in 8.2 d). The on/off cycletimes, pressures upstream and downstream of the membr
35、ane, and the nitrogen concentration level duringeach operating cycle are to be recorded. Repair or maintenance procedures for the nitrogen generator unitare not permitted to be performed during this test period.8.5 For nitrogen generators using pressure swing absorption separation technology, the ni
36、trogenconcentration is to be measured in a nitrogen receiver tank. The unit is to be operated and provisionsmade for fully purging the nitrogen receiver tank. Provisions shall then be made for tank purging tofacilitate unit cycling. The average nitrogen generation rate during the operating cycle sha
37、ll be determinedand shall not be less than the rate specified in 8.2 d). The on/off cycle times, pressures upstream anddownstream of the pressure swing absorption element, and the nitrogen concentration level during eachoperating cycle are to be recorded. Repair or maintenance procedures for the nit
38、rogen generator unit arenot permitted to be performed during this testing.FEBRUARY 10, 2015 UL 2879 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMANUFACTURING AND PRODUCTION TESTS9 Air compressor and receiver9.1 Each air compressor and air
39、/nitrogen receiver shall be comply with the applicable production testingrequirements of ANSI/UL 1450 and the nitrogen generator control units shall comply with the applicableproduction testing requirements of the Standard for Industrial Control Panels, UL 508A.9.2 A pressure vessel produced in acco
40、rdance with the requirements of the United States Department ofTransportation or Canadian Transport Commission shall be tested in accordance with the applicablerequirements.10 Nitrogen Generator Unit10.1 Each nitrogen generator unit shall be tested in accordance with Section 7, Nitrogen Concentratio
41、nTest, to determine that 98% nitrogen is produced. This test shall be permitted to be conducted using afactory air compressor that is not intended to be supplied with the unit.10.2 Each nitrogen generator unit shall be tested for leakage at the normal operating pressures usingcalibrated leak detecto
42、rs, leak detector compounds, or other means that provide equivalent results.MARKING11 General11.1 Each nitrogen generator unit shall be legibly and permanently marked with the following:a) The manufacturers or private labelers name or identifying symbol,b) A distinctive product identification design
43、ation, andc) Serial number.11.2 If a nitrogen generator unit is manufactured at more than one factory, each unit shall have adistinctive permanent marking to identify it as the product of a particular factory.FEBRUARY 10, 2015UL 28798UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR
44、DISTRIBUTION WITHOUT PERMISSION FROM ULINSTALLATION AND MAINTENANCE INSTRUCTIONS12 General12.2 Nitrogen generator units shall be provided with installation and maintenance instructions that includeat least the following items:a) Detailed instructions for properly installing the units.b) If the air c
45、ompressor is provided separately, detailed instructions for properly connecting theair compressor to the nitrogen generator unit.c) Detailed instructions for maintaining the unit including maintenance required to maintain thedesired level of nitrogen within the system.d) Reference to the need for pr
46、oper ventilation and installation in accordance with OSHAregulations to avoid an excessive concentration of oxygen in an area.e) Reference to the need for periodic or continuous monitoring of the nitrogen purityimmediately downstream of the nitrogen separation element and within the sprinkler system
47、 toverify that 98 percent nitrogen is being provided.f) Reference to installation and use in accordance with NFPA 13; and inspection, testing andmaintenance in accordance with the Standard for the Inspection, Testing and Maintenance ofWater-Based Fire Protection Systems, ANSI/NFPA 25.FEBRUARY 10, 2015 UL 2879 9UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFEBRUARY 10, 2015UL 287910No Text on This Page
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1