1、IEEE Std 45-1998_InterpretationIEEE Standards Interpretation for IEEE Std 45-1998IEEE Recommended Practice for Electric Installations on ShipboardCopyright 2004 by the Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue New York, New York 10016-5997 USA All Rights Reserved.This is

2、an interpretation of IEEE Std 45-1998. Interpretations are issued to explain and clarify the intent of a standard and are not intended to constitute an alteration to the original standard or to supply consulting information. Permission is hereby granted to download and print one copy of this documen

3、t. Individuals seeking permission to reproduce and/or distribute this document in its entirety or portions of this document must contact the IEEE Standard Department for the appropriate license. Use of the information contained in this document is at your own risk.IEEE Standards Department Copyright

4、s and Permissions 445 Hoes Lane, P. O. Box 1331 Piscataway, New Jersey 08855-1331, USAApril 9, 2004 Interpretation Number: #1 Clause No: 8.11 Interpretation requestWhat are the reasons and rationale for IEEEs requirement in subclause 8.11 as to why cable should not be painted? Subclause 8.11 states

5、that, “cables should not be painted except 5000V types, which may be painted yellow.“ http:/standards.ieee.org/reading/ieee/interp/45-1998.html (1 of 3) 2009/01/06 7:04:08 PMIEEE Std 45-1998_InterpretationInterpretation for IEEE Std IEEE Std 45-1998 The request for interpretation applies to IEEE Std

6、 45-1998 which has been superseded by IEEE Std 45-2002. Specific to the 1998 standard. Subclause 8.11 - Paint applies to cable construction only. Painting of power control and other cables rated 600 volt for use identification was not recommended. SKV cables could be identified as a 5KV circuit by u

7、sing a yellow color. This could be a yellow compound or yellow paint. As stated, this applies to cable construction only and does not apply to any cables upon or after installation. There is no prohibition of painting cables after installation. Painting after installation should have no affect on ca

8、ble operation. However, this covers up all cable identification as to number and conductor size, as well as voltage rating. This would make trouble shooting very difficult. There is also no flame propagation test data on painted cables. Interpretation Number: #2 Clause Nos: 11.39.1 and 13.1 Interpre

9、tation request #2IEEE Recommended Practice for Electrical Installations on Shipboard. (45-1998) subclause 11.39.1, third paragraph states: “ Fuses should not, and circuit breakers need not be provided for the neutral of a circuit.“ Part 13.1, Distribution panels, third paragraph states: “Circuit bre

10、akers in grounded neutral distribution panels should include a pole or switch for the neutral.“We are building two high-speed catamaran aluminum car and passenger ferries. The electrical distribution system includes 208 /120 vac four wire with the neutral grounded to the hull. How subclauses 11.39.1

11、 and 13.1 are interpreted will determine if single pole or two-pole circuit http:/standards.ieee.org/reading/ieee/interp/45-1998.html (2 of 3) 2009/01/06 7:04:08 PMIEEE Std 45-1998_Interpretationbreakers are required in distribution panels and ultimately affect the weight and size of the distributio

12、n panels.Interpretation #2 for IEEE Std 45-1998Subclause 11.39.1 quoted is actually 11.39.1.15. This is covered in subclause 5.9.6.6 in the IEEE Std 45-2002 regarding system grounding. It states “fuses should not and circuit breakers need not be provided for the neutral circuit. Fuses should not be

13、used and circuit breakers are not required.“Subclause 13.1 - Distribution panels (fifth paragraph). This is covered in subclause 17.1 of the 2002 revision of IEEE Std 45. It reads, circuit breakers in grounded neutral distribution panels “may“ include a pole to simultaneously switch the neutral.This

14、 revision (IEEE Std 45-2002) states that a circuit breaker for switching the neutral may be installed, but it is not a requirement. The addition of a two- pole breaker for neutral switching is the choice of the designer or user and this is not a requirement.Copyright 2004 IEEE. All rights reserved.Back to Available IEEE Standards Interpretations Online Copyright IEEE-SA Contact IEEE-SA For questions or comments, please contact the IEEE-SA Webmaster. http:/standards.ieee.org/reading/ieee/interp/45-1998.html (3 of 3) 2009/01/06 7:04:08 PM

展开阅读全文
相关资源
  • IEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdfIEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdf
  • IEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdfIEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdf
  • IEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdfIEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdf
  • IEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdfIEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdf
  • IEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdfIEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdf
  • IEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdfIEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdf
  • IEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdfIEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdf
  • IEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdfIEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdf
  • IEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdfIEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdf
  • IEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdfIEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > IEC

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1