资源描述

1、11-10 22 14 33 - 1 SECTION 22 14 33 PACKAGED, PEDESTAL DRAINAGE PUMP UNITS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. Packaged pedestal drain

2、age pump units. 1.2 RELATED WORK A. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING. B. Section 22 05 12, GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT. C. SECTION 22 08 00 COMMISSIONING OF PLUMBING SYSTEMS. Requirements for commissioning, systems readiness checklist, and training. D. Section

3、 26 29 11, LOW-VOLTAGE MOTOR STARTERS. 1.3 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Manufacturers Literature and Data: 1. Pump: a. Manufacturer and model. b. Operating speed. c. Capacity. d. Characteristic performance curves. 2. Motor: a.

4、 Manufacturer, / frame and type /. b. Speed. c. Current Characteristics and W (HP). d. Efficiency. C. Certified copies of all the factory and construction site test data sheets and reports. D. Complete operating and maintenance manuals including wiring diagrams, technical data sheets and information

5、 for ordering replaceable parts: 1. Include complete list which indicates all components of the system. 2. Include complete diagrams of the internal wiring for each item of equipment. 3. Diagrams shall have their terminals identified to facilitate installation, operation and maintenance. E. Complete

6、d System Readiness Checklist provided by the Commissioning Agent and completed by the contractor, signed by a qualified technician and Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-10 22 14 33 - 2 dated on the date of completion, in accordance w

7、ith the requirements of Section 22 08 00 COMMISSIONING OF PLUMBING SYSTEMS. 1.4 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. National Electrical Manuf

8、acturers Association (NEMA): ICS6-93 (R2006) Industrial Control and Systems Enclosures 250-2008 . Enclosures for Electrical Equipment (1000 Volts Maximum) C. Underwriters Laboratories, Inc. (UL): 508-99 (R2008) . Standards For Industrial Control Equipment PART 2 - PRODUCTS SPEC WRITER NOTE: Make mat

9、erial requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify only that which applies to the project. Coordinate and assure that the electrical characteristics specified below are clearly shown on the proper drawings. 2.1 PEDESTAL DRAIN

10、AGE PUMP A. Centrifugal, vertical, designed for / 60 / 82 / degrees C (/ 140 / 180 / degrees F) maximum water temperature. Pump shall have a capacity of _ LPM ( _ GPM) at _ meters of head (_ feet of head) when driven by a _ HP _ volt _ phase electric motor. Driver shall be electric motor. Provide pe

11、rforated suction strainer. Systems may include one, two, or more pumps with alternator as required by the Contract Documents: 1. Pump housings may be cast iron, bronze, aluminum or stainless steel. Cast iron housings for submersible pumps shall be epoxy coated. B. Impeller: Brass, bronze or cast iro

12、n. C. Shaft: Bronze, stainless steel or other approved corrosion-resisting metal. D. Bearings: As required to hold shaft alignment, anti-friction type for thrust permanently lubricated. E. Motor NEMA 4: Maximum 40 degrees C (104 degrees F) ambient temperature rise, drip proof , voltage and phase as

13、shown in schedule on Electrical drawings conforming to NEMA 250-Type 4. Motor shall be non-overloading over the entire pump curve. Refer to Section 22 05 12, GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT. F. Starting Switch: Manually-operated, tumbler type, as specified in Section 26 29 11, LOW-

14、VOLTAGE MOTOR STARTERS. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-10 22 14 33 - 3 G. Automatic Control and Level Alarm: Furnish a control panel in a Nema 1 enclosure for indoors or in a Nema 4X enclosure for outdoors. The controls shall be s

15、uitable for operation with the electrical characteristics listed on the Electrical drawings. The control panel shall have a level control system with switches to start and stop pumps automatically, and to activate a high water alarm. The level control system will include sensors in the sump that det

16、ect the level of the liquid. The sensors may be float type switches, ultrasonic level sensors, transducers, or other appropriate equipment. The high water alarm shall have a red beacon light at the control panel and a buzzer, horn, or bell. The alarm shall have a silencing switch. Provide auxiliary

