1、 Errata NFPA 101Life Safety Code2015 Edition Reference: 28.2.3.2 Errata No.: 101-15-3 The Committee on Residential Occupancies notes the following error in the 2015 edition of NFPA 101, Life Safety Code. 1. Add 28.2.3.2 and renumber remaining paragraphs. This text was inadvertently omitted from the

2、First and Second Draft and is to read as follows: 28.2.3 Capacity of Means of Egress. 28.2.3.1 The capacity of means of egress shall be in accordance with Section 7.3. 28.2.3.2 Street floor exits shall be sufficient for the occupant load of the street floor plus the required capacity of stairs and r

3、amps discharging onto the street floor. 28.2.3.2* 28.2.3.3* Corridors, other than those within individual guest rooms or individual guest suites, shall be of sufficient width to accommodate the required occupant load and shall be not less than 44 in. (1120 mm). A.28.2.3.2 A.28.2.3.3 The exemption co

4、ntained in 28.2.3.2 28.2.3.3 applies to corridors within an individual room or suite and does not apply where a suite can be subdivided and rented separately. . Issue Date: September 8, 2014 (Note: Electronic products and pamphlet reprints may have this errata incorporated. For current information about the NFPA Codes and Standards, including this errata, please see www.nfpa.org/codelist) Copyright 2014 All Rights Reserved NATIONAL FIRE PROTECTION ASSOCIATION