UL SUBJECT 1856-2013 OUTLINE OF INVESTIGATION FOR UNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMS (Issue 1)《地下燃料箱内部改造系统的调查大纲 (议题1)》.pdf

上传人:visitstep340 文档编号:1069200 上传时间:2019-04-02 格式:PDF 页数:30 大小:76.91KB
下载 相关 举报
UL SUBJECT 1856-2013 OUTLINE OF INVESTIGATION FOR UNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMS (Issue 1)《地下燃料箱内部改造系统的调查大纲 (议题1)》.pdf_第1页
第1页 / 共30页
UL SUBJECT 1856-2013 OUTLINE OF INVESTIGATION FOR UNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMS (Issue 1)《地下燃料箱内部改造系统的调查大纲 (议题1)》.pdf_第2页
第2页 / 共30页
UL SUBJECT 1856-2013 OUTLINE OF INVESTIGATION FOR UNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMS (Issue 1)《地下燃料箱内部改造系统的调查大纲 (议题1)》.pdf_第3页
第3页 / 共30页
UL SUBJECT 1856-2013 OUTLINE OF INVESTIGATION FOR UNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMS (Issue 1)《地下燃料箱内部改造系统的调查大纲 (议题1)》.pdf_第4页
第4页 / 共30页
UL SUBJECT 1856-2013 OUTLINE OF INVESTIGATION FOR UNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMS (Issue 1)《地下燃料箱内部改造系统的调查大纲 (议题1)》.pdf_第5页
第5页 / 共30页
点击查看更多>>
资源描述

1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJune 14, 20131UL 1856OUTLINE OF INVESTIGATIONFORUNDERGROUND FUEL TANK INTERNAL RETROFIT SYSTEMSIssue Number 1June 14, 2013Summary of TopicsThis is the First Issue of Subject 1856, Outline of Inve

2、stigation forUnderground Fuel Tank Internal Retrofit Systems covers lining, upgradeand structural types of nonmetallic retrofit systems (products) intendedfor field installation inside of steel or fiberglass underground fuel tanks incommercial (public) or private (fleet) automotive fueling stationap

3、plications. These products are also intended for primary containment oftypical liquid fuels as identified in this Outline, and may provide otherfeatures, such as secondary containment and structural improvements, asdescribed for each specific type of retrofit system.This issue becomes effective JUNE

4、 14, 2017.COPYRIGHT 2013 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJUNE 14, 2013UL 18562No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION F

5、ROM ULCONTENTSINTRODUCTION1 Scope .52 General 72.1 Units of measurement .72.2 Undated references .73 Glossary .7CONSTRUCTION4 General 94.7 Lining systems 104.8 Upgrade systems 104.9 Structural systems .114.10 Interstitial spaces .114.11 Manways and fittings .114.12 Tank compartments 11PERFORMANCE5 G

6、eneral .125.1 Test tank preparation 125.2 System installation .125.3 System material tests 145.4 System leakage tests 146 Tank Burial Tests 156.1 General sample and test preparation 156.2 Fitting torque and bending tests .166.3 Interstitial strength test .176.4 Saturated soil load test .176.5 Inters

7、titial communication test .187 Long Term Compatibility 187.1 General sample and test preparation 187.2 Physical property and visual exam tests 207.2.2 Visual exam test .207.2.3 Bond Strength Test 217.2.4 Flexural strength test .217.2.5 Tensile strength test .227.3 Test sample exposures 228 Installat

8、ion and Production Tests 238.1 General 238.2 Tank tests 238.3 Impact test .238.4 Leakage test 24MARKINGS9 General .24JUNE 14, 2013 UL 1856 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINSTRUCTIONS10 General 25Appendix A Test Fuel Formulati

9、onsA1 Representative Aggressive Combustible Test Fuel Mixtures and UL-B100 .A1A2 Representative Aggressive Flammable Test Fuels and Mixtures .A2Appendix B PULL-OFF DISK PREPARATIONB1 Bond Strength Test Pull-Off Disks B1JUNE 14, 2013UL 18564UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCT

10、ION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover nonmetallic retrofit systems (products) intended for field installation insideof steel or fiberglass underground fuel tanks in commercial (public) or private (fleet) automotive fuelingstation applications. T

11、hese products are intended for containment of typical liquid fuels as identified in thisOutline, and may provide other features as described for each specific type of retrofit system.1.2 These products are nonmetallic thermoset (such as FRP, epoxy, PUR or polyesters) or thermoplastic(such as PE) mat

12、erials that may or may not be bonded to the interior tank wall, depending upon thesystem type. These products typically use pre-fabricated sections with coatings applied on site, orhomogeneous or layered spray-on/roll-on materials applied on site, and may optionally be covered forminor repair of the

13、 host tank.1.2.1 Lining systems provide only primary containment of stored fuels, and do not add significantstructural strength to the host tank.1.2.2 Upgrade systems provide both primary containment and secondary containment of stored fuels withinterstitial monitoring, and are co-structural with th