17、contacts for remote alarming to the Energy Control Center and BAC net compatible open-protocol type interface to DDC Controls System. The circuitry of the control panel shall include: 1. power switch to turn on/off the automatic control mechanism 2. HOA switches to manually override automatic contro

18、l mechanism 3. run lights to indicate when pumps are powered up 4. level status lights to indicate when water in sump has reached the predetermined on/off and alarm levels 5. magnetic motor contactors 6. disconnect/breaker for each pump 7. automatic motor overload protection H. For a duplex system,

19、provide an alternating relay to automatically alternate leadoff and standby duties of each pump of a duplex unit at the end of each pumping cycle. Standby pump shall start when water level in sump rises to a predetermined level that indicates excessive inflow or failure of the lead pump. I. Sensors

20、that detect the level of water in the sump shall be so arranged as to allow the accumulation of enough volume of liquid below the normal on level that the pump will run for a minimum cycle as recommended by pump manufacturer to prevent short cycling. Sensors shall be located to activate the alarm ad

21、equately before the water level rises to the inlet pipe. J. Provide two separate power supplies to the control panel, one for the control/alarm circuitry and one for power to the pump motors. Each power supply is to be fed from its own breaker so that if a pump overload trips a breaker, the alarm sy

22、stem will still function. Each power supply is to be wired in its own conduit. K. Wiring from the sump to the control panel shall have separate conduits for the pump power and for the sensor switches. All conduits are to be Provided by IHSNot for ResaleNo reproduction or networking permitted without

23、 license from IHS-,-,-11-10 22 14 33 - 4 sealed at the basin and at the control panel to prevent the intrusion of moisture and of flammable and/or corrosive gases. L. Sump: Furnish cast iron, fiberglass or high density polyethylene basin with gas tight covers. Covers shall have a manhole with a bolt

24、ed cover of minimum size to inspect and service the pumps, vent connection, and openings for pumps and controls. Sump shall be sized to allow an adequate volume of water to accumulate for a minimum one minute cycle of pump operation. M. Provide a union, check and ball valve in the discharge of each

25、pump. N. Removal/Disconnect System: A removal/disconnect system shall be provided where indicated on drawing. The system will consist of a discharge fitting mounted on vertical guide rails attached to the sump. The pump shall be fitted with an adapter fitting that easily connects to/disconnects from

26、 the discharge fitting as the pump is raised from or lowered into the sump. The discharge piping will connect to the discharge fitting so that it is not necessary to disconnect any piping in order to remove the pump. Where the sump depth is greater than five feet or other conditions exist to make th

27、e removal of the pump difficult or hazardous, the system shall include a rail guided quick disconnect apparatus to allow the pump to be pulled up out of the sump without workers entering the sump and without disconnecting the piping. PART 3 - EXECUTION 3.1 STARTUP AND TESTING A. Make tests as recomm

28、ended by product manufacturer and listed standards and under actual or simulated operating conditions. Tests of the various items of equipment shall be performed simultaneously with the system of which each item is an integral part. B. Tests shall include system capacity and all control and alarm fu

29、nctions. C. When any defects are detected, correct defects and repeat test. D. The Commissioning Agent will observe startup and contractor testing of selected equipment. Coordinate the startup and contractor testing schedules with the Resident Engineer and Commissioning Agent. Provide a minimum of 7

30、 days prior to notice. 3.2 COMMISSIONING A. Provide commissioning documentation accordance with the requirements of Section 22 08 00 COMMISSIONING OF PLUMBING SYSTEMS for all inspection, startup, and contractor testing required above and required by the System Readiness Checklist provided by the Com

31、missioning Agent. B. Components provided under this section of the specification will be tested as part of a larger system. Refer to Section 22 08 00 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-10 22 14 33 - 5 COMMISSIONING OF PLUMBING SYSTEMS

