REG UFGS-26 56 19 00 40-2013 ROADWAY LIGHTING.pdf

上传人:吴艺期 文档编号:1019663 上传时间:2019-03-21 格式:PDF 页数:11 大小:52.54KB
下载 相关 举报
REG UFGS-26 56 19 00 40-2013 ROADWAY LIGHTING.pdf_第1页
第1页 / 共11页
REG UFGS-26 56 19 00 40-2013 ROADWAY LIGHTING.pdf_第2页
第2页 / 共11页
REG UFGS-26 56 19 00 40-2013 ROADWAY LIGHTING.pdf_第3页
第3页 / 共11页
REG UFGS-26 56 19 00 40-2013 ROADWAY LIGHTING.pdf_第4页
第4页 / 共11页
REG UFGS-26 56 19 00 40-2013 ROADWAY LIGHTING.pdf_第5页
第5页 / 共11页
点击查看更多>>
资源描述

1、*USACE / NAVFAC / AFCESA / NASA UFGS-26 56 19.00 40 (May 2013)-Preparing Activity: NASA SupersedingUFGS-26 56 19.00 40 (November 2008)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2013*SECTION TABLE OF CONTENTSDIVISION 26 - ELECTRICALSECTION 26 56 19.00 40R

2、OADWAY LIGHTING05/13PART 1 GENERAL1.1 REFERENCES1.2 SUBMITTALS1.3 ADMINISTRATIVE REQUIREMENTSPART 2 PRODUCTS2.1 SYSTEM DESCRIPTION2.2 STREET-LIGHTING LUMINAIRES2.2.1 Roadway Luminaire Components2.2.2 End-Mounted High-Intensity-Discharge (HID) Luminaires2.2.3 Side-Mounted (HID) Luminaires2.2.4 Lamp B

3、allasts2.2.4.1 Multiple-Circuit Ballasts2.2.4.2 Series Circuit Transformers2.2.5 Lamps2.2.5.1 (HID) Lamps and Ballasts2.2.5.2 Low Pressure Sodium2.2.6 Side-Mounted Incandescent Luminaires2.2.7 Incandescent LampsPART 3 EXECUTION3.1 INSTALLATION3.1.1 End-Mounted High-Intensity-Discharge (HID) Luminair

4、es3.1.2 Side-Mounted (HID) Luminaires3.1.3 Side-Mounted Incandescent Luminaires3.2 FIELD TESTING- End of Section Table of Contents -SECTION 26 56 19.00 40 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-26 5

5、6 19.00 40 (May 2013)-Preparing Activity: NASA SupersedingUFGS-26 56 19.00 40 (November 2008)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2013*SECTION 26 56 19.00 40ROADWAY LIGHTING05/13*NOTE: This guide specification covers the requirements for highway an

6、d roadway lighting luminaires.Drawings should show details of each street lighting fixture with letter designation keyed to the drawings and electrical symbols describing the type, style, class, kind, and size of fixture as follows:Roadway lighting fixtures including luminaires for IES as listed in

7、IES RP-8, “Lighting Distribution Patterns.“Coordinate this section with UFGS Section 26 09 23.00 40 LIGHTING CONTROL DEVICES and UFGS Section 26 56 13.00 40 LIGHTING POLES AND STANDARDS.Roadway-lighting standards and fixture details on drawings should describe, in plan and elevation, the type and ki

8、nd of pole, bracket, luminaire, base, and foundation required for installation at the location indicated. Elevation details should indicate height of pole, bracket-spread length, luminaire, depth of foundation, anchor bolts, underground conduit connections, ground rods, and ground connections. Plan

9、views should indicate foundation configuration, conduit stub-ups, base dimensions, and bolt circles. Foundation detail drawings should accurately describe the nature and properties of soil surrounding foundations for the support of lighting standards.Foundations for installation of area, flood light

10、ing, roadway lighting, and security lighting standards and fixtures in filled locations may require modification to resist horizontal movement without permanent set under stipulated wind loads.Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this gui

11、de specification or preparing new project SECTION 26 56 19.00 40 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-specification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For

12、bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments, suggestions and recommended changes for this guide specification are welcome and should be submitted as

13、a Criteria Change Request (CCR).*NOTE: TO DOWNLOAD UFGS GRAPHICSGo to http:/www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf.*NOTE: This section contains the following sketches (Graphics) and are available in metric (SI) and U.S. Customary (IP) system dimensions. Sketch titles and style numbers are unchanged

14、for both types. The metric values indicated are a conversion of U.S. Customary (IP) system dimensions.Do not include list of sketches, or sketches themselves, in project specifications. Use luminaire sketches as details on drawings whenever possible. If special features are required, do not modify s

15、ketches, but indicate these changes as notes in fixture schedule. The “XL“ style numbers and dates should remain on the drawing details.Sketch No. TitleXL-1 Roadway and Area LightXL-4 Roadway and Area LightXL-6 Area and Street Lighting Cutoff LuminaireXL-13 thru 19 Reserved for Future Exterior Lumin

16、airesNOTE: Do not include this index in project specification.*NOTE: Show the following information on the drawings or specify in the project specifications:a. Luminaire schedule and indicate pertinent information; i.e., mounting, lamps, ballasts, and voltage.1. Type of luminaire;2. Voltage, wattage

17、, and frequency rating required;SECTION 26 56 19.00 40 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-3. Accessories required, such as photocell, time switches, and auxiliary lamps;4. Location of poles or standards;5. Referenced sketch; and6.

