1、 Tentative Interim Amendment NFPA 101Life Safety Code2015 Edition Reference: 11.8.5 TIA 15-4 (SC 16-8-17 / TIA Log #1217) Pursuant to Section 5 of the NFPA Regulations Governing the Development of NFPA Standards, the National Fire Protection Association has issued the following Tentative Interim Ame

2、ndment to NFPA 101, Life Safety Code, 2015 edition. The TIA was processed by the Technical Committee on Fundamentals and the Correlating Committee on Safety to Life, and was issued by the Standards Council on August 4, 2016, with an effective date of August 24, 2016. A Tentative Interim Amendment is

3、 tentative because it has not been processed through the entire standards-making procedures. It is interim because it is effective only between editions of the standard. A TIA automatically becomes a public input of the proponent for the next edition of the standard; as such, it then is subject to a

4、ll of the procedures of the standards-making process. 1. Revise Subsection 11.8.5 to read as follows: 11.8.5 Emergency and Standby Power. 11.8.5.1 Emergency lighting in accordance with Section 7.9 shall be provided. 11.8.5.2 Emergency power requirements for electric fire pumps shall be in accordance

5、 with NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection. 11.8.5.3 Emergency power for detection, alarm, and communications systems shall be in accordance with NFPA 72, National Fire Alarm and Signaling Code. 11.8.5.4 Requirements for standby power shall be as specified i

6、n 11.8.5.4.1 through 11.8.5.4.4. 11.8.5.4.1 Type 60, Class 1, Level 1, standby power in accordance with NFPA 110, Standard for Emergency and Standby Power Systems, shall be provided. 11.8.5.4.2 The standby power system shall have a capacity and rating sufficient to supply all required equipment. 11.

7、8.5.4.3 Selective load pickup and load shedding shall be permitted in accordance with NFPA 70, National Electrical Code. 11.8.5.4.4 The standby power system shall be connected to the following: (1) Jockey pump, except as otherwise provided in 40.4.2 for special-purpose industrial occupancies (2) Air

8、 compressor serving dry-pipe and pre-action systems, except as otherwise provided in 40.4.2 for special-purpose industrial occupancies (3) Emergency command center equipment and lighting (4) Not less than one elevator serving all floors, with standby power transferable to any elevator (5) Mechanical

9、 equipment for smokeproof enclosures (6) Mechanical equipment required to conform with the requirements of Section 9.3 (7) Stairway video monitoring equipment as required by 11.8.8 Issue Date: August 4, 2016 Effective Date: August 24, 2016 (Note: For further information on NFPA Codes and Standards, please see www.nfpa.org/docinfo) Copyright 2016 All Rights Reserved NATIONAL FIRE PROTECTION ASSOCIATION