资源描述

1、Designation: E119 18bE119 18c An American National StandardStandard Test Methods forFire Tests of Building Construction and Materials1This standard is issued under the fixed designation E119; the number immediately following the designation indicates the year oforiginal adoption or, in the case of r

2、evision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.INTRODUCTIONThe perform

3、ance of walls, columns, floors, and other building members under fire-exposureconditions is an item of major importance in securing constructions that are safe, and that are not amenace to neighboring structures or to the public. Recognition of this is registered in the codes ofmany authorities, mun

4、icipal and other. It is important to secure balance of the many units in a singlebuilding, and of buildings of like character and use in a community; and also to promote uniformityin requirements of various authorities throughout the country. To do this it is necessary that thefire-resistive propert

5、ies of materials and assemblies be measured and specified according to a commonstandard expressed in terms that are applicable alike to a wide variety of materials, situations, andconditions of exposure.Such a standard is found in the test methods that follow. They prescribe a standard exposing fire

6、 ofcontrolled extent and severity. Performance is defined as the period of resistance to standard exposureelapsing before the first critical point in behavior is observed. Results are reported in units in whichfield exposures can be judged and expressed.The test methods may be cited as the “Standard

7、 Fire Tests,” and the performance or exposure shallbe expressed as “2-h,” “6-h,” “12-h,” etc.When a factor of safety exceeding that inherent in the test conditions is desired, a proportionalincrease should be made in the specified time-classification period.1. Scope*1.1 The test methods described in

8、 this fire-test-response standard are applicable to assemblies of masonry units and to compositeassemblies of structural materials for buildings, including loadbearing and other walls and partitions, columns, girders, beams,slabs, and composite slab and beam assemblies for floors and roofs. They are

9、 also applicable to other assemblies and structuralunits that constitute permanent integral parts of a finished building.1.2 It is the intent that classifications shall register comparative performance to specific fire-test conditions during the periodof exposure and shall not be construed as having

10、 determined suitability under other conditions or for use after fire exposure.1.3 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame undercontrolled conditions, but does not by itself incorporate all factors required for fire hazard or

11、fire risk assessment of the materials,products or assemblies under actual fire conditions.1.4 These test methods prescribe a standard fire exposure for comparing the test results of building construction assemblies. Theresults of these tests are one factor in assessing predicted fire performance of

12、building construction and assemblies. Applicationof these test results to predict the performance of actual building construction requires the evaluation of test conditions.1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematicalconve

13、rsions to SI units that are provided for information only and are not considered standard.1 These test methods are under the jurisdiction of ASTM Committee E05 on Fire Standards and are the direct responsibility of Subcommittee E05.11 on Fire Resistance.Current edition approved Sept. 1, 2018Nov. 1,

14、2018. Published October 2018November 2018. Originally approved in 1917 as C19-1917 T. Last previous edition approvedin 2018 as E119 18a.E119 18b. DOI: 10.1520/E0119-18B.10.1520/E0119-18C.These test methods, of which the present standard represents a revision, were prepared by Sectional Committee on

15、Fire Tests of Materials and Construction, under thejoint sponsorship of the National Bureau of Standards, the ANSI Fire Protection Group, and ASTM, functioning under the procedure of the American National StandardsInstitute.This document is not an ASTM standard and is intended only to provide the us

16、er of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard a

17、s published by ASTM is to be considered the official document.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States11.6 This standard does not purport to address all of the sa

18、fety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability ofregulatory limitations prior to use.1.7 The text of this standard references notes and footnotes

19、 which provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be considered as requirements of the standard.1.8 This international standard was developed in accordance with internationally recognized principles on standardizationestablished in the De

20、cision on Principles for the Development of International Standards, Guides and Recommendations issuedby the World Trade Organization Technical Barriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2C569 Test Method for Indentation Hardness of Preformed Thermal Insulations (Wit

21、hdrawn 1988)3D6513 Practice for Calculating the Superimposed Load on Wood-frame Walls for Standard Fire-Resistance TestsE176 Terminology of Fire StandardsE177 Practice for Use of the Terms Precision and Bias in ASTM Test MethodsE691 Practice for Conducting an Interlaboratory Study to Determine the P

22、recision of a Test MethodE814 Test Method for Fire Tests of Penetration Firestop SystemsE2226 Practice for Application of Hose Stream3. Terminology3.1 DefinitionsFor definitions of terms found in this test method, refer to Terminology E176.4. Significance and Use4.1 These test methods are intended t

23、o evaluate the duration for which the types of building elements noted in 1.1 contain a fire,retain their structural integrity, or exhibit both properties during a predetermined test exposure.4.2 The test exposes a test specimen to a standard fire controlled to achieve specified temperatures through

24、out a specified timeperiod. When required, the fire exposure is followed by the application of a specified standard fire hose stream applied inaccordance with Practice E2226. The test provides a relative measure of the fire-test-response of comparable building elementsunder these fire exposure condi

