1、SSPC-SP 1 April 23, 20151SSPC: The Society for Protective CoatingsSurface Preparation Standard No. 1Solvent Cleaning1. Scope1.1 This standard defines the end-condition of a metal surface from which visible deposits of oil, grease, and other visible contaminants have been removed in preparation for s
2、ubsequent application of protective coatings or for the use of additional methods to prepare the surface for the application of coatings. The standard also includes requirements for materials and procedures necessary to achieve and verify the end condition. 2. Definition2.1 When viewed without magni
3、fication, a solvent-cleaned surface shall be free of visible oil, grease, dust, dirt, drawing and cutting compounds, and other visible soluble contaminants. “Visible” means detectable with normal or corrected normal vision without the use of additional test equipment (see Note 6.1). 2.2 For the purp
4、ose of this standard, a “solvent” is defined as any liquid or vapor, permitted by the owner of the item being cleaned and used in compliance with all health, safety and environmental regulations applicable at the job site, that will dissolve or emulsify visible deposits of soluble contaminants on th
5、e surface. Examples of solvents include: water, emulsion or alkaline cleaners, and hydrocarbons. 3. Surface Preparation Before and After Solvent Cleaning3.1 Before solvent cleaning, remove visible foreign matter (other than grease and oil) by one or a combination of the following manual methods: bru
6、shing with stiff fiber or wire brushes, or scraping. 3.2 Remove localized deposits of oil or grease by scraping. Remove the remaining visible oil or grease by any of the methods listed in Section 4.Immediately before using additional methods of surface preparation or immediately prior to coating app
7、lication if additional surface preparation is not required, the surface shall meet requirements of Section 2.1. 4. Methods of Solvent Cleaning4.1 Apply the solvent to the surface by spraying or using rags or brushes wetted with approved solvent. Wipe or scrub the surface with rags or brushes wetted
8、with solvent.1Use clean solvent and clean rags or brushes for the final rinsing or wiping. 4.2 Use stabilized chlorinated hydrocarbon solvents to perform vapor degreasing.4.3 Immerse completely in a tank or tanks of solvent. For the last immersion, use solvent that will not deposit residual contamin
9、ants on the surface being cleaned. 4.4 Apply emulsion or alkaline cleaners as described in Sections 4.1 through 4.3. After treatment, wash the surface with surface preparation water2or steam to remove visible residual contaminants. 4.5 Steam clean, using detergents or cleaners and follow by steam or
10、 surface preparation water wash to remove visible residual contaminants. 5. Disclaimer5.1 This is a consensus standard developed by SSPC: The Society for Protective Coatings. While every precaution is taken to ensure that all information furnished in SSPC standards is as accurate, complete, and usef
11、ul as possible, SSPC cannot assume responsibility nor incur any obligation resulting from the use of any materials, coatings, or methods specified herein, or of the specification or standard itself.5.2 This standard does not attempt to address problems concerning safety associated with its use. The
12、user of this standard, as well as the user of all products or practices described herein, is responsible for instituting appropriate 1 Local regulations or owner restrictions may prohibit the use of certain solvents. If coating is to be applied following solvent cleaning, the coating manufacturer sh
13、ould be consulted for recommended solvents. 2 The SSPC/NACE waterjetting standards (SSPC-SP WJ-1, 2, 3 and 4/NACE WJ-1, 2, 3, and 4) define surface preparation water (SP water) as “water of sufficient purity and quality that it does not prevent the surface being cleaned from achieving the specified
14、degree of surface cleanliness or nonvisible contamination criteria when contained in the procurement documents.”SSPC-SP 1April 23, 20152health and safety practices and for ensuring compliance with all governmental regulations.6. NotesNotes are not requirements of this standard. 6.1 Additional Verifi
15、cation Methods: Project specifications may require visual verification to be supplemented by methods including but not limited to the options listed below for the visual detection and verification methods defined in Section 2.1. Areas subject to verification by these methods should be identified pri
16、or to solvent cleaning.6.1.1 Wipe Test: A clean dry white rag is wiped across the dry cleaned area(s) and examined for visible residue. 6.1.2 Ultraviolet Light: The cleaned area(s) are examined for the presence of fluorescing hydrocarbon residues using ultraviolet light.36.1.3 Water-Break Test: The
17、cleaned area(s) are examined in accordance with ASTM F22, “Standard Test Method for Hydrophobic Surface Films by the Water-Break Test.”46.1.4 Surface Dust Test: The cleaned area(s) are examined in accordance with ISO 8502-3, “Preparation of steel surfaces before application of paint and related prod
18、uctsTests for the assessment of surface cleanliness, Part 3: Assessment of dust on steel surfaces prepared for painting (pressure-sensitive tape method).”5An acceptable dust class should be established prior to conducting surface dust tests. 3 SSPC TU 11, “Inspection of Fluorescent Coating Systems”
19、provides guidance on inspection techniques and recommended personal protective equipment.4 ASTM International, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. For referenced ASTM standards, visit the ASTM website, . For Annual Book of ASTM Standards volume information, refer to the standard
20、s Document Summary page on the ASTM website.5 International Organization for Standardization (ISO), Case Postale 56, Geneva CH-1211, Switzerland. ISO standards may also be obtained through the American National Standards Institute (ANSI) at Copyright SSPC standards, guides, and technical reports are
21、 copyrighted world-wide by SSPC: The Society for Protective Coatings. Any photocopying, re-selling, or redistribution of these standards, guides, and technical reports by printed, electronic, or any other means is strictly prohibited without the express written consent of SSPC: The Society of Protective Coatings and a formal licensing agreement.