ISO TS 11602-2-2010 Fire protection - Portable and wheeled fire extinguishers - Part 2 Inspection and maintenance《消防 手提灭火器与轮式灭火器 第2部分 检查与保养》.pdf

上传人:孙刚 文档编号:1257964 上传时间:2019-09-02 格式:PDF 页数:26 大小:255.50KB
下载 相关 举报
ISO TS 11602-2-2010 Fire protection - Portable and wheeled fire extinguishers - Part 2 Inspection and maintenance《消防 手提灭火器与轮式灭火器 第2部分 检查与保养》.pdf_第1页
第1页 / 共26页
ISO TS 11602-2-2010 Fire protection - Portable and wheeled fire extinguishers - Part 2 Inspection and maintenance《消防 手提灭火器与轮式灭火器 第2部分 检查与保养》.pdf_第2页
第2页 / 共26页
ISO TS 11602-2-2010 Fire protection - Portable and wheeled fire extinguishers - Part 2 Inspection and maintenance《消防 手提灭火器与轮式灭火器 第2部分 检查与保养》.pdf_第3页
第3页 / 共26页
ISO TS 11602-2-2010 Fire protection - Portable and wheeled fire extinguishers - Part 2 Inspection and maintenance《消防 手提灭火器与轮式灭火器 第2部分 检查与保养》.pdf_第4页
第4页 / 共26页
ISO TS 11602-2-2010 Fire protection - Portable and wheeled fire extinguishers - Part 2 Inspection and maintenance《消防 手提灭火器与轮式灭火器 第2部分 检查与保养》.pdf_第5页
第5页 / 共26页
点击查看更多>>
资源描述

1、 Reference number ISO/TS 11602-2:2010(E) ISO 2010TECHNICAL SPECIFICATION ISO/TS 11602-2 First edition 2010-08-15 Fire protection Portable and wheeled fire extinguishers Part 2: Inspection and maintenance Protection contre lincendie Extincteurs portatifs et extincteurs sur roues Partie 2: Contrle et

2、maintenance ISO/TS 11602-2:2010(E) PDF disclaimer This PDF file may contain embedded typefaces. In accordance with Adobes licensing policy, this file may be printed or viewed but shall not be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the

3、editing. In downloading this file, parties accept therein the responsibility of not infringing Adobes licensing policy. The ISO Central Secretariat accepts no liability in this area. Adobe is a trademark of Adobe Systems Incorporated. Details of the software products used to create this PDF file can

4、 be found in the General Info relative to the file; the PDF-creation parameters were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In the unlikely event that a problem relating to it is found, please inform the Central Secretariat

5、 at the address given below. COPYRIGHT PROTECTED DOCUMENT ISO 2010 All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing fro

6、m either ISO at the address below or ISOs member body in the country of the requester. ISO copyright office Case postale 56 CH-1211 Geneva 20 Tel. + 41 22 749 01 11 Fax + 41 22 749 09 47 E-mail copyrightiso.org Web www.iso.org Published in Switzerland ii ISO 2010 All rights reservedISO/TS 11602-2:20

7、10(E) ISO 2010 All rights reserved iiiContents Page Foreword iv Introduction.v 1 Scope1 2 Normative references1 3 Terms and definitions .1 4 Inspection, maintenance and recharging .4 5 Hydrostatic proof-pressure tests.10 Annex A (normative) Competent persons12 Annex B (normative) Proof-pressure test

8、ing.13 Annex C (normative) Obsolete extinguishers17 Annex D (informative) Hazard types .18 Bibliography19 ISO/TS 11602-2:2010(E) iv ISO 2010 All rights reservedForeword ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies (ISO member bodies)

9、. The work of preparing International Standards is normally carried out through ISO technical committees. Each member body interested in a subject for which a technical committee has been established has the right to be represented on that committee. International organizations, governmental and non

10、-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization. International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part

11、 2. The main task of technical committees is to prepare International Standards. Draft International Standards adopted by the technical committees are circulated to the member bodies for voting. Publication as an International Standard requires approval by at least 75 % of the member bodies casting

12、a vote. In other circumstances, particularly when there is an urgent market requirement for such documents, a technical committee may decide to publish other types of document: an ISO Publicly Available Specification (ISO/PAS) represents an agreement between technical experts in an ISO working group