32、 and related sections for contractor responsibilities for system commissioning. 3.3 DEMONSTRATION AND TRAINING A. Provide services of manufacturers technical representative for four hours to instruct VA Personnel in operation and maintenance of units. B. Submit training plans and instructor qualifications in accordance with the requirements of Section 22 08 00 COMMISSIONING OF PLUMBING SYSTEMS. - - - E N D - - - Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-

展开阅读全文
相关资源
猜你喜欢
  • NF C94-232-2-1993 Methods of measurement for radio transmitters Part 12  guidelines for drawing up descriptive leaflets for transmitters and transposers for sound and television br.pdf NF C94-232-2-1993 Methods of measurement for radio transmitters Part 12 guidelines for drawing up descriptive leaflets for transmitters and transposers for sound and television br.pdf
  • NF C94-233-1993 Methods of measurement for radio transmitters Part 13  performance characteristics for fm sound broadcasting 《无线电发射机的测量方法 第13部分 调频声广播的性能特性》.pdf NF C94-233-1993 Methods of measurement for radio transmitters Part 13 performance characteristics for fm sound broadcasting 《无线电发射机的测量方法 第13部分 调频声广播的性能特性》.pdf
  • NF C94-234-1997 Methods of measurement for radio transmitters Part 14  external intermodulation products caused by two or more transmitters using the same or adjacent antennas 《无线电.pdf NF C94-234-1997 Methods of measurement for radio transmitters Part 14 external intermodulation products caused by two or more transmitters using the same or adjacent antennas 《无线电.pdf
  • NF C94-566-1998 Measurement of exposure to radio-frequency electromagnetic fields Field strength in the frequency range 100 kHz to 1 GHz 《射频电磁场暴露测量 频率范围为 100 kHz - 1 GHz 的场强》.pdf NF C94-566-1998 Measurement of exposure to radio-frequency electromagnetic fields Field strength in the frequency range 100 kHz to 1 GHz 《射频电磁场暴露测量 频率范围为 100 kHz - 1 GHz 的场强》.pdf
  • NF C94-864-2-1998 Standardization of interconnections between broadcasting transmitters or transmitter systems and supervisory equipment Part 2  interface standards for systems usi.pdf NF C94-864-2-1998 Standardization of interconnections between broadcasting transmitters or transmitter systems and supervisory equipment Part 2 interface standards for systems usi.pdf
  • NF C96-001-1984 Electronic components Semiconductor devices Discrete devices and integrated circuits Part 1  general 《电子元件 半导体器件 分立元件和集成电路 第1部分 总则》.pdf NF C96-001-1984 Electronic components Semiconductor devices Discrete devices and integrated circuits Part 1 general 《电子元件 半导体器件 分立元件和集成电路 第1部分 总则》.pdf
  • NF C96-002-2001 Semiconductor devices - Discrete devices and integrated circuits - Part 2  rectifier diodes 《半导体器件 分立器件和集成电路 第2部分 整流二极管》.pdf NF C96-002-2001 Semiconductor devices - Discrete devices and integrated circuits - Part 2 rectifier diodes 《半导体器件 分立器件和集成电路 第2部分 整流二极管》.pdf
  • NF C96-003-1986 Semiconductor devices Discrete devices and integrated circuits Part 3  signal (including switching) and regulator diodes 《半导体器件 分立器件和集成电路 第3部分 信号(包括开关)和整流二极管》.pdf NF C96-003-1986 Semiconductor devices Discrete devices and integrated circuits Part 3 signal (including switching) and regulator diodes 《半导体器件 分立器件和集成电路 第3部分 信号(包括开关)和整流二极管》.pdf
  • NF C96-005-1994 Discrete devices and integrated circuits Part 5  optoelectronic devices 《分立器件和集成电路 第5部分 光电器件》.pdf NF C96-005-1994 Discrete devices and integrated circuits Part 5 optoelectronic devices 《分立器件和集成电路 第5部分 光电器件》.pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > 其他

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1