1、BRITISH STANDARD BS EN 50266-2-3:2001 Incorporating Corrigendum No. 1 Common test methods for cables under fire conditions Test for vertical flame spread of vertically-mounted bunched wires or cables Part 2-3: Procedures Category B The European Standard EN 50266-2-3:2001 has the status of a British
2、Standard ICS 13.220.40; 29.060.20 Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELEC Not for Resale No reproduction or networking permitted without license from IHS - -BS EN 50266-2-3:2001 This British Standard, having been prepared under the
3、 direction of the Electrotechnical Sector Committee, was published under the authority of the Standards Committee and comes into effect on 15 August 2001 BSI 30 September 2002 ISBN 0 580 38032 7 National foreword This British Standard is the official English language version of EN 50266-2-3:2001, in
4、cluding Corrigendum March 2002. Together with BS EN 50266-1, BS EN 50266-2-1, BS EN 50266-2-2; BS EN 50266-2-4 and BS EN 50266-2-5, it supersedes BS 4066-3:1994 which is withdrawn. BS 4066-3: 1994 had a number of test categories. All these test categories are retained in BS EN 50266, and can be foun
5、d in the respective parts of the new publication as follows: The UK participation in its preparation was entrusted by Technical Committee GEL/20, Electric cables, to Subcommittee GEL/20/3, Insulation and sheath, which has the responsibility to: A list of organizations represented on this subcommitte
6、e can be obtained on request to its secretary. Cross-references The British Standards which implement international or European publications referred to in this document may be found in the BSI Catalogue under the section entitled “International Standards Correspondence Index”, or by using the “Sear
7、ch” facility of the BSI Electronic Catalogue or of British Standards Online. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard does not of itself confer immunity from legal ob
8、ligations. Test category in BS 4066-3 Equivalent part of BS EN 50266 a A F/R BS EN 50266-2-1 A BS EN 50266-2-2 B BS EN 50266-2-3 C BS EN 50266-2-4 BS EN 50266-2-5 b a In all cases, the particular part is to be used in conjunction with BS EN 50266-1, which describes the test apparatus. b This part de
9、scribes Category D, which did not form part of BS 4066-3. aid enquirers to understand the text; present to the responsible European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed; monitor related international and European developments and
10、promulgate them in the UK. Summary of pages This document comprises a front cover, an inside front cover, the EN title page, pages 2 to 11 and a back cover. The BSI copyright date displayed in this document indicates when the document was last issued. Amendments issued since publication Amd. No. Dat
11、e Comments 13854 Corrigendum No. 1 30 September 2002 Change to date of withdrawal in EN foreword Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELEC Not for Resale No reproduction or networking permitted without license from IHS - -EUROPEAN ST
12、ANDARD EN 50266-2-3 NORME EUROPENNE EUROPISCHE NORM February 2001 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels 2001 CENELEC -
13、 All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50266-2-3:2001 E ICS 13.220.40; 29.020; 29.060.20 Supersedes HD 405.3 S1:1993 Incorporating corrigendum March 2002 English version Common test methods for cables under fire conditions - Test
14、for vertical flame spread of vertically-mounted bunched wires or cables Part 2-3: Procedures - Category B Mthodes dessai communes aux cbles soumis au feu - Essai de propagation verticale de la flamme des fils ou cbles en nappes en position verticale Partie 2-3: Procdures - Catgorie B Allgemeine Prfv
15、erfahren fr Kabel und isolierte Leitungen im Brandfall - Prfung der senkrechten Flammenausbreitung von senkrecht angeordneten Bndeln von Kabeln und isolierten Leitungen Teil 2-3: Prfverfahren - Prfart B This European Standard was approved by CENELEC on 2000-08-01. CENELEC members are bound to comply
16、 with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secre
17、tariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as t
18、he official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom. Copyright European Com
19、mittee for Electrotechnical Standardization Provided by IHS under license with CENELEC Not for Resale No reproduction or networking permitted without license from IHS - -EN 50266-2-3:2001 - 2 - Foreword This European Standard was prepared by Working Group 10 of the Technical Committee CENELEC TC 20,
20、 Electric cables. When used in conjunction with EN 50266-1 this European Standard supersedes HD 405.3 S1 in respect of test category B. All pre-existing categories of test from HD 405.3 S1 have been retained and updated in the different parts 2. A new category (Category D) has been added to cater fo
21、r testing at very low non-metallic volumes. The description of the apparatus given in EN 50266-1 updates that in HD 405.3 S1. The text of the draft was submitted to the Unique Acceptance procedure and was approved by CENELEC as EN 50266-2-3 on 2000-08-01. The following dates were fixed: - latest dat
22、e by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2001-08-01 - latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2002-08-01 Annexes designated normative are part of the body
23、of the standard. Annexes designated informative are given for information only. In this standard, annex A is normative and annex B is informative. _ Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELEC Not for Resale No reproduction or networki
24、ng permitted without license from IHS - - 3 - EN 50266-2-3:2001 Contents Page Introduction4 1 Scope5 2 Normative references .5 3 Definitions .5 3.1 Ignition source 5 3.2 Char5 3.3 Flame spread .5 4 Test apparatus6 4.1 General.6 4.2 Ignition source 6 5 Test procedure .6 5.1 Test sample6 5.2 Determina
25、tion of number of test pieces .6 5.3 Mounting of the test sample .7 5.4 Flame application time .7 6 Evaluation of test results.7 7 Performance requirements.8 8 Retest procedure 8 9 Test report 8 Annex A (normative) Guidance on cable selection for type approval testing 10 Annex B (informative) Recomm
26、ended performance requirements.11 Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELEC Not for Resale No reproduction or networking permitted without license from IHS - -EN 50266-2-3:2001 - 4 - Introduction Methods of test for flame spread char
27、acteristics for a single vertical insulated wire or cable are given in EN 50265, but it cannot be assumed that, because a cable or wire meets the requirements of that standard, a vertical bunch of similar cables or wires will behave in a similar manner. This is because flame spread along a vertical
