1、 1 Copyright 2014 IEEE. All rights reserved. Interpretation Section 23. Clearances Rule 232.A. Table 1 Vertical clearance of wires above ground or rails Basic clearances Minimum vertical clearance of wires above ground or rails (1961, 6th Edition; Volume 12, NESC Archives, pages 56-57) (9 December 2

2、014) IR577a Question: What is the appropriate column in Table 1 contained within Rule 232.A. Basic Clearances to evaluate a service drop for minimum clearance? NOTE Perspective 1 the ”open” is implicit to service drops and they would fall into column 1 and 2, while perspective 2 is the use of column

3、 2. 2 Copyright 2014 IEEE. All rights reserved. The issue arises when attempting to evaluate service drop clearances for an insulated 120 V to ground service drop at the point of attachment to the building that are above spaces or ways accessible to pedestrians only to the terms of the 1961 Edition.

4、 One opinion is that in the text of the heading, “Open supply line wires, arc wires and service drops,” the “open” carries through the entire heading “Open supply line wires,” “Open arc wires” and “Open service drops.” This would indicate that only open wire service drops fall within column 2, and t

5、hat the applicable footnotes would be footnote 14 and footnote 8. In this first opinion, an insulated service drop would fall into column 1 under “insulated conductors supported on and cabled together with an effectively 3 Copyright 2014 IEEE. All rights reserved. grounded messenger,” and the applic

6、able footnote would be footnote 7. This opinion allows for a 120 V to ground service drop at the point of attachment to the building that was constructed with open wire under certain conditions to have a minimum 8 clearance, and for an insulated service drop under certain conditions to have a minimu

7、m clearance of 10 ft. A second opinion is that column 2, “Open supply line wires, arc wires and service drops” applies to all service drops as defined. This opinion allows for a 120 V to ground service drop at the point of attachment to the building under certain conditions to have a minimum 8 ft cl

8、earance. A complicating factor to applying either opinion to evaluating a service drop as the point of attachment is defined as customer equipment and subject to the National Electric Code, while the service drop is utility equipment and subject to the National Electric Safety Code. If the use of “o

9、pen” is implicit in establishing clearances for insulated 120 V to ground service drops, it is unclear how the transition between utility clearance requirements and customer attachment height requirements can be accommodated. Discussion: Additional Definitions and Rules 63. Service means the conduct

10、ors and equipment for delivering electric energy from the secondary distribution or street main, or other distribution feeder, or from the transformer, to the wiring system of the premises served. For overhead circuits, it includes the conductors from the last line pole to the service switch or fuse

11、. The portion of the overhead service between the pole and building is designated as “service drop.” 230. C Supply Cables As far as clearances are concerned, supply cable having effectively grounded continuous metal sheath, or insulated conductors supported on and cabled together with an effectively

12、 grounded messenger, of all voltages, are classified the same as guys and messenger. The definition contained within 63. Service would indicate that open wire or insulated service between the pole and building is defined as the service drop and should be evaluated under the middle column which conta

13、ins “service drop” This definition is also consistent with 1940 National Electric Code, and the application of footnote 8 (2) is consistent with the 1940 National Electric Code Section 2325. Point of Attachment to Building. 4 Copyright 2014 IEEE. All rights reserved. Rule 230.C would indicate that t

14、he first column would apply to a service or parallel aerial cable commonly referred to as “parlay” for structure to structure (pole to pole) vertical clearances. The rule references guys which run either pole to pole or to the ground which would be an anchor guy. The 1961 NESC Edition is being appli

15、ed to service drop installations that were constructed pre-1961 to determine grandfathering status. If opinion 1 is accurate and an insulated service drop has a greater minimum clearance than an open wire service drop, would it be acceptable for the customer to seek relief from the expense under Rul

16、e 201A similar to interpretation request 195 dated June 24, 1977, since the greater clearance for an insulated service drop versus on open wire service drop is not securing any additional protection? Further, if opinion 1 is correct, how does that comport with the allowance for communication equipme

17、nt less than 160 V to ground having a different and more lenient clearance requirement than the insulated 120 V to ground service drop? Interpretation This Interpretation is limited to NESC 1961 Edition clearance requirements for service drops over spaces or ways accessible to pedestrians only, as d

18、etailed in Rule 232.A., Table 1. Two statements in the first opinion are correct: 1) The word “open” carries through the entire heading of the second column, and 2) An insulated service drop falls in the first column. Note that this statement is based on the description of an insulated service drop

19、as: “insulated conductors supported on and cabled together with an effectively grounded messenger.” Such cables are commonly referred to as “triplex” cables (120/240 single-phase for this interpretation) and classified as 230C3 cables in later NESC editions. Therefore, footnote 7 applies to triplex

20、service drops and footnote 8 applies to open-wire service drops. In the heading of the Table 1 middle column (second column), “Open” applies to all of the three designated types of conductors: supply line wires, arc wires and service drops. A semicolon would have been used after “arc wires” if the m

21、iddle column was intended to apply to all service drops. Rather, triplex service drops are covered in the first column under “insulated conductors supported on and cabled together with an effectively grounded messenger.” The following two comments also apply to this Interpretation Request: 5 Copyrig

22、ht 2014 IEEE. All rights reserved. 1) Open wire services can be either bare or covered with an insulating material. If cabled to a messenger as described above (triplex cable), the service is not “open wire.” 2) Regarding the question about seeking relief, the NESC does not preclude an appeal to the

23、 commission under the provisions of Rule 201.A. (NESC 1961 Edition). See also NESC IR 577. _ National Electrical Safety Code and NESC are both registered trademarks and service marks of the Institute of Electrical and Electronics Engineers, Inc. The NESC is available from the Institute of Electrical and Electronics Engineers, Inc., 445 Hoes Lane, Piscataway, NJ 08854, USA (http:/standards.ieee.org/)

展开阅读全文
相关资源
  • IEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdfIEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdf
  • IEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdfIEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdf
  • IEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdfIEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdf
  • IEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdfIEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdf
  • IEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdfIEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdf
  • IEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdfIEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdf
  • IEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdfIEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdf
  • IEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdfIEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdf
  • IEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdfIEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdf
  • IEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdfIEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > IEC

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1