UL 555-2006 UL Standard for Safety Fire Dampers (Seventh Edition Reprint with Revisions Through and Including October 21 2016)《阻燃器》.pdf

上传人:eveningprove235 文档编号:1068301 上传时间:2019-04-02 格式:PDF 页数:50 大小:782.23KB
下载 相关 举报
UL 555-2006 UL Standard for Safety Fire Dampers (Seventh Edition Reprint with Revisions Through and Including October 21 2016)《阻燃器》.pdf_第1页
第1页 / 共50页
UL 555-2006 UL Standard for Safety Fire Dampers (Seventh Edition Reprint with Revisions Through and Including October 21 2016)《阻燃器》.pdf_第2页
第2页 / 共50页
UL 555-2006 UL Standard for Safety Fire Dampers (Seventh Edition Reprint with Revisions Through and Including October 21 2016)《阻燃器》.pdf_第3页
第3页 / 共50页
UL 555-2006 UL Standard for Safety Fire Dampers (Seventh Edition Reprint with Revisions Through and Including October 21 2016)《阻燃器》.pdf_第4页
第4页 / 共50页
UL 555-2006 UL Standard for Safety Fire Dampers (Seventh Edition Reprint with Revisions Through and Including October 21 2016)《阻燃器》.pdf_第5页
第5页 / 共50页
点击查看更多>>
资源描述

1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 555 Fire DampersUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR D

2、ISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Fire Dampers, UL 555 Seventh Edition, Dated July 12, 2006 Summary of Topics This revision to ANSI/UL 555 is being issued to remove the reference to the withdrawal date of UL 873 and to address universal upkeep of UL Standards for Safe

3、ty. These revisions are considered to be non-substantive and not subject to ULs STP process. Text that has been changed in any manner or impacted by ULs electronic publishing system is marked with a vertical line in the margin. Changes in requirements are marked with a vertical line in the margin an

4、d are followed by an effective date note indicating the date of publication or the date on which the changed requirement becomes effective. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanica

5、l photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable for any s

6、pecial, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of such damage.

7、 In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, damage, clai

8、m, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standard on the purchasers computer system. The requirements in this Standard are now in effect, except for those paragraphs, sections, tables, gures, and/or

9、 other elements of the Standard having future effective dates as indicated in the note following the affected item. The prior text for requirements that have been revised and that have a future effective date are located after the Standard, and are preceded by a SUPERSEDED REQUIREMENTS notice. MAY 2

10、1, 2014 UL 555 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MAY 21, 2014 UL 555 tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL JULY 12, 2006 (Title Pag

11、e Reprinted: May 21, 2014) 1 UL 555 Standard for Fire Dampers The third edition was titled Fire Dampers and Ceiling Dampers. First Edition October, 1968 Second Edition July, 1973 Third Edition May, 1979 Fourth Edition January, 1990 Fifth Edition May, 1995 Sixth Edition June, 1999 Seventh Edition Jul

12、y 12, 2006 This ANSI/UL Standard for Safety consists of the Seventh Edition including revisions through May 21, 2014. The most recent designation of ANSI/UL 555 as an American National Standard (ANSI) occurred on November 5, 2013. ANSI approval for a standard does not include the Cover Page, Transmi

13、ttal Pages, Title Page, or effective date information. The Department of Defense (DoD) has adopted UL 555 on July 29, 1994. The publication of revised pages or a new edition of this Standard will not invalidate the DoD adoption. Comments or proposals for revisions on any part of the Standard may be

14、submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at http:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should be altered in any way. All of ULs S

15、tandards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2014 UNDERWRITERS LABORATORIES INC. ANSI/UL 555-2013UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL N

16、OVEMBER 5, 2013 FIRE DAMPERS - UL 555 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope 4A 2 General 5 2.1 Components .5 2.2 Units of measurement .6 2.3 Undated references .6 3 Glossary .6 CO

17、NSTRUCTION 4 General 7 5 Heat Responsive Devices 7 6 Sleeves 8 7 Protection Against Corrosion 12 8 Actuators .13 PERFORMANCE 9 General .13 10 Fire Endurance and Hose Stream Test 15 10.1 Conditions of acceptance .15 10.2 Test assemblies 17 10.3 Control and conduct of re test 20 11 Cycling Test 20C 12