28、bunch of cables depends on a number of features, such as: a) the volume of combustible material exposed to the fire and to any flame which may be produced by the combustion of the cables; b) the geometrical configuration of the cables and their relationship to an enclosure; c) the temperature at whi
29、ch it is possible to ignite the gases emitted from the cables; d) the quantity of combustible gas released from the cables for a given temperature rise; e) the volume of air passing through the cable installation; f) the construction of the cable, e.g. armoured or unarmoured, multi or single core. A
30、ll of the foregoing assume that the cables are able to be ignited when involved in an external fire. EN 50266 gives details, in various parts, of a test where a number of cables are bunched together to form various test sample installations. For easier use and differentiation of the apparatus and th
31、e various test categories, the parts are designated as follows: Part 1 Apparatus Part 2-1 Category A F/R Part 2-2 Category A Part 2-3 Category B Part 2-4 Category C Part 2-5 Category D Parts from 2-1 onwards define the various categories and the relevant procedures. The categories are distinguished
32、by test duration, the volume of non-metallic material of the test sample and the method of mounting the sample for the test. In all categories, cables having at least one conductor of cross-sectional area greater than 35 mm are tested in a spaced configuration, whereas cables of conductor cross-sect
33、ional area of 35 mm or smaller are tested in a touching configuration. The categories are not necessarily related to different safety levels in actual cable installations. The actual installed configuration of the cables may be a major determinant in the level of flame spread occurring in an actual
34、fire. The method of mounting described as Category A F/R (part 2-1) is intended for special cable designs used in particular installations. Categories A, B, C and D (parts 2-2 to 2-5 respectively) are for general use where different non-metallic volumes are applicable. Additional categories, especia
35、lly to cover the use of small diameter communication cables in closely bunched configurations, will be further considered when more data is available. Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELEC Not for Resale No reproduction or networ
36、king permitted without license from IHS - - 5 - EN 50266-2-3:2001 1 Scope EN 50266 specifies methods of test for the assessment of vertical flame spread of vertically-mounted bunched wires or cables, electrical or optical, under defined conditions. NOTE For the purpose of this standard the term elec
37、tric wire or cable covers all insulated metallic conductor cables used for the conveyance of energy or signals. The test is intended for type approval testing. The requirements for the selection of cables for testing are given in annex A. The flame spread is measured as the extent of damage of the c
38、able sample. This procedure may be used to demonstrate the cables ability to limit flame spread. This part 2-3 covers Category B and relates to cables installed on the test ladder to achieve a nominal total volume of non-metallic material of 3,5 litres per metre of test sample. The flame application
39、 time is 40 min. The method of mounting uses the front of the standard ladder. The category is intended for general use where medium volumes of non-metallic material are required to be evaluated. A recommended performance requirement is given in annex B. 2 Normative references This European Standard
40、 incorporates by dated or undated reference, provisions from other publications. These normative references are cited at the appropriate places in the text and the publications are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to thi
41、s European Standard only when incorporated in it by amendment or revision. For undated references the latest edition of the publication referred to applies. EN 50266-1 Common test methods for cables under fire conditions - Test for vertical flame spread of vertically-mounted bunched wires or cables
42、- Part 1 : Apparatus EN 60695-4 Fire hazard testing - Part 4: Terminology concerning fire tests EN 60811-1-3 Insulating and sheathing materials of electric cables - Common test methods Part 1- 3: General application - Methods for determining the density - Water absorption tests - Shrinkage test 3 De
43、finitions For the purpose of this EN 50266-2-3 the following definitions apply. Definitions are taken from EN 60695-4. 3.1 ignition source a source of energy that initiates combustion 3.2 char carbonaceous residue resulting from pyrolysis or incomplete combustion 3.3 flame spread propagation of a fl
44、ame front Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELEC Not for Resale No reproduction or networking permitted without license from IHS - -EN 50266-2-3:2001 - 6 - 4 Test apparatus 4.1 General The apparatus specified in EN 50266-1 shall b
45、e used. 4.2 Ignition source The ignition source shall be one ribbon-type propane gas burner as specified in EN 50266-1. 5 Test procedure 5.1 Test sample The test sample shall comprise a number of test pieces of cable from the same production length, each having a minimum length of 3,5 m. The total n
46、umber of test pieces in the test sample shall be that number required to provide a nominal total volume of non-metallic material of 3,5 litres per metre of test sample. The test sample shall be chosen within the limitations given in annex A. The test pieces forming the test sample shall be condition
47、ed at a temperature of (20 10) C for at least 16 h before commencing the test. The test pieces shall be dry. 5.2 Determination of the number of test pieces In order to calculate the appropriate number of test pieces, it is necessary to determine the volume per metre of non-metallic material of one t
48、est piece. A length of cable which shall not be less than 0,3 m long is carefully cut to ensure that the surfaces are at right angles to the cable axis, thus enabling precise measurements of its length. The density of each non-metallic component (including cellular material) shall be measured in an
49、appropriate way, e.g. clause 8 of EN 60811-1-3, in order to obtain values expressed to the second decimal place. Each non-metallic material C ishall be removed from the test piece and weighed. Any non-metallic material making up less than 5 % of the total non-metallic weight of the test piece shall be assumed to have a density of 1,0 kg/dm.