25、tions. The exposure is not representative of all fire conditions because conditions vary with changesin the amount, nature and distribution of fire loading, ventilation, compartment size and configuration, and heat sink characteristicsof the compartment. Variation from the test conditions or test sp

26、ecimen construction, such as size, materials, method of assembly,also affects the fire-test-response. For these reasons, evaluation of the variation is required for application to construction in thefield.4.3 The test standard provides for the following:4.3.1 For walls, partitions, and floor or roof

27、 test specimens:4.3.1.1 Measurement of the transmission of heat.4.3.1.2 Measurement of the transmission of hot gases through the test specimen.4.3.1.3 For loadbearing elements, measurement of the load carrying ability of the test specimen during the test exposure.4.3.2 For individual loadbearing mem

28、bers such as beams and columns:4.3.2.1 Measurement of the load carrying ability under the test exposure with consideration for the end support conditions (thatis, restrained or not restrained).4.4 The test standard does not provide the following:4.4.1 Information as to performance of test specimens

29、constructed with components or lengths other than those tested.4.4.2 Evaluation of the degree by which the test specimen contributes to the fire hazard by generation of smoke, toxic gases,or other products of combustion.4.4.3 Measurement of the degree of control or limitation of the passage of smoke

30、 or products of combustion through the testspecimen.4.4.4 Simulation of the fire behavior of joints between building elements such as floor-wall or wall-wall, etc., connections.4.4.5 Measurement of flame spread over the surface of test specimens.4.4.6 The effect on fire-resistance of conventional op

31、enings in the test specimen, that is, electrical receptacle outlets, plumbingpipe, etc., unless specifically provided for in the construction tested. Also see Test Method E814 for testing of fire stops.2 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Servi

32、ce at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.3 The last approved version of this historical standard is referenced on www.astm.org.E119 18c25. Test Specimen5.1 The test specimen shall be representative of

33、 the construction that the test is intended to assess, as to materials, workmanship,and details such as dimensions of parts, and shall be built under conditions representative of those applied in building constructionand operation. The physical properties of the materials and ingredients used in the

34、 test specimen shall be determined and recorded.5.2 The size and dimensions of the test specimen specified herein shall apply for classifying constructions of dimensions withinthe range employed in buildings. When the conditions of use limit the construction to smaller dimensions, the dimensions of

35、thetest specimen shall be reduced proportionately for a test qualifying them for such restricted use.5.3 Test specimens designed with a built-up roof shall be tested with a roof covering of 3-ply, 15-lb (6.8-kg) 3 ply, 15 lb (6.8kg) type felt, with not more than 120 lb (54 kg) per square (100 ft2 (9

36、 m2) of hot mopping asphalt without gravel surfacing. Testswith this covering do not preclude the field use of other coverings with a larger number of plys of felt, with a greater amount ofasphalt or with gravel surfacing.5.4 Roofing systems designed for other than the use of built-up roof coverings

37、 shall be tested using materials and details ofconstruction representative of field application.6. Protection and Conditioning of Test Specimen6.1 Protect the test specimen during and after fabrication to ensure its quality and condition at the time of test. The test specimenshall not be tested unti

38、l its required strength has been attained, and, until an air-dry condition has been achieved in accordance withthe requirements given in 6.2 6.4. Protect the testing equipment and test specimen undergoing the fire-resistance test from anycondition of wind or weather that is capable of affecting resu

39、lts. The ambient air temperature at the beginning of the test shall bewithin the range of 50 to 90F (10 to 32C). The velocity of air across the unexposed surface of the test specimen, measured justbefore the test begins, shall not exceed 4.4 ft (1.3 m/s), as determined by an anemometer placed at rig

40、ht angles to the unexposedsurface. When mechanical ventilation is employed during the test, an air stream shall not be directed across the surface of the testspecimen.6.2 Prior to the fire-resistance test, condition test specimens with the objective of providing moisture condition within the testspe

41、cimen representative of that in similar construction in buildings. For purposes of standardization, this condition is establishedat equilibrium resulting from conditioning in an ambient atmosphere of 50 % relative humidity at 73F (Note 1).6.2.1 With some constructions it is difficult or impossible t

42、o achieve such uniformity. Where this is the case, test specimens aretested when the dampest portion of the test specimen, or the portion at 6-in. (152-mm) depth below the surface of massiveconstructions, has achieved a moisture content corresponding to conditioning to equilibrium with air in the ra

43、nge of 50 to 75 %relative humidity at 73 6 5F (23 6 3C).6.2.2 When evidence is shown that test specimens conditioned in a heated building will fail to meet the requirements of 6.2 aftera 12-month conditioning period, or in the event that the nature of the construction is such that it is evident that

44、 conditioning ofthe test specimen interior is prevented by hermetic sealing, the moisture condition requirements of 6.2 are permitted to be waived,and either 6.2.2.1 or 6.2.2.2 shall apply.6.2.2.1 Alternative conditioning methods are permitted to be used to achieve test specimen equilibrium prescrib