14、e host tank.1.2.3 Structural systems provide both primary containment and secondary containment of stored fuelswith interstitial monitoring, and are self-structural without the host tank.1.3 These products are intended for containment of automotive fuels and exposure to soil fluids that havesimilar

15、chemical, physical and material compatibility properties as represented by the test liquids in theserequirements based on fuels formulated in accordance with 40 CFR Part 80, Regulation of Fuels and FuelAdditives, and meeting the following ASTM Fuel Specifications and blend limitations:a) ASTM D-975,

16、 Standard Specification for Diesel Fuel Oils, with biodiesel blends up to amaximum of 5 percent (B5);b) ASTM D-7467, Standard Specification for Low Blend Biodiesel, with biodiesel blends from 6to 20 percent (B6 to B20).c) ASTM D-4814, Standard Specification for Automotive Spark-Ignition Engine Fuel,

17、 gasoline oroxygenated gasoline, with limited ethanol blends up to a maximum of 10 percent (E10);d) ASTM D-5798, Standard Specification for Ethanol Fuel Blends for Flexible-Fuel AutomotiveSpark-Ignition Engines, high blend ethanol, with gasoline/ethanol mixtures blends from 51 to 83percent (E51 E83)

18、; ande) Mid Range Ethanol Blends (E11 to E50) using variable mixtures of ASTM D4814 Low BlendEthanol and ASTM D5798 High Blend Ethanol1.4 Products covered by this outline are intended to be installed and used in accordance with one or moreof the following:a) Flammable and Combustible Liquids Code, N

19、FPA 30;b) Code for Motor Fuel Dispensing Facilities and Garages, NFPA 30A;c) Uniform Fire Code, NFPA 1;JUNE 14, 2013 UL 1856 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULd) International Fire Code published by the International Fire Counci

20、l; ore) Other applicable federal and state regulations for the specific product or application it isbeing utilized in.1.5 These products are intended for field installation, by only qualified persons, inside the host tankwithout a need for excessive excavation, in accordance with the manufacturers i

21、nstructions and the localrequirements. Prior to installation, cleaning, inspecting, repairing and preparing the host tank interiorsurface is also conducted by qualified persons in accordance with the manufacturers instructions.1.6 These products are intended to be periodically inspected and maintain

22、ed for continued service, ortaken out of service if deemed necessary by qualified persons in accordance with industry recommendedpractices, the manufacturers instructions or applicable regulations.1.7 These products and the manufacturers installation instructions have not been investigated for their

23、physiological effect, if any, for safety of any persons during the installation process, and the potential riskassociated with the opening, entering, purging, cleaning, inspecting, surface preparation, systeminstallation, and testing of a tank that has been used to store flammable or combustible liq

24、uids.1.8 These products and requirements are not intended to cover or evaluate the installation equipment,safety of the installer, compliance with worker safety regulations (such as confined spaces, hazardouslocations, or OSHA), or any environmental emissions or disposal regulations, (such as EPA).1

25、.9 These products have not been evaluated for use after natural disasters, or exposures to chemicalsnot representative of the test liquids or excessive physical damage beyond the expected installation anduses as identified in these requirements.1.10 These requirements do not cover additional claims,

26、 if any, related to improved fuel quality, nor theeffect, if any, of the products material(s) on fuel quality or properties.1.11 These requirements do not cover thin coatings or paints that may be directly applied to internal tanksurfaces, and do not cover flexible or rigid tank bladders that are no

27、t directly bonded to internal tanksurfaces.1.12 These requirements do not cover external corrosion protection systems for steel underground tanks,which are found in UL1746 External Corrosion Protection Systems for Steel Underground StorageTanks.JUNE 14, 2013UL 18566UL COPYRIGHTED MATERIAL NOT AUTHOR

28、IZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2 General2.1 Units of measurement2.1.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.2.2 Undated references2.2.1 Any undated reference to a code or standard

29、 appearing in the requirements of this standard shallbe interpreted as referring to the latest edition of that code or standard.3 Glossary3.1 For the purposes of this outline the following definitions apply.3.2 HOST TANK An installed underground fuel storage tank that has been Listed for compliance

30、inaccordance with the applicable Standards for:a) Steel Underground Tanks for Flammable Liquids, UL 58;b) External Corrosion Protection Systems for Steel Underground Storage Tanks, UL 1746;c) Glass Fiber Reinforced Plastic Underground Storage Tanks for Petroleum Products,Alcohols, and Alcohol-Gasoli

31、ne Mixtures, UL 1316;3.3 RETROFIT SYSTEM Engineered nonmetallic (thermoset or thermoplastic) material(s) that arefield installed inside of a host tank, and provide different refurbished levels of containment, optionalrepair, and other features as follows:a) Lining System A retrofit system that is di

32、rectly bonded to the interior wall of the host tank,provides only primary containment of stored fuels, and does not add significant structuralstrength to the host tank.b) Upgrade System A retrofit system that is directly bonded to the interior wall of the hosttank, provides both primary containment

