资源描述

1、IEEE Standards Interpretations for IEEE Std C37.04 -1999,IEEE Std C37.06-2000,and IEEE Std C37.09-1999 Copyright 2010 by the Institute of Electrical and Electronics Engineers, Inc. Three Park Avenue New York, New York 10016-5997 USA All Rights Reserved. This is an interpretation of IEEE Std C37.04-1

2、999, IEEE Std C37.06-2000, and IEEE Std C37.09-1999. Interpretations are issued to explain and clarify the intent of a standard and are not intended to constitute an alteration to the original standard or to supply consulting information. Permission is hereby granted to download and print one copy o

3、f this document. Individuals seeking permission to reproduce and/or distribute this document in its entirety or portions of this document must contact the IEEE Standards Department for the appropriate license. Use of the information contained in this document is at your own risk. IEEE Standards Depa

4、rtment Copyrights and Permissions 445 Hoes Lane, P. O. Box 1331 Piscataway, New Jersey 08855-1331, USA July 2010 Interpretation Number 1: Topic: Rated Interrupting Time Interpretation Request #1 Question: What is the applicability of interrupting times determined by 50 Hz testing to applications of

5、the high voltage circuit breaker when applied at 60Hz? Are the interrupting times obtained at 50 Hz converted to a 60 Hz basis or added to the contact parting time raw? Discussion: 1. IEEE Std. C37.04-1999, 5.6 defines the rated interrupting time of a circuit breaker as the maximum permissible inter

6、val between the energizing of the trip circuit at rated control voltage and rated operating pressure for mechanical operation, and the interruption of the current in the main circuit in all poles. In discussing numerical values of interrupting time, IEEE Std C37.04-1999 uses cycles as the unit of me

7、asure and clarifies that cycles are based on corresponding rated power frequency. 2. IEEE /ANSI Std. C37.06-2000, Table 1 provides for the preferred ratings of indoor circuit breakers including the rated interrupting time which is given in milliseconds Page 1 of 3IEEE Std C37.04-1999, C37.06-2000, C

8、37.09-19997/2/2010mhtml:file:/A:AcquisitionIEEE Errata, IEEE Intp & NESC Intp07022010C37.04_INT-1.3. IEEE Std. C37.09-1999, 4.8.1.2 states: “If a circuit breaker contains interrupters that are not affected significantly by the di/dt, then tests performed at 50 Hz can be used to demonstrate the perfo

9、rmance at 60 Hz and vice versa.” For the purposes of this inquiry, let us assume that the interrupters under test fit this criterion. 4. IEEE Std. C37.09-1999, 4.8.1.4 requires that in order to demonstrate the breaker is capable of meeting the requirements for the rated interrupting time, it must be

10、 shown that is can interrupt with the current zeros occurring in such relation to contact parting as to yield the longest arcing time. Further paragraphs define and discuss the arcing time in units of milliseconds. Proposed Solution: High voltage circuit breakers which are tested at 50 Hz and subseq

11、uently applied at 60 Hz, or vice versa, may have their rated interrupting time defined by the sum of the contact parting time (at rated control voltage) and the maximum arcing time as determined during the design testing under IEEE Std C37.09-1999 converted to the appropriate frequency base. For exa

12、mple, for a circuit breaker with a 30 msec contact parting time which was tested at 50 Hz and determined to have a maximum arcing time of 22 msec. the following would be considered valid: If the above conversion is considered technically valid, then the breaker cited could be rated as a 50 msec (3 c

13、ycle) breaker. If not accepted, then the next preferred value for rated interrupting time would be 83 msec (5 cycles). Interpretation Response #1 IEEE Std C37.09-1999 is unclear on the issue of di/dt with the word “significant.“ No distinction can be made between alternative implementations based on

14、 this. There can be arguments made for both using one test to cover both frequencies as well as performing tests at both frequencies. IEEE Std C37.09-1999, 4.8.1.2.contains wording that will allow for one test to cover both 50 and 60Hz, but does not give clear, defined parameters for determining whe

15、n such testing applies. This situation is being referred to the sponsor for possible action at the next revision. Back to Available IEEE Standards Interpretations OnlinePage 2 of 3IEEE Std C37.04-1999, C37.06-2000, C37.09-19997/2/2010mhtml:file:/A:AcquisitionIEEE Errata, IEEE Intp & NESC Intp07022010C37.04_INT-1. Copyright IEEE-SA Contact IEEE-SA For questions or comments, please contact the IEEE-SA Webmaster. Page 3 of 3IEEE Std C37.04-1999, C37.06-2000, C37.09-19997/2/2010mhtml:file:/A:AcquisitionIEEE Errata, IEEE Intp & NESC Intp07022010C37.04_INT-1.

展开阅读全文
相关资源
  • IEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdfIEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdf
  • IEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdfIEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdf
  • IEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdfIEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdf
  • IEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdfIEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdf
  • IEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdfIEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdf
  • IEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdfIEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdf
  • IEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdfIEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdf
  • IEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdfIEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdf
  • IEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdfIEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdf
  • IEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdfIEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdf