1、BRITISH STANDARD BS EN 50086-2-2:1996 Incorporating Amendment No. 1 and Corrigendum No. 1 Specification for Conduit systems for cable management Part 2: Particular requirements Section 2.2: Pliable conduit systems The European Standard EN 50086-2-2:1995 with the incorporation of amendment A11:1998 h

2、as the status of a British Standard This British Standard should be read in conjunction with BS EN 50086-1:1994 ICS 29.120.10 NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW Copyright British Standards Institution Reproduced by IHS under license with BSI - Uncontrolled Copy No

3、t for Resale No reproduction or networking permitted without license from IHS - - -BS EN 50086-2-2:1996 This British Standard, having been prepared under the direction of the Electrotechnical Sector Board, was published under the authority of the Standards Board and comes into effect on 15 April 199

4、6 BSI 26 February 2002 The following BSI references relate to the work on this standard: Committee reference PEL/113 Draft for comment 92/04072 DC ISBN 0 580 25528 X Committees responsible for this British Standard The preparation of this British Standard was entrusted to Technical Committee PEL/113

5、, Cable management, upon which the following bodies were represented: ASTA Certification Services British Electrical Systems Association (BEAMA Ltd.) British Telecommunications plc Electrical Installation Equipment Manufacturers Association Electricity Association Gland Manufacturers Technical Commi

6、ttee Institution of Electrical Engineers Institution of Incorporated Executive Engineers Amendments issued since publication Amd. No. Date Comments 10514 January 2000 Deletion from Annex AA of A-deviations for Finland 13546 Corrigendum No. 1 26 February 2002 Correction to title of standard Copyright

7、 British Standards Institution Reproduced by IHS under license with BSI - Uncontrolled Copy Not for Resale No reproduction or networking permitted without license from IHS - - -BS EN 50086-2-2:1996 BSI 26 February 2002 i Contents Page Committees responsible Inside front cover National foreword ii Fo

8、reword 2 Text of EN 50086-2-2 3 Copyright British Standards Institution Reproduced by IHS under license with BSI - Uncontrolled Copy Not for Resale No reproduction or networking permitted without license from IHS BS EN 50086-2-2:1996 ii BSI 26 February 2002 National foreword This British Standard ha

9、s been prepared by Technical Committee PEL/113 and is the English language version of EN 50086-2-2:1995, Conduit systems for cable management Part 2-2 Particular requirements for pliable conduit systems, including amendment A11:1998 and corrigendum February 2001, published by the European Committee

10、for Electrotechnical Standardization (CENELEC). This British Standard is to be read in conjunction with BS EN 50086-1:1994 Specification for conduit systems for cable management Part 1: General requirements. The references to Part 1 should be read as references to BS EN 50086-1:1994 which is the Eng

11、lish language version of EN 50086-1:1993. A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations.

12、 Summary of pages This document comprises a front cover, an inside front cover, pages i and ii, the EN title page, pages 2 to 9 and a back cover. The BSI copyright notice displayed in this document indicates when the document was last issued. Copyright British Standards Institution Reproduced by IHS

13、 under license with BSI - Uncontrolled Copy Not for Resale No reproduction or networking permitted without license from IHS - - -EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 50086-2-2 May 1995 + A11 December 1998 ICS 29.120.10 Incorporating corrigendum February 2001 Descriptors: Electric wir

14、ing system, pliable conduit, mechanical characteristics, electrical characteristics, test English version Conduit systems for cable management Part 2-2: Particular requirements for pliable conduit systems (includes amendment A11:1998) Systmes de conduits pour la gestion du cblage Partie 2-2: Rgles p

15、articulires pour systmes de conduits cintrables (inclut lamendement A11:1998) Installationsrohrsysteme zum Fhren von Leitungen fr elektrische Energie und fr Information Teil 2-2: Besondere Anforderungen fr biegsame Elektroinstallationsrohrsysteme (enthlt nderung A11:1998) This European Standard was

16、approved by CENELEC on 1994-12-06. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such

17、national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own lan

18、guage and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden,

19、Switzerland and United Kingdom. CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B-1050 Brussels 1995 Copyright reserved to CENELEC members Ref. No

