1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 710A Rooftop Grease and Oil Collection and Containment SystemsUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIA
2、L NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Rooftop Grease and Oil Collection and Containment Systems, UL 710A First Edition, Dated July 10, 2015 Summary of Topics This First Edition of UL 710A covers Rooftop Grease and Oil Collecti
3、on and Containment Systems. The new requirements are substantially in accordance with Proposal(s) on this subject dated July 11, 2014. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical pho
4、tocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable for any specia
5、l, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of such damage. In n
6、o event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, damage, claim, or
7、 judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standard on the purchasers computer system. The requirements in this Standard are now in effect, except for those paragraphs, sections, tables, gures, and/or othe
8、r elements of the Standard having future effective dates as indicated in the note following the affected item. The prior text for requirements that have been revised and that have a future effective date are located after the Standard, and are preceded by a SUPERSEDED REQUIREMENTS notice. JULY 10, 2
9、015 UL 710A tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL JULY 10, 2015 UL 710A tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL JULY 10, 2015 1 UL 710A S
10、tandard for Rooftop Grease and Oil Collection and Containment Systems First Edition July 10, 2015 This UL Standard for Safety consists of the First Edition. Comments or proposals for revisions on any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposa
11、l Request in ULs On-Line Collaborative Standards Development System (CSDS) at http:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Stan
12、dards shall remain the sole and exclusive property of UL. COPYRIGHT 2015 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL JULY 10, 2015 UL 710A 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FUR
13、THER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .4 2 Components 4 3 Units of Measurement .4 4 Undated References 5 CONSTRUCTION 5 General 5 PERFORMANCE 6 Fire Exposure Tests .5 6.1 Preparation of samples 5 6.2 Flaming brand test 6 6.3 Flaming grease test .6
14、 6.4 Fire exposure test 6 7 Grease Containment Tests .7 7.1 Rain test (Dry) .7 7.2 Rain test (Oil soaked) .7 8 Mechanical Abuse Tests Impact Tests .7 MARKINGS 9 General 7 INSTRUCTIONS 10 General .8 APPENDIX A Standards for ComponentsA1 JULY 10, 2015 UL 710A 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FO
15、R FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 These requirements cover rooftop grease and oil collection and containment systems for use on roof coverings or roof systems achieving Class A, B, and C when tested in accordance with Standard for Standard Tes
16、t Methods for Fire Tests of Roof Covering Materials, UL 790. 1.2 The rooftop grease and oil collection and containment systems covered by these requirements are intended solely for use outdoors as collection and containment systems. The collection and containment systems are not intended for indoor
17、household use, nor are they intended for permanent attachment to the mounting surface of the roong system. 1.3 These systems are intended to be installed in accordance with the Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, NFPA 96, the International Mechanica
18、l Code (IMC) and/or the Uniform Mechanical Code (UMC). 2 Components 2.1 Except as indicated in 2.2, a component of a product covered by this standard shall comply with the requirements for that component. See Appendix A for a list of standards covering components generally used in the products cover
19、ed by this standard. 2.2 A component is not required to comply with a specic requirement that: a) Involves a feature or characteristic not required in the application of the component in the product covered by this standard, or b) Is superseded by a requirement in this standard. 2.3 A component shal
20、l be used in accordance with its rating established for the intended conditions of use. 3 Units of Measurement 3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory or approximate information. JULY 10, 2015 UL 710A 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FO
21、R FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 4 Undated References 4.1 Any undated reference to a code or standard appearing in the requirements of this standard shall be interpreted as referring to the latest edition of that code or standard. CONSTRUCTION 5 General 5.1 The enclo
22、sure of a collection and containment system shall be formed and assembled such that it has the strength and rigidity necessary to resist the abuses likely to be encountered during its intended service. The degree of resistance inherent in the system shall preclude total or partial loosening or displ
23、acement of parts, and other serious defects, which alone or in combination constitute a risk of re, explosion, or injury to persons. 5.2 Among the factors taken into consideration if an enclosure is being judged for acceptability are its: a) Mechanical strength; b) Resistance to impact; c) Moisture-
24、absorption properties; d) Flammability; e) Resistance to corrosion; and f) Resistance to distortion at temperatures to which the enclosure may be subjected under conditions of intended or abnormal use. PERFORMANCE 6 Fire Exposure Tests 6.1 Preparation of samples 6.1.1 The wooden deck for the re expo
25、sure tests is to be constructed with nominal one by eight inch pine boards and conditioned as described for Class A and B burning-brand decks in the Standard for Standard Test Methods for Fire Tests of Roof Covering Materials, UL 790. The deck is to be mounted at the maximum incline recommended by t
26、he manufacturer but not greater than an incline of 5 inches per horizontal foot (127 mm per 0.3 m). JULY 10, 2015 UL 710A 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 6.2 Flaming brand test 6.2.1 This test shall demonstrate the effect of
27、 having the system exposed to aming solid particles falling onto the system from a grease duct ventilator. The system shall not sustain combustion and the system shall conne the burning to the immediate area of the brand. Also, there shall be no evidence of burning or ignition of the supporting surf