33、and secondary containment of stored fuels withinterstitial monitoring, and is co-structural with the host tank.c) Structural System A retrofit system that may or may not be bonded to the interior wall ofthe host tank, provides both primary containment and secondary containment of stored fuelswith in

34、terstitial monitoring, and is self-structural from the host tank.3.4 REFURBISH The addition of materials to an existing tank structure after surface preparations, forthe intended purpose of returning the entire tank wall to at least its original design thickness and/orstrength.3.5 REPAIR The localiz

35、ed addition of materials to an existing tank structure after surfacepreparations to plug a leak or intended to return a portion of the tank wall to its original design thicknessand/or strength.JUNE 14, 2013 UL 1856 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHO

36、UT PERMISSION FROM UL3.6 PRIMARY CONTAINMENT (PRIMARY) The ability of an enclosed tank design or construction todirectly contact and confine a liquid while in normal use (intended fuel storage) without leakage. Primaryretrofit systems form a refurbished primary (100 percent of all surfaces covered)

37、within the existing tankstructure.3.7 SECONDARY CONTAINMENT (SECONDARY) The ability of a tank design or construction todirectly contact and confine a liquid in abnormal use (from primary leakage) without leakage. Secondaryretrofit systems form both a new primary and interstitial space (of minimum 33

38、0 annular degrees) withinthe existing tank structure, which becomes the refurbished secondary.3.8 THIN COATING Any material directly applied to the interior of the tank wall that has a combinedtotal system thickness of less than 70 mils.3.9 QUALIFIED PERSON A worker specifically trained by the manuf

39、acturer to perform proper fieldinstallation of its retrofit system in accordance with the specified instructions. The qualified person is notrequired to be an employee of the manufacturer.3.10 FUELS Typically those liquids identified in 40 CFR Part 80 Regulation of Fuels and FuelAdditives and compli

40、ant with only the ASTM Fuel Specification below that are dispensed in commercialor fleet motor vehicle fueling stations for used in automotive engines (internal combustion orcompression ignition):a) ASTM D-975, Standard Specification for Diesel Fuel Oils, with biodiesel blends up to amaximum of 5 pe

41、rcent (B5);b) ASTM D-7467, Standard Specification for Low Blend Biodiesel, with biodiesel blends from 6to 20 percent (B6 to B20).c) ASTM D-4814, Standard Specification for Automotive Spark-Ignition Engine Fuel, gasoline oroxygenated gasoline, with limited ethanol blends up to a maximum of 10 percent

42、 (E10);d) ASTM D-5798, Standard Specification for Ethanol Fuel Blends for Flexible-Fuel AutomotiveSpark-Ignition Engines, high blend ethanol, with gasoline/ethanol mixtures blends from 51 to 83percent (E51 E83); ande) Mid Range Ethanol Blends (E11 to E50) using variable mixtures of ASTM D4814 Low Bl

43、endEthanol and ASTM D5798 High Blend Ethanol3.11 CO-STRUCTURAL A retrofit system that is designed to meet equivalent structural requirementsof an underground tank standard, with shared structural strength between the host tank and retrofitsystem.3.12 SELF-STRUCTURAL A retrofit system that is designe

44、d to meet equivalent structuralrequirements of an underground tank standard, without any structural contribution from the host tank.3.13 ADHESIVE FAILURE Failure (typically loss of strength and detachment) between the host tanksurface and the system bonding adhesive.3.14 COHESIVE FAILURE Failure of

45、materials or layers within either the host tank or retrofit system,but not the bonding adhesive between them.JUNE 14, 2013UL 18568UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONSTRUCTION4 General4.1 All retrofit systems shall be designed f

46、or field installation (without the need for excessive excavationor tank opening) inside of existing steel and/or fiberglass underground fuel storage (host) tanks that havepreviously been certified as meeting any one of following standards:a) Steel Underground Tanks for Flammable Liquids, UL 58;b) Ex

47、ternal Corrosion Protection Systems for Steel Underground Storage Tanks, UL 1746;c) Glass Fiber Reinforced Plastic Underground Storage Tanks for Petroleum Products,Alcohols, and Alcohol-Gasoline Mixtures, UL 1316;Note If necessary for system installation, tank top excavation and cut openings are per

48、mitted, providedthese details are in the instructions.4.2 All retrofit systems shall clearly define the above host tank(s) and basic parameters for which they aredesigned for, including, but not limited to the items below.a) System bonding to steel and/or fiberglass (if applicable),b) Maximum tank d

49、iameter and length/diameter ratio,c) Minimum tank opening size needed for installation,d) Maximum hole or crack dimensions which may be repaired,e) Minimum containment coverage in circumferential degrees, andf) Minimum average thickness of any field applied material(s).4.3 All retrofit systems shall clearly define for steel and/or fiberglass tanks as applicable, the process(es)and minimum specifications for each step in the installation, including, but not limited to the items below:a) Tank cleanout, surface inspection, thickness mea