18、Extent and location of the work to be accomplished and wiring and equipment necessary for a complete installation.*NOTE: Demolition work that involves disposal of fluorescent and HID lamps and ballasts requires the use of Section 02 84 16 HANDLING OF LIGHTING BALLASTS AND LAMPS CONTAINING PCBs AND M

19、ERCURY.*PART 1 GENERAL*NOTE: If Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS is not included in the project specification, applicable requirements there from should be inserted and the following paragraph deleted.*Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS applies

20、 to work specified in this section.1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use

21、the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text automatically be

22、deleted from this section of the project specification when you choose to reconcile references in the publish print process.*The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.SECTIO

23、N 26 56 19.00 40 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IES)IES RP-8 (2000; Errata 2004; R 2005; Errata 2007) Roadway LightingNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)ANSI A

24、NSLG C78.42 (2009) For Electric Lamps: High-Pressure Sodium LampsANSI C136.11 (2006) American Standard for Roadway Lighting Equipment Series Sockets and Series Sockets ReceptaclesANSI C136.15 (2011) American National Standard for Roadway Lighting Equipment - High-Intensity-Discharge and Low-Pressure

25、 Sodium Lamps in Luminaires - Field IdentificationANSI C136.2 (2004; R 2009) American National Standard for Roadway and Area Lighting Equipment: Luminaires Voltage ClassificationANSI C136.3 (2005; R 2009) American National Standard for Roadway and Area Lighting Equipment Luminaire AttachmentsANSI C1

26、36.6 (2004) American National Standard for Roadway Lighting Equipment - Metal Heads and Reflector Assemblies - Mechanical and Optical InterchangeabilityANSI C136.9 (2003) American National Standard for Roadway and Area Lighting Equipment - Socket Support Assemblies for Metal Heads - Mechanical Inter

27、changeabilityANSI C82.4 (2002) American National Standard for Ballasts for High-Intensity-Discharge and Low-Pressure Sodium (LPS) Lamps (Multiple-Supply Type)ANSI C82.9 (2010) American National Standard for High-Intensity Discharge and Low-Pressure Sodium Lamps, Ballasts and Transformers - Definitio

28、nsU.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)21 CFR 1040 Performance Standards for Light-Emitting Products1.2 SUBMITTALS*NOTE: Review Submittal Description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals SECTION 26 56

29、19.00 40 Page 5Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-required for the project. Keep submittals to the minimum required for adequate quality control.A “G” following a submittal item indicates that the submittal requires Government approval.

30、Some submittals are already marked with a “G”. Only delete an existing “G” if the submittal item is not complex and can be reviewed through the Contractors Quality Control system. Only add a “G” if the submittal is sufficiently important or complex in context of the project.For submittals requiring

31、Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the “G“ designation to indicate the approving authority. Codes for Army projects using the Resident Management System (RMS) are: “AE“ for Architect-Engineer; “DO“ for District Offic

32、e (Engineering Division or other organization in the District Office); “AO“ for Area Office; “RO“ for Resident Office; and “PO“ for Project Office. Codes following the “G“ typically are not used for Navy, Air Force, and NASA projects.Choose the first bracketed item for Navy, Air Force and NASA proje

33、cts, or choose the second bracketed item for Army projects.*Government approval is required for submittals with a “G“ designation; submittals not having a “G“ designation are for Contractor Quality Control approval.for information only. When used, a designation following the “G“ designation identifi

34、es the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:SD-01 Preconstruction SubmittalsMaterial, Equipment, and Fixture Lists.Equipment and Performance DataSD-02 Shop DrawingsStreet-Lighting LuminairesInstallatio

35、n DrawingsSD-03 Product DataStreet-Lighting FixturesStreet-Lighting LuminairesSD-06 Test ReportsOperational TestsSECTION 26 56 19.00 40 Page 6Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-SD-07 CertificatesLighting-Distribution Certificates1.3 ADMI

36、NISTRATIVE REQUIREMENTSSubmit the following information at the Preconstruction Meeting:a. Material, Equipment, and Fixture Lists for highway and roadway lighting fixtures including manufacturers style or catalog numbers, specification and drawing reference numbers, warranty information, and fabricat

37、ion site informationb. Equipment and Performance Data for highway and roadway lighting systems consisting of life test, system functional flows, safety features, mechanical automated details, automatic interlocks, and such features as electrical system protective device ratingsc. Lighting-distributi

38、on Certificates showing compliance with the following requirement: lighting-distribution curves for each type of fixture prepared, utilizing the fixture manufacturers own facilities or those of an independent nationally recognized laboratory, in accordance with the standard procedure developed by th

39、e Illuminating Engineering Society.PART 2 PRODUCTS*NOTE: Revise as necessary to meet project requirements.*2.1 SYSTEM DESCRIPTIONProvide street-lighting fixtures, equipped with lamps. Furnish fixtures complete with wiring and mounting devices ready for installation at the locations indicated.Submit

40、Installation Drawings for the highway and roadway lighting systems. Indicate on drawings overall physical features, dimensions, ratings, service requirements, and weight of equipment.2.2 STREET-LIGHTING LUMINAIRESProvide enclosed and gasketed vaportight street-lighting luminaires in accordance with

41、IES RP-8 for Types I, II, III, IV, and V lighting-distribution patterns.*NOTE: Select street-lighting luminaires, ballasts, and lamps from the following parts to suit project requirements.Factors affecting the selection of luminaire types include the following:Fixture efficiency is the percent of av

42、ailable lumens from the light source that emits from the fixture. The most efficient fixture should be SECTION 26 56 19.00 40 Page 7Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-selected commensurate with the other design requirements.The spacing t

43、o mounting height ratio (S/MH) indicates how far apart the fixtures can be placed in relation to their mounting height. This ratio should be available in the fixture manufacturers literature. A medium-to-wide distribution of light from the fixture should be selected. Fewer fixtures are required using the larger, more efficient light sources. Overlapping