1、3535789 0320303 843 = Veterans Administration Washington, DC 20420 H-08-3 VA CONSTRUCTION STANDARD 801-4 July 15, 1987 RACEWAYS IN FLUOROSCOPIC, RADIOGRAPHIC, AND DEEP THERAPY ROOMS 1. A universal x-ray raceway system shall be provided in the radiographic, fluoroscopic and deep therapy rooms. Racewa
2、y size and layout shall be adequate to accommodate equipment of any of the major manufacturers. Floor slab shall be depressed sufficiently to accommodate the raceways. Raceway systcm layout for projects shall be indicated on the preliminary drawings. For additional information, see VA Handbook H-08-
3、4, “Standard Details,” Volume I, Architec- tural”. I 2. In existing hospitals where it is not feasible to provide a universal x-ray raceway system in the floor slab, point to point conduit system for fluoroscopic, radiographic and deep therapy rooms shall be run below floor or ceiling slab. Holes in
4、 slab shall be lined with lead sleeves, properly caulked and flanged to assure the required x-ray protection. RESCISSION: ,VA Construction Standard 801-4, dated November 2, 1964. p7p-7 G.E. NEUMANN Director, Office of Facilities Distribution: RPC: 0830 FD Printing Dare: 7/87 -7 3801 015473 e3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-