UL SUBJECT 2987-2016 Outline of Investigation for Steel Sprinkler Pipe Corrosion Indicators (Issue 1).pdf

上传人:roleaisle130 文档编号:1069383 上传时间:2019-04-02 格式:PDF 页数:8 大小:23.17KB
下载 相关 举报
UL SUBJECT 2987-2016 Outline of Investigation for Steel Sprinkler Pipe Corrosion Indicators (Issue 1).pdf_第1页
第1页 / 共8页
UL SUBJECT 2987-2016 Outline of Investigation for Steel Sprinkler Pipe Corrosion Indicators (Issue 1).pdf_第2页
第2页 / 共8页
UL SUBJECT 2987-2016 Outline of Investigation for Steel Sprinkler Pipe Corrosion Indicators (Issue 1).pdf_第3页
第3页 / 共8页
UL SUBJECT 2987-2016 Outline of Investigation for Steel Sprinkler Pipe Corrosion Indicators (Issue 1).pdf_第4页
第4页 / 共8页
UL SUBJECT 2987-2016 Outline of Investigation for Steel Sprinkler Pipe Corrosion Indicators (Issue 1).pdf_第5页
第5页 / 共8页
点击查看更多>>
资源描述

1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULOCTOBER 25, 20161UL 2987Outline of Investigation for Steel Sprinkler Pipe Corrosion IndicatorsIssue Number: 1October 25, 2016Summary of TopicsThis First issue of the Outline of Investigation for

2、Steel Sprinkler PipeCorrosion Indicators, UL 2987, is being issued to address corrosionindicator devices intended to be installed within a sprinkler system havingsteel piping to provide a means to determine when substantial internalcorrosion is occurring within the system.ULs Outlines of Investigati

3、on are copyrighted by UL LLC. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of ULLL

4、C.COPYRIGHT 2016 UL LLCUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULOCTOBER 25, 2016UL 29872No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 S

5、cope .42 Components 43 Units of Measurement .54 Undated References 5CONSTRUCTION5 General 5PERFORMANCE6 General 67 Leakage Test 68 Strength of Body Test .6MARKINGS9 General 7INSTALLATION AND MAINTENANCE INSTRUCTIONS10 General .7OCTOBER 25, 2016 UL 2987 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FUR

6、THER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover corrosion indicating devices intended to be installed within a wet or drypipe sprinkler system having steel piping to provide for a means to determine when substantial internalcorrosion is occu

7、rring within the system. This equipment is intended for installation in accordance with themanufacturers installation instructions and the applicable requirements of the following standards:a) Standard for the Installation of Sprinkler Systems, ANSI/NFPA 13.b) Standard for the Installation of Sprink

8、ler Systems in Low-Rise Residential Occupancies,ANSI/NFPA 13R.c) Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings andManufactured Homes, ANSI/NFPA 13D.d) National Electrical Code, ANSI/NFPA 70.2 Components2.1 Except as indicated in 2.2, a component of a product cov

9、ered by this Outline shall comply with therequirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the application of the component in theproduct covered by this Outline, orb) Is superseded by a

10、 requirement in this Outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomplete in construction features or restricted in performance capabilities.Such components are intended for use only under limited con

11、ditions, such as temperatures not exceedingspecified limits, and shall be used only under those specific conditions.OCTOBER 25, 2016UL 29874UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL3 Units of Measurement3.1 Values stated without parenth

12、eses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this Outline shall beinterpreted as referring to the latest edition of that code or standard.CONSTRUCTION5 Ge

13、neral5.1 A corrosion indicator shall be constructed for a minimum rated pressure of 175 psig (1.2 MPa).5.2 Steel piping used for the body of a corrosion indicating device shall conform to Schedule 10 or 40steel pipe made in accordance with Standard Specification for Black and Hot-Dipped Zinc-Coated(

14、Galvanized) Welded and Seamless Steel Pipe for Fire Protection Use, ASTM A795, or StandardSpecification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless, ASTM A53 orStandard Specification for Electric-Resistance-Welded Steel Pipe, ASTM A 135/A 135M.5.3 When a corrosion indicat

15、or uses a thin wall section of steel piping described in 5.1 to provide a meansof indicating substantial internal corrosion, the thin wall section shall comply with the following:a) A nominal thickness not greater than 30 percent of the nominal wall thickness of thesprinkler piping for which the ind

16、icator is intended to be used.b) A nominal thickness that will result in a hoop stress applied to the thinned section that is notmore than 50 percent of the minimum yield strength of the material.c) A thickness tolerance of not greater than 0.005 inch.5.4 Pressure switches shall comply with the appl

17、icable construction requirements in the Standard forAlarm Accessories for Automatic Water-Supply Control Valves for Fire Protection Service, UL 753.5.5 Accessory equipment shall comply with the construction requirements applicable to the device and itsintended use.5.6 Threaded end connections shall

18、comply with National Pipe Threads (NPT) conforming to theStandard for Pipe Threads, General Purpose (Inch), ANSI/ASME B1.20.1 or Standard for Dryseal PipeThreads (Inch), ANSI B1.20.3.5.7 Grooved end connections shall comply with the Standard for Grooved and Shouldered Joints,ANSI/AWWA C600.OCTOBER 2

19、5, 2016 UL 2987 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL5.8 Flanged end connections shall comply with the Standard for Pipe Flanges and Flanged Fittings: NPS1/2 through 24, ANSI/ASME B16.5.PERFORMANCE6 General6.1 Pressure switches sha

20、ll comply with the applicable performance requirements in the Standard forAlarm Accessories for Automatic Water-Supply Control Valves for Fire Protection Service, UL 753.6.2 Accessory equipment shall comply with the performance requirements applicable to the device andits intended use.7 Leakage Test