20、. EN 50086-2-2:1995 + A11:1998 E Copyright British Standards Institution Reproduced by IHS under license with BSI - Uncontrolled Copy Not for Resale No reproduction or networking permitted without license from IHS - - -EN 50086-2-2:1995 BSI 26 February 2002 2 Foreword This European Standard has been

21、 prepared by CENELEC Technical Committee TC 113, Cable management systems. The text of the draft was submitted to the formal vote and was approved by CENELEC as EN 50086-2-2 on 1994-12-06. This Part 2-2 specifies particular requirements for pliable conduit systems. A conduit system which complies wi

22、th this standard is deemed safe for use. The following dates were fixed: For products which have complied with the relevant national standard before 1996-12-01, as shown by the manufacturer or by a certification body, this previous standard may continue to apply for production until 2001-12-01. This

23、 Part 2-2 supplements or modifies the corresponding clauses of EN 50086-1:1993, Conduit systems for cable management Part 1: General requirements. Where a particular clause or subclause of Part 1 is not mentioned in this Part 2-2, that clause or subclause applies as far as is reasonable. Where this

24、Part 2-2 states “addition”, “modification” or “replacement”, the relevant text of Part 1 is to be adapted accordingly. Subclauses, tables and figures which are in addition to those in Part 1 are numbered starting with 101. Annexes which are in addition to those in Part 1 are labelled AA, BB, etc. Fo

25、reword to amendment A11 At the request of the Finnish electrotechnical committee, a draft for an amendment to EN 50086-2-2:1995 was submitted to the CENELEC members for acceptance in October 1998. The text of the draft was accepted by CENELEC as amendment A11 to EN 50086-2-2:1995 on 1998-12-16. The

26、following dates were fixed: Contents Page Foreword 2 1S c o p e 3 2 Normative references 3 3 Definitions 3 4 General requirements 3 5 General conditions for tests 3 6 Classification 3 7 Marking and documentation 3 8D i m e n s i o n s 3 9 Construction 4 10 Mechanical properties 4 11 Electrical prope

27、rties 5 12 Thermal properties 6 13 Fire effects 6 14 External influences 6 15 Electromagnetic compatibility 7 Annex A 7 Annex AA (informative) A-deviations 7 Figure 101 Bending test apparatus 7 Figure 102 Gauge for checking the minimum inside diameter after bending and resistance to heat tests 8 Fig

28、ure 103 Assembly of conduit and terminating fitting for bonding test 8 Table 101 Thread lengths 4 Table 102 Maximum entry diameter and minimum entry length details 4 latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement

29、 (dop) 1995-12-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 1996-12-01 latest date by which the existence of the amendment has to be announced at national level (doa) 1999-03-16 latest date by which the amendment has to be implemented at national

30、level by publication of an identical national standard or by endorsement (dop) 1999-06-16 Copyright British Standards Institution Reproduced by IHS under license with BSI - Uncontrolled Copy Not for Resale No reproduction or networking permitted without license from IHS - - -EN 50086-2-2:1995 BSI 26

31、 February 2002 3 1 Scope This clause of Part 1 is applicable, except as follows. Addition: This standard specifies the requirements for pliable conduit systems including self-recovering conduit systems. Conduit systems which are used as an integral part of other equipment also have to be tested acco

32、rding to the relevant standard for that equipment. 2 Normative references This clause of Part 1 is applicable. 3 Definitions This clause of Part 1 is applicable. 4 General requirements This clause of Part 1 is applicable. 5 General conditions for tests This clause of Part 1 is applicable. 6 Classifi

33、cation This clause of Part 1 is applicable, except as follows. 6.1.1.1, 6.1.2.1, 6.1.3.1, 6.1.3.4, 6.1.4.1 and 6.1.5.1 are not applicable. 7 Marking and documentation This clause of Part 1 is applicable, except as follows. Addition: 7.1.101 The conduit shall be marked in accordance with 7.1 at regul

34、ar intervals along its length of preferably 1 m but not longer than 3 m. Where this is technically impractical, the mark shall be on a label attached to the product at each end. Compliance is checked by inspection. 7.1.102 The manufacturer shall document for the system the minimum inside diameter an

35、d the classification in accordance with clause 6. Compliance is checked by inspection. 8 Dimensions Replacement: 8.1 Threads shall comply with EN 60423. Outside diameters of non-metallic conduits shall comply with EN 60423. Outside diameters of metallic and composite conduits need not comply with EN

