IEEE C62 92 1 ERTA-2017 en Errata to Guide for the Application of Neutral Grounding in Electrical Utility Systems-Part I Introduction.pdf

上传人:rimleave225 文档编号:1249273 上传时间:2019-09-02 格式:PDF 页数:4 大小:432.38KB
下载 相关 举报
IEEE C62 92 1 ERTA-2017 en Errata to Guide for the Application of Neutral Grounding in Electrical Utility Systems-Part I Introduction.pdf_第1页
第1页 / 共4页
IEEE C62 92 1 ERTA-2017 en Errata to Guide for the Application of Neutral Grounding in Electrical Utility Systems-Part I Introduction.pdf_第2页
第2页 / 共4页
IEEE C62 92 1 ERTA-2017 en Errata to Guide for the Application of Neutral Grounding in Electrical Utility Systems-Part I Introduction.pdf_第3页
第3页 / 共4页
IEEE C62 92 1 ERTA-2017 en Errata to Guide for the Application of Neutral Grounding in Electrical Utility Systems-Part I Introduction.pdf_第4页
第4页 / 共4页
亲,该文档总共4页,全部预览完了,如果喜欢就下载吧!
资源描述

1、30 November 2017 Product STD22421E IEEE Std C62.92.1 -2016 (Revision of IEEE Std C62.92.1-2000) Errata to IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems Part I: Introduction Sponsor Surge Protective Devices Committee of the IEEE Power and Energy Society Correction

2、Sheet Issued 30 November 2017 Copyright 2017 by The Institute of Electrical and Electronics Engineers. Inc. All rights reserved. Published 2017 Printed in the United States of America. This correction sheet may be freely reproduced and distributed in order to maintain the utility and currency of the

3、 underlying Standard. This correction sheet may not be sold, licensed or otherwise distributed for any commercial purposes whatsoever. The content of this correction sheet may not be modified. 30 November 2017 Product STD22421E Page 11, change the definition of coefficient of grounding (COG) to read

4、 as follows: coefficient of grounding (COG): The ratio, ELG/ELL (expressed as a percentage), of the highest root-mean-square (rms) line-to-ground power-frequency voltage ELG on a sound phase, at a selected location, during a fault to ground affecting one or more phases to the line-to-line power-freq

5、uency voltage ELL that would be obtained at the selected location with the fault removed. Page 13, change the Notes below Figure 1 to read as follows: NOTE 1 Va , Vb , and Vc are the respective source voltages (line-to-neutral). NOTE 2 RS and XS are the equivalent source resistance and reactance, pe

6、r phase. NOTE 3 Rn and Xn are the neutral resistance and reactance of the system as seen at the source. NOTE 4 Cg is the total system capacitance to ground and is obtained by connecting all three phases together and measuring the capacitance with the neutral grounding branch open-circuited. NOTE 5 C

7、g /3 is the grounded-wye partial, or zero-sequence, capacitance of the system. NOTE 6 CS is the ungrounded wye equivalent of the interphase partial capacitances of the system, obtained by subtracting the zero-sequence capacitance Cg/3 from the positive sequence capacitance C1. NOTE 7 f is frequency

8、in hertz. NOTE 8 The switch S, simulates a single-line-to-ground fault on a-phase. NOTE 9 Vf is the prefault line-to-ground voltage at the fault, the energization voltage. Page 15, the first paragraph under subclause 6.2 should read as follows: Various classes of grounding are available to the syste

9、m designer, each having a unique set of attributes. The response characteristics of the various classes of grounding may be defined or classified in terms of the ratios of symmetrical component parameters, such as the positive-sequence reactance X1, the negative-sequence reactance X2, the zero-seque

10、nce reactance X0, the positive-sequence resistance R1, the negative-sequence resistance R2, and the zero-sequence resistance R0 (see Clarke B6, Wagner and Evans B22, and Willheim and Waters B23). Page 16, change the Notes below Figure 2 to read as follows: NOTE 1 Vf is the Thevenin circuit pre-fault

11、 voltage. NOTE 2 Va is the line-to-neutral source voltage of Figure 1. NOTE 3 3I0 is the fault line current through closed switch S of Figure 1. NOTE 4 The equivalence sign () indicates the result when capacitance is negligible. NOTE 5 The remaining variables are defined in the notes following Figur

12、e 1. Page 16, subclause 6.3 should read as follows: The term coefficient of grounding (COG) is used in system grounding practice. COG is defined as / 100%,LG LLEE where LGE is the highest root-mean-square (rms), line-to-ground power-frequency voltage on a sound phase, at a selected location, during

13、a line-to-ground fault affecting one or more phases. LLE is the line-to-line power-frequency voltage that would be obtained, at the selected location, with the fault removed. The COG for three-phase systems is calculated from the phase-sequence impedance components, as viewed from the fault location

14、. The COG is useful in the selection of a surge arrester rating for a selected location (see IEEE Std 32-1972 B11, IEEE Std C62.2-1987 B13, IEEE Std C62.22-2009 B15, and IEEE Tutorial Course B17). 30 November 2017 Product STD22421E Pages 16 and 17, subclause 6.4 should read as follows: The term grou

15、nd-fault factor (GFF) is, to a limited extent, now used instead of COG. At a selected location on a three-phase system, and for a given system configuration, the GFF is the ratio of the highest rms line-to-ground power-frequency voltage (as measured phase-to-ground) on a sound phase during a fault t

16、o ground (affecting one or more phases at any point) to the rms power-frequency voltage (as measured phase-to-ground) that would be obtained at the selected location with the fault removed (see IEEE Std C62.82.1-2010 B16). Thus, the GFF is related to the COG by 3 , as shown in Equation (1) below: 3

17、100COGGFF (1) where GF is the ground-fault factor COG is the coefficient of grounding expressed as a percentage Page 23, Replace Figure A.1 with the following figure: Page 24, the text between equation (A.9) and equation (A.10) should read as follows: Where COGa, COGb, and COGc are the coefficients

18、of grounding for each respective phase. Z1, Z2, and Z0 are the positive, negative, and zero sequence impedances, respectively, () RF is the fault resistance, () a and a2 are phasor operators 2330 . 5 j 1 1 2 0 ; 0 . 5 j 1 2 4 022aa 30 November 2017 Product STD22421E In order to eliminate one parameter, it is convenient to divide each impedance by X1. Defining the ratios R1= R1/X1; R0=R0/X1, X0=X0/X1, RF=RF/X1 Page 33, equation (B.1) should read as follows: 100.0 592 0.1 736 l og /km60 60 eg DffZj h (B.1)

展开阅读全文
相关资源
  • IEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdfIEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdf
  • IEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdfIEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdf
  • IEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdfIEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdf
  • IEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdfIEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdf
  • IEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdfIEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdf
  • IEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdfIEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdf
  • IEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdfIEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdf
  • IEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdfIEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdf
  • IEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdfIEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdf
  • IEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdfIEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > IEC

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1