21、7.1 A corrosion indicator shall be capable of withstanding without leakage through the body or at jointsan internal hydrostatic pressure of two times the rated working pressure, applied for a period of 1 minute.7.2 During this test, a thin wall section of pipe used as an indicator is to be perforate

22、d so as to apply thetest pressure the entire body of the device.7.3 A representative sample(s) of the corrosion indicator is be filled with water and vented of air. Thepressure is to be gradually increased at a rate not exceeding 300 psig (2.07 MPa) per minute until therequired test pressure is achi

23、eved and held for 1 minute. Visual observations are to be made for leakagethrough the body.8 Strength of Body Test8.1 A corrosion indicator shall withstand without rupture a hydrostatic pressure of four times the ratedworking pressure applied for a period of 5 minutes.8.2 During this test, a thin wa

24、ll section of pipe used as an indicator is to be perforated so as to apply thetest pressure the entire body of the device.8.3 A representative sample(s) of the corrosion indicator is to be filled with water and vented of air. Thepressure is to be gradually increased at a rate not exceeding 300 psig

25、(2.07 MPa) per minute until therequired test pressure is achieved and held for 5 minutes.OCTOBER 25, 2016UL 29876UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMARKINGS9 General9.1 Each corrosion indicator shall be legibly and permanently mar

26、ked with the following:a) The manufacturers or private labelers name or identifying symbol,b) A distinctive product identification designation,c) Pressure rating, andd) Nominal size.9.2 If a corrosion indicator is manufactured at more than one factory, each unit shall have a distinctivepermanent mar

27、king to identify it as the product of a particular factory.INSTALLATION AND MAINTENANCE INSTRUCTIONS10 General10.1 Steel sprinkler pipe corrosion indicators shall be provided with installation and maintenanceinstructions that include at least the following items:a) Detailed instructions for properly

28、 installing and maintaining the equipment.b) Reference to the need for periodic or continuous monitoring of the corrosion indicator todetermine its functional status.c) Operating temperature ranged) The set pressure of the pressure switch when used.e) Type of steel pipe for which the corrosion indic

29、ator is intended to be used.f) Maximum system working pressure associated with the use of the corrosion indicatorg) Reference to installation and use in accordance with the Standard for the Installation ofSprinkler Systems, NFPA 13; and inspection, testing and maintenance in accordance with theStandard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems,ANSI/NFPA 25.OCTOBER 25, 2016 UL 2987 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULOCTOBER 25, 2016UL 29878No Text on This Page

展开阅读全文
相关资源
猜你喜欢
  • BS EN 61508-2-2010 Functional safety of electrical electronic programmable electronic safety-related systems Requirements for electrical electronic programmable electronic safety-r.pdf BS EN 61508-2-2010 Functional safety of electrical electronic programmable electronic safety-related systems Requirements for electrical electronic programmable electronic safety-r.pdf
  • BS EN 61508-3-2010 Functional safety of electrical electronic programmable electronic safety-related systems - Software requirements《电气 电子 可编程电子安全性相关系统的功能安全性 软件要求》.pdf BS EN 61508-3-2010 Functional safety of electrical electronic programmable electronic safety-related systems - Software requirements《电气 电子 可编程电子安全性相关系统的功能安全性 软件要求》.pdf
  • BS EN 61508-4-2010 Functional safety of electrical electronic programmable electronic safety related systems Definitions and abbreviations《电气 电子 可编程电子安全性相关系统的功能安全性 定义和缩略语》.pdf BS EN 61508-4-2010 Functional safety of electrical electronic programmable electronic safety related systems Definitions and abbreviations《电气 电子 可编程电子安全性相关系统的功能安全性 定义和缩略语》.pdf
  • BS EN 61508-5-2010 Functional safety of electrical electronic programmable electronic safety related systems Examples of methods for the determination of safety integrity levels《电气.pdf BS EN 61508-5-2010 Functional safety of electrical electronic programmable electronic safety related systems Examples of methods for the determination of safety integrity levels《电气.pdf
  • BS EN 61508-6-2010 Functional safety of electrical electronic programmable electronic safety related systems Guidelines on the application of IEC 61508-2 and IEC 61508-3《电气 电子 程序可控.pdf BS EN 61508-6-2010 Functional safety of electrical electronic programmable electronic safety related systems Guidelines on the application of IEC 61508-2 and IEC 61508-3《电气 电子 程序可控.pdf
  • BS EN 61508-7-2010 Functional safety of electrical electronic programmable electronic safety related systems Overview of techniques and measures《电气 电子 可编程电子安全性相关系统的功能安全性 技术和措施总则》.pdf BS EN 61508-7-2010 Functional safety of electrical electronic programmable electronic safety related systems Overview of techniques and measures《电气 电子 可编程电子安全性相关系统的功能安全性 技术和措施总则》.pdf
  • BS EN 61511-3-2017 Functional safety Safety instrumented systems for the process industry sector Guidance for the determination of the required safety integrity levels《功能安全性 加工工业部门.pdf BS EN 61511-3-2017 Functional safety Safety instrumented systems for the process industry sector Guidance for the determination of the required safety integrity levels《功能安全性 加工工业部门.pdf
  • BS EN 61512-1-1999 Batch control - Models and terminology《产品批控制 模型和术语》.pdf BS EN 61512-1-1999 Batch control - Models and terminology《产品批控制 模型和术语》.pdf
  • BS EN 61512-2-2002 Batch control - Data structures and guidelines for languages《按批控制 数据结构和语言指南》.pdf BS EN 61512-2-2002 Batch control - Data structures and guidelines for languages《按批控制 数据结构和语言指南》.pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > 其他

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1