45、ed in 6.2 (Note2), or6.2.2.2 The specimen tested when its strength is at least equal to its design strength after a minimum 28 day conditioning period.6.3 Avoid conditioning procedures that will alter the structural or fire-resistance characteristics of the test specimen from thoseproduced as the re

46、sult of conditiong in accordance with procedures given in 6.2.6.4 Information on the actual moisture content and distribution within the test specimen shall be obtained within 72 h prior tothe fire. Include this information in the test report (Note 3).NOTE 1A recommended method for determining the r

47、elative humidity within a hardened concrete test specimen with electric sensing elements isdescribed in Appendix I of the paper by Menzel, C. A., “A Method for Determining the Moisture Condition of Hardened Concrete in Terms of RelativeHumidity,” Proceedings,ASTM,Vol 55, 1955, p. 1085.Asimilar proce

48、dure with electric sensing elements is permitted to be used to determine the relativehumidity within test specimens made with other materials.With wood constructions, the moisture meter based on the electrical resistance method can be used, when appropriate, as an alternative to the relativehumidity

49、 method to indicate when wood has attained the proper moisture content. Electrical methods are described on page 12-2 of the 1999 edition ofthe Wood Handbook of the Forest Products Laboratory, U.S. Department ofAgriculture.The relationships between relative humidity and moisture contentare given in Table 3-4 on p. 3-7. This indicates that wood has a moisture content of 13 % at a relative humidity of 70 % for a temperature of 70 to 80F(21 to 27C).NOTE 2An example where alternative conditioning may be employed is where concrete specimens are conditioned at elevated te

展开阅读全文
相关资源
猜你喜欢
  • BS ISO IEC 15773-1998 Information technology - Telecommunications and information exchange between systems - Broadband private integrated services network - Inter-exchange signalli .pdf BS ISO IEC 15773-1998 Information technology - Telecommunications and information exchange between systems - Broadband private integrated services network - Inter-exchange signalli .pdf
  • BS ISO IEC 15944-10-2013 Information technology Business Operational View IT-enabled coded domains as semantic components in business transactions《信息技术 商业运作视图 作为商业交易中语义成分的启用IT编码的领域.pdf BS ISO IEC 15944-10-2013 Information technology Business Operational View IT-enabled coded domains as semantic components in business transactions《信息技术 商业运作视图 作为商业交易中语义成分的启用IT编码的领域.pdf
  • BS ISO IEC 15944-5-2008 Information technology - Business operational view - Identification and referencing of requirements of jurisdictional domains as sources of external constra.pdf BS ISO IEC 15944-5-2008 Information technology - Business operational view - Identification and referencing of requirements of jurisdictional domains as sources of external constra.pdf
  • BS ISO IEC 15944-8-2012 Information technology Business Operational View Identification of privacy protection requirements as external constraints on business transactions《信息技术 商业运.pdf BS ISO IEC 15944-8-2012 Information technology Business Operational View Identification of privacy protection requirements as external constraints on business transactions《信息技术 商业运.pdf
  • BS ISO IEC 15945-2002 Information technology - Security techniques - Specification of TTP services to support the application of digital signatures《信息技术 安全性技术 对数字签字进行支持的TTP服务业务的规范》.pdf BS ISO IEC 15945-2002 Information technology - Security techniques - Specification of TTP services to support the application of digital signatures《信息技术 安全性技术 对数字签字进行支持的TTP服务业务的规范》.pdf
  • BS ISO IEC 15946-5-2017 Information technology Security techniques Cryptographic techniques based on elliptic curves Elliptic curve generation《信息技术 安全技术 基于椭圆曲线的密码技术 椭圆曲线类生成》.pdf BS ISO IEC 15946-5-2017 Information technology Security techniques Cryptographic techniques based on elliptic curves Elliptic curve generation《信息技术 安全技术 基于椭圆曲线的密码技术 椭圆曲线类生成》.pdf
  • BS ISO IEC 15961-1-2013 Information technology Radio frequency identification (RFID) for item management Data protocol Application interface《信息技术 项目管理的射频识别(RFID) 数据协议 应用接口》.pdf BS ISO IEC 15961-1-2013 Information technology Radio frequency identification (RFID) for item management Data protocol Application interface《信息技术 项目管理的射频识别(RFID) 数据协议 应用接口》.pdf
  • BS ISO IEC 15961-2004 Information technology - Radio frequency identification (RFID) for item management - Data protocol - Application interface《信息技术 项目管理的射频识别(RFID) 数据协议 应用接口》.pdf BS ISO IEC 15961-2004 Information technology - Radio frequency identification (RFID) for item management - Data protocol - Application interface《信息技术 项目管理的射频识别(RFID) 数据协议 应用接口》.pdf
  • BS ISO IEC 15961-4-2016 Information technology Radio frequency identification (RFID) for item management Data protocol Application interface commands for battery assist and sensor .pdf BS ISO IEC 15961-4-2016 Information technology Radio frequency identification (RFID) for item management Data protocol Application interface commands for battery assist and sensor .pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > ASTM

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1