18、 Salt-Spray Exposure Test 20D 13 Spring Closing Force Test .21 14 Dynamic Closure Test .21 14.1 General .21 14.2 Method .22 14.3 Velocity prole testing for multiple section assembly 24 15 Duct Impact Test 24B 16 Hydrostatic Strength Test for Pneumatic Actuators 26 MARKING 17 General 27 INSTALLATION

19、AND OPERATING INSTRUCTIONS 18 General 28 APPENDIX A Standards for ComponentsA1 NOVEMBER 5, 2013 FIRE DAMPERS - UL 555 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL APPENDIX B Standard Time-Temperature Curve for Control of Fire Tests B1 FE

20、BRUARY 23, 2009 FIRE DAMPERS - UL 555 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 These requirements cover re dampers that are intended for use where air ducts penetrate or terminate at openings in walls or part

21、itions; in air transfer openings in partitions; and where air ducts extend through oors as specied in the Standard for Installation of Air-Conditioning and Ventilating Systems, NFPA 90A. Fire dampers are intended for installation in accordance with codes such as the BOCA National Mechanical Code, SB

22、CCI Standard Mechanical Code, ICBO Uniform Mechanical Code, and the International Mechanical Code. 1.2 Fire dampers are evaluated for use as either: a) Fire Dampers for Static Systems For HVAC systems that are automatically shut down in the event of a re or for air transfer openings in walls or part

23、itions, b) Fire Dampers for Dynamic Systems For HVAC systems that are operational in the event of a re, c) Combination Fire and Smoke Dampers For locations in HVAC systems where a re damper and a smoke damper are required at a single location, or d) Corridor Dampers For locations in HVAC Systems whe

24、re air ducts penetrate or terminate at openings in the ceilings of interior corridors when permitted by authority having jurisdiction. Revised 1.2 effective May 4, 2012 1.3 Under these requirements a re damper is subjected to a standard re exposure, controlled to achieve specied temperatures through

25、out a specied time period, followed by the application of a specied standard hose stream. This exposure by itself is not representative of all re conditions; conditions vary with changes in the amount, nature, and distribution of re loading, ventilation, compartment size and conguration, and heat si

26、nk characteristics of the compartment. These requirements provide a relative measure of re performance of re damper assemblies under these specied re exposure conditions. Any variation from the construction or conditions that are tested such as method of installation and materials has the potential

27、to substantially change the performance characteristics of the re damper assembly. 1.4 Fire dampers for static systems (no air ow through the damper) are intended to close automatically upon the detection of heat by a heat responsive device. 1.5 Under these requirements combination re and smoke damp

28、ers, corridor dampers and re dampers for dynamic systems are exposed to standardized heat and airow conditions and are evaluated for dynamic closure under these conditions. Revised 1.5 effective May 4, 2012 1.6 Combination re and smoke dampers and corridor dampers shall also comply with the applicab

29、le requirements in the Standard for Smoke Dampers, UL 555S. Revised 1.6 effective May 4, 2012 MAY 4, 2010 FIRE DAMPERS - UL 555 4AUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 1.7 Fire dampers for dynamic systems are intended for use where

30、 the airow is operational at the time of re, such as in a smoke control system, or from other situations in which the fan system is operational at the time of a re. 1.8 Where re dampers are required in ducts that penetrate re barriers and where the duct is also used as part of a smoke control system

31、, the system designer shall ascertain which type of re damper is appropriate for the application. Fire dampers for dynamic systems are evaluated only for dynamic closure under heated airow conditions. Combination re and smoke dampers and corridor dampers that have an elevated temperature rating are

32、evaluated for dynamic closure under heated airow conditions and they are also evaluated to operate under heated air conditions. Revised 1.8 effective May 4, 2012 1.9 Tests conducted in accordance with these requirements are intended to demonstrate the performance of re dampers during the period of r

33、e test exposure and are not intended to determine acceptability of re dampers for use after exposure to re. 1.10 It is the intent that tests conducted in accordance with the test methods described herein develop data to enable regulatory authorities to determine the acceptability of re damper assemb

