1、IEEE Guide for Electrical and Control Design of Hydroelectric Water Conveyance Facilities IEEE Std 1827-2016 IEEE Power and Energy Society Sponsored by the Energy Development and Power Generation Committee IEEE 3 Park Avenue New York, NY 10016-5997 USAIEEE Std 1827-2016 IEEE Guide for Electrical and

2、 Control Design of Hydroelectric Water Conveyance Facilities Sponsor Energy Development and Power Generation Committee of the IEEE Power and Energy Society Approved 7 December 2016 IEEE-SA Standards BoardAbstract: Electrical and control design of water conveyance facilities associated with hydroelec

3、 tric projects including associated penstocks, valves, and gates are described in this guide. Guid- ance to plan and prepare designs is included. Installation, operation, or maintenance guideline and methodologies are not included. Design of new facilities and rehabilitation or replacement of exist

4、ing facilities is covered. Comprehensive considerations for design, monitoring, control, protec- tion, and operation of water conveyance facilities associated with hydroelectric projects is provided. Guidance in electrical and instrumentation work unique to water conveyance systems is provided. Guid

5、ance for the safe control of water release systems, bypass systems, and failure modes are provided. Reliability measures such as redundancy and power source considerations are provided. Gate and valve types and associated operating mechanisms are introduced. Power and non-power water conduits includ

6、ing penstocks, tunnels, and canals are covered. Keywords: control, conveyance, design, electrical, gate, hydroelectric, IEEE 1827, monitoring, penstock, protection, valve, water The Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue, New York, NY 10016-5997, USA Copyright 2017 by

7、The Institute of Electrical and Electronics Engineers, Inc. All rights reserved. Published 31 March 2017. Printed in the United States of America. IEEE is a registered trademark in the U.S. Patent fitness for a particular purpose; non-infringement; and quality, accuracy, effectiveness, currency, or

8、completeness of material. In addition, IEEE disclaims any and all conditions relating to: results; and workmanlike effort. IEEE standards documents are supplied “AS IS” and “WITH ALL FAULTS.” Use of an IEEE standard is wholly voluntary. The existence of an IEEE standard does not imply that there are

9、 no other ways to produce, test, measure, purchase, market, or provide other goods and services related to the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved and issued is subject to change brought about through developments in the state of the ar

10、t and comments received from users of the standard. In publishing and making its standards available, IEEE is not suggesting or rendering professional or other services for, or on behalf of, any person or entity nor is IEEE undertaking to perform any duty owed by any other person or entity to anothe

11、r. Any person utilizing any IEEE Standards document, should rely upon his or her own independent judgment in the exercise of reasonable care in any given circumstances or, as appropri- ate, seek the advice of a competent professional in determining the appropriateness of a given IEEE standard. IN NO

12、 EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY , OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO: PROCURE- MENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY , WHET

13、HER IN CON- TRACT, STRICT LIABILITY , OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE UPON ANY STANDARD, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND REGARDLESS OF WHETHER SUCH DAMAGE WAS FORESEEABLE.4 Copyright 2017 IEEE. All right

14、s reserved. Translations The IEEE consensus development process involves the review of documents in English only. In the event that an IEEE standard is translated, only the English version published by IEEE should be considered the approved IEEE standard. Official statements A statement, written or

15、oral, that is not processed in accordance with the IEEE-SA Standards Board Operations Manual shall not be considered or inferred to be the official position of IEEE or any of its committees and shall not be considered to be, or be relied upon as, a formal position of IEEE. At lectures, symposia, sem

16、inars, or educational courses, an individual presenting information on IEEE standards shall make it clear that his or her views should be considered the personal views of that individual rather than the formal position of IEEE. Comments on standards Comments for revision of IEEE Standards documents

17、are welcome from any interested party, regardless of membership affiliation with IEEE. However, IEEE does not provide consulting information or advice pertain- ing to IEEE Standards documents. Suggestions for changes in documents should be in the form of a proposed change of text, together with appr

18、opriate supporting comments. Since IEEE standards represent a consensus of concerned interests, it is important that any responses to comments and questions also receive the concur- rence of a balance of interests. For this reason, IEEE and the members of its societies and Standards Coordi- nating C

19、ommittees are not able to provide an instant response to comments or questions except in those cases where the matter has previously been addressed. For the same reason, IEEE does not respond to interpretation requests. Any person who would like to participate in revisions to an IEEE standard is wel

20、come to join the relevant IEEE working group. Comments on standards should be submitted to the following address: Secretary, IEEE-SA Standards Board 445 Hoes Lane Piscataway, NJ 08854 USA Laws and regulations Users of IEEE Standards documents should consult all applicable laws and regulations. Compl

21、iance with the provisions of any IEEE Standards document does not imply compliance to any applicable regulatory require- ments. Implementers of the standard are responsible for observing or referring to the applicable regulatory requirements. IEEE does not, by the publication of its standards, inten

22、d to urge action that is not in compliance with applicable laws, and these documents may not be construed as doing so. Copyrights IEEE draft and approved standards are copyrighted by IEEE under US and international copyright laws. They are made available by IEEE and are adopted for a wide variety of