36、 60423, providing they are used with terminating fittings with threads complying with EN 60423. Compliance is checked by means of the gauges specified in EN 60423. 8.2 Threadable conduits and threadable conduit fittings shall comply with Table 101. Non-threadable conduit fittings shall comply with T

37、able 102. The minimum inside diameter of the conduit system shall be declared by the manufacturer. Compliance is checked by measurement. Copyright British Standards Institution Reproduced by IHS under license with BSI - Uncontrolled Copy Not for Resale No reproduction or networking permitted without

38、 license from IHS - - -EN 50086-2-2:1995 4 BSI 26 February 2002 Table 101 Thread lengths Table 102 Maximum entry diameter and minimum entry length details 9 Construction This clause of Part 1 is applicable. 10 Mechanical properties This clause of Part 1 is applicable, except as follows. 10.2 Compres

39、sion test For self-recovering conduits, instead of 10.2.4, 10.2.5, 10.2.6, 10.2.7 and 10.2.8, the following applies. 10.2.101 The intermediate piece shall be submitted to a constantly increasing compression force (N) determined in such a way as to flatten the sample by an amount exceeding 25 % but n

40、ot exceeding 50 % of its initial outside diameter within 30 s. The compression force shall not be less than the values given in Table 4. The force and the intermediate piece shall then be removed. Fifteen minutes after removal, the outside diameter of the sample, where it has flattened, shall be mea

41、sured again. After the test, the difference between the initial outside diameter and the outside diameter of the flattened sample shall not exceed 10 % of the outside diameter, as measured before the test and the sample shall show no cracks visible to normal or corrected vision without magnification

42、. Size External thread Internal thread Minimum length (mm) Minimum length(mm) 6 8 10 12 16 20 25 32 40 50 63 75 05,5 06,5 08,5 10,5 12,5 14,0 17,0 19,0 19,0 19,0 19,0 19,0 06,5 07,5 09,5 11,5 13,5 15,0 18,0 20,0 20,0 20,0 20,0 20,0 Size Maximum entry diameter(mm) Minimum entry length(mm) 6 8 10 12 1

43、6 20 25 32 40 50 63 75 06,5 08,5 10,5 12,5 16,5 20,5 25,5 32,6 40,7 50,8 63,9 75,9 06,0 08,0 10,0 12,0 16,0 20,0 25,0 30,0 32,0 42,0 50,0 50,0 Copyright British Standards Institution Reproduced by IHS under license with BSI - Uncontrolled Copy Not for Resale No reproduction or networking permitted w

44、ithout license from IHS - - -EN 50086-2-2:1995 BSI 26 February 2002 5 10.4 Bending test 10.4.101 Conduits shall be subjected to a bending test by means of the apparatus shown in Figure 101. 10.4.102 The test shall be made on six samples of conduit, the length of each sample being at least: a) 30 tim

45、es the nominal outside diameter for plain conduits; b) 12 times the nominal outside diameter for corrugated conduits. Three of the samples shall be tested at the ambient temperature; the other three shall be tested at the declared transport, permanent application and installation temperature in acco

46、rdance with Table 1 with a tolerance of 2 C. 10.4.103 For the test at ambient temperature, the sample shall be clamped vertically in the bending apparatus in accordance with Figure 101. The sample shall be slowly bent by hand to the left through approximately 90 , back to the vertical position, to t

47、he right through approximately 90 , and back to the vertical position. This sequence of operations shall be repeated three more times but at the end the sample shall not be bent back to the vertical position. The sample shall be maintained in the bent position for 5 min, after which it shall be plac

48、ed in such a position that the straight portions are at 45 to the vertical, one end of the sample pointing upwards and the other downwards. For the test at the declared transport, permanent application and installation temperature, the sample clamped in the bending apparatus as shown in Figure 101 s

49、hall be conditioned for 2 h in a cold chamber at this temperature 2 C. After the test, the sample shall show no cracks visible to normal or corrected vision without magnification and it shall be possible to pass the appropriate gauge, in accordance with Figure 102, through the sample under its own weight and without any initial speed. 10.5 Flexing test This subclause of Part 1 is not app