1、 1 Copyright 2014 IEEE. All rights reserved. Interpretation Section 23. Clearances Rule 232.A. Table 1 Vertical clearance of wires above ground or rails Basic clearances Minimum vertical clearance of wires above ground or rails (1961, 6th Edition; Volume 12, NESC Archives, pages 56-57) (9 December 2

2、014) IR577 Question: Does the language in the middle column of Table 232-1, entitled “Open supply line wires, arc wires and service drops” apply to all service drops or only open-wire drops? The language of the middle column is unclear regarding the clearances required by this Table. Specifically, c

3、larification of the minimum required clearance for a 120 V to ground triplex service drop (now known as a 230C3 cable) is requested, at point of attachment to the structure, above pedestrian-only areas. This becomes an issue when attempting to apply grandfathered status to the terms of the 1961 Edit

4、ion, to the service height clearance to an older home. The lack of clarity arises when trying to apply the footnotes for the clearances indicated for “Spaces or ways accessible to pedestrians only” One interpretation could be that the (middle column) language applies to all service drops and that, c

5、onsequently, Footnote 8(2) gives the flexibility to reduce that clearance to 8 ft, under certain conditions. Another interpretation is that the minimum clearance required by Table 232-1 is 10 ft, for what is now known as a 230C3 cable; that footnote 8(2) would apply only to open-wire services and th

6、en only when the form of the building will not permit 10 ft clearance. The second interpretation would also seem to indicate that, for the 230C3 cable described, the only avenue for reduction in the 15 ft clearance (stated in the Table) lies in application of footnote 7(4). 2 Copyright 2014 IEEE. Al

7、l rights reserved. Discussion: The language in this Table was changed significantly in this Edition, as was the language of Rule 230.C., describing “Supply Cables.” The verbatim inclusion of Rule 230.C. into the first column of Table 232-1, as well as into footnote 7(4), appears to be intentional an

8、d a clear indication that the committee recognized the differences between open-wire facilities and those described in Rule 230.C., and wanted to draw clear distinctions between the two types. Interpretation This Interpretation is limited to NESC 1961 Edition clearance requirements for service drops

9、 over spaces or ways accessible to pedestrians only, as detailed in Rule 232.A., Table 1. In answer to the question presented, the middle column of Table 1, “Open supply line wires, arc wires and service drops,” applies to open-wire service drops only; it does not apply to triplex service drops. Con

10、sequently, footnote 7 applies to triplex service drops and footnote 8 applies to open-wire service drops. In the heading of the Table 1 middle column, “Open” applies to all of the three designated types of conductors: supply line wires, arc wires and service drops. A semicolon would have been used a

11、fter “arc wires” if the middle column was intended to apply to all service drops. Rather, triplex service drops are covered in the first column under “insulated conductors supported on and cabled together with an effectively grounded messenger.” See also NESC IR 577a. _ National Electrical Safety Code and NESC are both registered trademarks and service marks of the Institute of Electrical and Electronics Engineers, Inc. The NESC is available from the Institute of Electrical and Electronics Engineers, Inc., 445 Hoes Lane, Piscataway, NJ 08854, USA (http:/standards.ieee.org/)

展开阅读全文
相关资源
  • IEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdfIEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdf
  • IEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdfIEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdf
  • IEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdfIEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdf
  • IEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdfIEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdf
  • IEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdfIEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdf
  • IEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdfIEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdf
  • IEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdfIEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdf
  • IEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdfIEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdf
  • IEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdfIEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdf
  • IEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdfIEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > IEC

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1