1、 1 Copyright 2017 IEEE. All rights reserved. Interpretation Section 12. Installation and maintenance of equipment Rule 124 Guarding live parts (2017 Edition, page 48) (4 May 2017) IR582 Question: Rule 124 covers the guarding of live parts in substations. For the purposes of guarding, do cable termin

2、ations fall under parts of indeterminate potential (Rule 124A3) or insulating covering on conductors (Rule 124C6)? Discussion: The substations for our company utilize cable systems operating at 4160 V and 6900 V (phase to phase). The cables are multi-conductor, shielded, type MC and connect to the o

3、verhead bus via riser structures where the cables have cable termination kits (as per IEEE Std 48). Guarding for the live parts (the compression lugs) are governed by Rule 124A1 and are typically achieved using the clearances from Table 124-1. The insulated, shielded parts of the cable are guarded b

4、y insulation per Rule 124C6. The cable termination provides insulation from the conductor and the exposed live part (the lug) of the cable at the top of the termination and covers the grounded, shield wire that comes out of the bottom of the termination. The top of the termination is at line potenti

5、al, and the bottom of the termination is at ground potential, therefore the termination itself may be considered a part at indeterminate potential (Rule 124A3). However, the termination is also a non-shielded insulation covering the live parts of the cable, which for the 4160 V system would appear t

6、o meet the requirements of Rule 124C6a (less than 2500 V to ground). The 6900 V system exceeds the 2500 V to ground requirement of Rule 124C6a, as the termination itself is non-shielded. The exception for Rule 124C6a does reference Article 310.6 of the National Electrical Code (NEC) (NFPA 70) for us

7、e of non-shielded insulated conductors for use up to 8000 V (phase to phase). However, neither Article 310.6 nor the 8000 V exception are in the latest version of the 2017 Edition of the NEC. The 2002 Edition of the NEC was the last version to have the 8000 V exception. In the 2005 Edition, the exce

8、ption was changed to 2400 V; this change effectively required all 4160 V cable systems to use shielded conductors. Both the exception for NESC Rule 124C6a and the exception for NEC Article 310.6 required the non-shielded insulated conductors to be listed by a qualified testing laboratory. Following

9、the change in the 2005 Edition of the NEC from 8000 V to 2400 V maximum, UL 1072 (Standard for Medium-Voltage Power Cables) was consequently revised to require shielded conductors above 2400 V. 2 Copyright 2017 IEEE. All rights reserved. In the 2011 Edition, Article 310.6 was removed and the content

10、 inserted into Article 310.10(E). From 2011 to the current 2017 Edition, Article 310.10(E) does allow the use of non-shielded, type MC cables up to 5000 V “in industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation,” b

11、ut otherwise limits non-shielded conductors to 2400 V maximum. It is unclear if the intent of Rule 124C6a is to allow non-shielded, insulated conductors from 2400 V to 8000 V when the NESC requirement to meet the NEC Article is no longer applicable and the cable can no longer be listed to UL 1072. I

12、f the exception to the NESC Rule 124C6a is then effectively limited (by reference to the NEC) to 2400 V (phase to phase), it may be interpreted to conflict with the Rule 124C6a allowance of non-shielded insulation up to 2500 V to ground. Interpretation The answer to the question is the cable termina

13、tion, as described, is of indeterminate voltage. Rule 124A provides the information to determine when guarding of live parts is required. As stated in the request, the top of the termination is at line potential and the bottom of the termination is at ground potential. Therefore, the cable terminati

14、on consists of sections of indeterminate voltages. If the cable termination does not have the required clearances for those voltages, then guarding is required. The Code does not specify the point on a cable termination at which various levels of voltage potential may be present; that depends on the

15、 gradient characteristics of the cable termination used. Rule 124C6 provides information on a type of guard that can be used when guarding is required by Rule 124A. The requestor of this interpretation specifically referred to the Exception for this rule. This Exception is based on the type of condu

16、ctor, and the Exception will not apply because the conductor is shielded. Thanks to the requestor for pointing out the reference to the NEC Article 310.6. This information will be provided to Subcommittee 3. _ National Electrical Code, NEC, and NFPA 70 are registered trademarks in the U.S. Patent & Trademark Office, owned by the National Fire Protection Association.

展开阅读全文
相关资源
  • IEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdfIEC TS 62492-1-2008 Industrial process control devices - Radiation thermometers - Part 1 Technical data for radiation thermometers《工业过程控制装置 辐射温度计 第1部分 辐射温度计的技术数.pdf
  • IEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdfIEC TR2 61464-1998 Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the mai.pdf
  • IEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdfIEC TR 61241-2-2-1993 Electrical apparatus for use in the presence of combustible dust part 2 test methods section 2 method for determining the electrical resis.pdf
  • IEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdfIEC TR 60972-1989 Classification and interpretation of new lighting products《新型照明产品的分类和说明》.pdf
  • IEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdfIEC TR 60943 Edition 21-2009 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals《特殊终端中电气设备部件用关于允许.pdf
  • IEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdfIEC TR 60943 AMD 1-2008 Guidance concerning the permissible temperature rise for parts of electrical equipment in particular for terminals Amendment 1《电气设备部件(特别.pdf
  • IEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdfIEC TR 60919-2-2008 Performance of high-voltage direct current (HVDC) systems with line-communicated converters - Part 2 Faults and switching《带线性通信转换器的高压直流(HVDC.pdf
  • IEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdfIEC TR 60870-6-505 Edition 11-2006 Telecontrol equipment and systems - Part.6-505 Telecontrol protocols compatible with ISO standards and ITU-T recommendations .pdf
  • IEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdfIEC TR 60344 CORR1-2012 Calculation of d c resistance of plain and coated copper conductors of low-frequency cables and wires - Application guide Corrigendum 1《.pdf
  • IEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdfIEC 62560 CORR1-2012 Self-ballasted LED-lamps for general lighting services by voltage 50 V - Safety specifications Corrigendum 1《普通照明用50 V以上自镇流LED灯 安全要求 勘误表1》.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > IEC

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1