23、 both public and private uses. These include both use, by reference, in laws and regulations, and use in private self-regulation, standardization, and the pro- motion of engineering practices and methods. By making these documents available for use and adoption by public authorities and private user

24、s, IEEE does not waive any rights in copyright to the documents.5 Copyright 2017 IEEE. All rights reserved. Photocopies Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to photocopy portions of any individual standard for company or organizational int

25、ernal use or individual, non-commercial use only. To arrange for payment of licensing fees, please contact Copyright Clearance Center, Customer Ser- vice, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions of any individual standard for educational classroom

26、 use can also be obtained through the Copyright Clearance Center. Updating of IEEE Standards documents Users of IEEE Standards documents should be aware that these documents may be superseded at any time by the issuance of new editions or may be amended from time to time through the issuance of amen

27、dments, corri- genda, or errata. An official IEEE document at any point in time consists of the current edition of the document together with any amendments, corrigenda, or errata then in effect. Every IEEE standard is subjected to review at least every 10 years. When a document is more than 10 year

28、s old and has not undergone a revision process, it is reasonable to conclude that its contents, although still of some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the latest edition of any IEEE standard. In order to determine wh

29、ether a given document is the current edition and whether it has been amended through the issuance of amendments, corrigenda, or errata, visit IEEE Xplore at http:/ieeexplore.ieee.org or contact IEEE at the address listed previously. For more information about the IEEE SA or IEEEs standards develop-

30、 ment process, visit the IEEE-SA Website at http:/standards.ieee.org. Errata Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following URL: http:/ standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata periodically. Paten

31、ts Attention is called to the possibility that implementation of this standard may require use of subject matter covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to the existence or validity of any patent rights in connection therewith. If a pa

32、tent holder or patent applicant has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the IEEE- SA Website at http:/standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may indicate whether the Submitter is willing or unwilling to

33、grant licenses under patent rights without compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of any unfair discrim- ination to applicants desiring to obtain such licenses. Essential Patent Claims may exist for which a Letter of Assurance has not

34、been received. The IEEE is not re- sponsible for identifying Essential Patent Claims for which a license may be required, for conducting inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or conditions provided in connection with submission of a

35、Letter of Assurance, if any, or in any licensing agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that determination of the valid- ity of any patent rights, and the risk of infringement of such rights, is entirely their own responsibility. Further informa

36、tion may be obtained from the IEEE Standards Association.6 Copyright 2017 IEEE. All rights reserved. Participants At the time this IEEE guide was completed, the Electrical and Control Design of Hydroelectric Water Conveyance Facilities Working Group had the following membership: Eric V aughn, Chair

37、David Apps, Vice Chair Jay Anders Ian Backus Mathieu Bergeron Edson Bortoni Frances Brinkman Derek Brown Lucas DeLong George Girgis Bret Gregory Randall Groves Karen Hedlund David Kornegay Gustavo Marjovsky Eric Mendlin Ravi Mutukutti-Arachchige Douglas Seely Roberto Siniscalchi Phil Spotts Wayne Ti

38、mm James V olk John Yale The following members of the individual balloting committee voted on this guide. Balloters may have voted for approval, disapproval, or abstention. David Apps Ian Backus Mathieu Bergeron Frances Brinkman Steven Brockschink Chris Brooks Derek Brown Gustavo Brunello Paul Cardi

39、nal Matthew Davis Lucas Delong Gary Donner Rostyslaw Fostiak Randall Groves James Gurney Werner Hoelzl Noriyuki Ikeuchi Piotr Karocki Yuri Khersonsky Lucas Kunz Mikhail Lagoda Charles Lennon Albert Livshitz Lawrenc Long Arthur Neubauer Michael Newman Branimir Petosic Bartien Sayogo Uwe Seeger Dougla

40、s Seely Robert Seitz Jeremy Smith Jerry Smith Gary Smullin Wayne Timm Eric Vaughn John Vergis James V olk Kenneth White John Yale When the IEEE-SA Standards Board approved this guide on 7 December 2016, it had the following membership: Jean-Philippe Faure, Chair Ted Burse, Vice Chair John D. Kulick,

41、 Past Chair Konstantinos Karachalios, Secretary Chuck Adams Masayuki Ariyoshi Stephen Dukes Jianbin Fan J. Travis Griffith Gary Hoffman Ronald W. Hotchkiss Michael Janezic Joseph L. Koepfinger* Hung Ling Kevin Lu Annette D. Reilly Gary Robinson Mehmet Ulema Yingli Wen Howard Wolfman Don Wright Yu Yuan Daidi Zhong *Member Emeritus

展开阅读全文
相关资源
  • IEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdfIEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdf
  • IEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdfIEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdf
  • IEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdfIEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdf
  • IEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdfIEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdf
  • IEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdfIEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdf
  • IEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdfIEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdf
  • IEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdfIEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdf
  • IEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdfIEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdf
  • IEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdfIEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdf
  • IEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdfIEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > IEC

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1