34、lies for use in locations where re resistance of a specied duration is required. 1.11 Fire dampers are intended to close automatically upon the detection of heat by the use of a fusible link or other heat responsive device. 1.12 These requirements do not cover: a) Performance of the re damper assemb

35、ly in walls, partitions, or oors constructed of materials other than those tested. b) The performance of the re damper assembly when installed using methods other than those re tested. c) Measurement of heat transmission through a re damper assembly. d) Measurement of the degree of control or limita

36、tion of the passage of smoke or products of combustion through the re damper assembly. MAY 4, 2010 FIRE DAMPERS - UL 555 4BUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 2 General 2.1 Components 2.1.1 Except as indicated in 2.1.2, a compone

37、nt of a product covered by this standard shall comply with the requirements for that component. See Appendix A for a list of standards covering components generally used in the products covered by this standard. 2.1.2 A component is not required to comply with a specic requirement that: a) Involves

38、a feature or characteristic not required in the application of the component in the product covered by this standard, or b) Is superseded by a requirement in this standard. MAY 4, 2010 FIRE DAMPERS - UL 555 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERM

39、ISSION FROM UL 2.1.3 A component shall be used in accordance with its rating established for the intended conditions of use. 2.1.4 Specic components are incomplete in construction features or restricted in performance capabilities. Such components are intended for use only under limited conditions,

40、such as certain temperatures not exceeding specied limits, and shall be used only under those specic conditions. 2.2 Units of measurement 2.2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory or approximate information. 2.3 Undated references 2.3.1 Any un

41、dated reference to a code or standard appearing in the requirements of this standard shall be interpreted as referring to the latest edition of that code or standard. 3 Glossary 3.1 For the purpose of this Standard the following denitions apply. 3.1.1 CONTROLLED CLOSURE The closure of a damper by me

42、ans of electric, pneumatic, hydraulic, or other similar device that inhibits the rate of closure. 3.1.1 added May 16, 2011 3.2 DYNAMIC CLOSURE The closure of a re damper under conditions of airow and heat upon activation of the heat responsive device. 3.3 HEAT RESPONSIVE DEVICE A safety device respo

43、nsive to changes in temperature in order to activate the closing mechanism of re dampers. 3.4 HEATED AIR OPERATION The operation of a smoke damper by means of the actuator when the damper is subjected to conditions of airow and heat. 3.5 PRIMARY HEAT RESPONSIVE DEVICE The heat responsive device with

44、 the lower temperature rating for re dampers equipped with two heat responsive devices. 3.6 REOPENABLE FIRE DAMPER A re damper equipped with a primary and a secondary heat responsive device. The re damper is operable after the primary heat responsive device activates, and not after the secondary dev

45、ice activates. 3.7 SECONDARY HEAT RESPONSIVE DEVICE The heat responsive device with the higher temperature rating for reopenable re dampers. 3.8 VOLUME CONTROL DAMPER A re damper employing position devices that enable the re damper to remain in positions other than fully open or fully closed. 3.9 NO

46、N-CONTROLLED CLOSURE The closure of a damper by means of spring operation, gravity or other similar device that does not inhibit the rate of closure. Non-controlled closure is also referred to as instantaneous closure, rapid closure or slam shut closure. 3.9 revised May 16, 2011 MAY 16, 2011 FIRE DA

47、MPERS - UL 555 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONSTRUCTION 4 General 4.1 Fire dampers shall be constructed to restrict the passage of ame when in the closed position. Combination re and smoke dampers, corridor dampers, and

48、re dampers for dynamic systems shall be constructed to close under the rated airow and heat conditions. A heat responsive device provided with a combination re and smoke damper shall have a temperature rating which is less than or equal to the temperature rating of the damper. Revised 4.1 effective

49、May 4, 2012 4.2 Through openings for operating clearances in re dampers shall not exceed 3/8 in (9.5 mm) in the vertical plane (such as between blades and each side of the re damper frame) at any location, and 1/32 in (0.8 mm) in the horizontal plane at any location (such as between blade-to-blade hinged joints in an interlocking curtain). 4.3 Any through opening between a re damper and its sleeve shall be insufficient in siz