28、ace. For the purpose of this Standard, sustained aming is considered any aming which continues uninterrupted for 5 seconds or more. 6.2.2 Flaming wood Class C test brands as described in the Standard for Standard Test Methods for Fire Tests of Roof Covering Materials, UL 790 shall be dropped onto th
29、e surface of the rooftop grease and oil collection and containment system. Brands are to be placed at one or two minute intervals. No brand is to be placed closer than 4 inches (102 mm) to the point where the previous brand was located. The lesser of 20 brands or a quantity to cover the surface of t
30、he containment system are to be used. 6.3 Flaming grease test 6.3.1 This test shall demonstrate the effect of aming oil dripping onto the system from a ventilator. The rooftop grease and oil collection and containment system shall not sustain combustion and the system shall conne the burning to the
31、immediate area of the oil drops. Also, there shall be no evidence of burning or ignition of the supporting surface. For the purpose of this Standard, sustained aming is considered any aming which continues uninterrupted for 5 seconds or more. 6.3.2 The system shall be installed on the wooden deck su
32、rface. Eight ounces of vegetable oil shall be ignited and allowed to burn for 20 seconds prior to any drops being made. Drops of the aming oil shall then be allowed to fall on the collection and containment system at intervals of 10 seconds between drops. Each drop is to be no less than 1/4 ounce, r
33、andomly dropped at different locations around the portion of the containment system intended to receive oil. At this rate there should be no more than approximately 32 drops of oil, and test should last for a duration of no more than 5 minutes and 10 seconds. 6.4 Fire exposure test 6.4.1 This test s
34、hall demonstrate the effect the system should have when a ame is applied to the system from an external ame source. The ames shall be conned to the system and there shall be no evidence that the ame is spreading beyond the system and there shall be no evidence of the roof deck, under the system, bur
35、ning. In addition, there shall be no evidence of burning particles blown outside the collection and containment systems enclosure. 6.4.2 The system shall be installed on a roof structure as described in the Standard for Standard Test Methods for Fire Tests of Roof Covering Materials, UL 790. An inte
36、rmittently applied Luminous Gas Flame at a temperature of 1400F (760C) shall be applied for 15 cycles to the system. During this test, the airow shall be maintained at 12 MPH (5.4 m/s). JULY 10, 2015 UL 710A 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PER
37、MISSION FROM UL 7 Grease Containment Tests 7.1 Rain test (Dry) 7.1.1 A representative sample of a rooftop grease or oil collection and containment system shall be subjected to an application of simulated rain for one-hour. The test apparatus described for the water spray test in the Standard for Pow
38、er Ventilators, UL 705 shall be used to apply the simulated rain. After the application of the rain, grease or oil shall be dripped onto the system. Water shall drain from the system and have no apparent effect on the ability of the system to absorb oil. 7.2 Rain test (Oil soaked) 7.2.1 A representa
39、tive sample, soaked with oil, shall be subjected to an application of simulated rain for one-hour. The system shall not permit the oil to wash away. After the application of the rain, a cup of oil shall be dripped onto the system and the systems ability to absorb the oil shall be veried. 8 Mechanica
40、l Abuse Tests Impact Tests 8.1 This test is conducted on three representative samples formed from thermoplastics that may affect the performance of the rooftop grease and oil collection and containment system. 8.2 The samples shall withstand the impact described in 8.3 without evidence of damage to
41、the component and the component shall remain structurally sound. 8.3 Each of three samples of the system shall be subjected to a single impact. This impact is to be produced by dropping a steel sphere, 2 inches (50.8 mm) in diameter, and weighing 1.18 lb. (0.535 kg) mass from a height of 51 inches (
42、1.29 m) to produce a 5 ft-lb. (6.78 joules) impact. The steel sphere shall strike the surface in a location different from those in the other two impacts. For surfaces other than the top of an enclosure, either the sample could be supported on the side and subjected to the ball impact mentioned abov
43、e, or the steel sphere is to be suspended by a cord and swung as a pendulum, dropping through a vertical distance of 51 inches (1.29 m) to strike the surface with a 5 ft-lb. (6.78 joules) impact. MARKINGS 9 General 9.1 Each collection and containment system shall be marked with the following: a) Man
44、ufacturers name or Trademark; b) Model, type, or catalog designation; and c) The date or other dating period of manufacture, which shall not exceed three consecutive months. 9.2 The following marking shall be visible after installation and provided in upper case letters at least 3/16 inches (4.8 mm)
45、 in height: “CAUTION PRODUCT MUST BE CHANGED WHEN THE (collection and containment nomenclature) IS SATURATED WITH GREASE OR OIL”. JULY 10, 2015 UL 710A 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 9.3 All markings shall be permanent, as
46、afforded by a metal nameplate securely attached, decal transfer, silk-screening, or adhesive-backed material that complies with the Standard for Marking and Labeling Systems, UL 969, and is suitable for the particular application. 9.4 All markings shall be placed where readily visible on a permanent
47、ly attached outside surface or in an operator accessible area. INSTRUCTIONS 10 General 10.1 Each rooftop grease and oil collection and containment system shall be provided with a set of installation and operating instructions. JULY 10, 2015 UL 710A 8UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER
48、 REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL APPENDIX A Standards for Components Standards under which components of the products covered by this standard are evaluated include the following: Title of Standard UL Standard Designation Air Ducts and Air Connectors, Factory-Made UL 181 Atta
49、chment Plugs and Receptacles UL 498 Ballasts, Fluorescent-Lamp UL 935 Cable Fittings, Conduit, Tubing, and UL 514B Circuit Breakers, Molded-Case, Molded-Case Switches and Circuit-Breaker Enclosures UL 489 Conduit, Flexible Metal UL 1 Conduit Steel, Electrical Rigid Metal UL 6 Controls for Household and Similar Use, Part 1: General Requirements, Automatic Electrical UL 60730-1 and/or the applicable Part 2 standard from the UL 60730 series Cord Sets and Power-Supply Cords UL 817 Dete