13、 and is accepted for publication if it is approved by more than 50 % of the members of the parent committee casting a vote; an ISO Technical Specification (ISO/TS) represents an agreement between the members of a technical committee and is accepted for publication if it is approved by 2/3 of the mem

14、bers of the committee casting a vote. An ISO/PAS or ISO/TS is reviewed after three years in order to decide whether it will be confirmed for a further three years, revised to become an International Standard, or withdrawn. If the ISO/PAS or ISO/TS is confirmed, it is reviewed again after a further t

15、hree years, at which time it must either be transformed into an International Standard or be withdrawn. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. ISO shall not be held responsible for identifying any or all such patent right

16、s. ISO/TS 11602-2 was prepared by Technical Committee ISO/TC 21, Equipment for fire protection and fire fighting, Subcommittee SC 2, Manually transportable fire extinguishers. This first edition of ISO/TS 11602-2 cancels and replaces ISO 11602-2:2000, of which it constitutes a technical revision. IS

17、O 11602 consists of the following parts, under the general title Fire protection Portable and wheeled fire extinguishers: Part 1: Selection and installation Technical Specification Part 2: Inspection and maintenance Technical Specification ISO/TS 11602-2:2010(E) ISO 2010 All rights reserved vIntrodu

18、ction This part of ISO 11602 presents a limited number of provisions for the inspection and maintenance of portable and wheeled fire extinguishers, in the knowledge that different countries have particular environments and climates which can affect the size, shape and occupancy of buildings. A count

19、rys specific building configurations can affect the inspection and maintenance of fire extinguishers; therefore, this part of ISO 11602 could be reinforced in respect of fire-extinguishing performance characteristics in the presentation of a general-purpose standard. It is proposed that further inve

20、stigation be undertaken in light of the above for the purposes of a future revision of this part of ISO 11602. TECHNICAL SPECIFICATION ISO/TS 11602-2:2010(E) ISO 2010 All rights reserved 1Fire protection Portable and wheeled fire extinguishers Part 2: Inspection and maintenance 1 Scope This part of

21、ISO 11602 gives requirements for the selection and installation of portable and wheeled fire extinguishers. It is intended as a companion to ISO/TS 11602-1. Fire extinguishers are a first line of defence against fires of limited size. They are needed even if the property is equipped with automatic s

22、prinklers, standpipe and hose, or other fixed protection equipment. This part of ISO 11602 is not applicable to permanently installed systems for fire extinguishment, even though portions of such systems may be portable (such as hose and nozzles attached to a fixed supply of extinguishing media). Ex

23、tinguishers for use on board aircraft, watercraft and vehicles are outside the scope of ISO 11602. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the lates

24、t edition of the referenced document (including any amendments) applies. ISO 5923, Fire protection Fire extinguishing media Carbon dioxide ISO 7201-1, Fire protection Fire extinguishing media Halogenated hydrocarbons Part 1: Specifications for halon 1211 and halon 1301 ISO 7201-2, Fire extinguishing

25、 media Halogenated hydrocarbons Part 2: Code of practice for safe handling and transfer procedures of halon 1211 and halon 1301 ISO 8421-1, Fire protection Vocabulary Part 1: General terms and phenomena of fire 3 Terms and definitions For the purposes of this document, the terms and definitions give

26、n in ISO 8421-1 and the following apply. 3.1 clean agent electrically non-conductive gaseous or vaporizing fire extinguishant that does not leave a residue upon vaporization ISO 7165:2009, 3.5 ISO/TS 11602-2:2010(E) 2 ISO 2010 All rights reserved3.2 closed recovery system system that provides for th

27、e transfer of media between extinguishers, supply containers, and recharge and recovery containers so that the escape of media to the atmosphere is minimized 3.3 competent person person with the necessary training and experience and with access to the requisite tools, equipment, parts and informatio

28、n (including the manufacturers service manual) to be capable of carrying out the inspection, maintenance and recharging procedures of this part of ISO 11602 3.4 film-forming foam extinguishing media comprising the aqueous film-forming foam (AFFF) and film-forming fluoroprotein (FFFP) foam types, and

29、 including grades suitable for polar solvents (water-soluble flammable liquids) and those not suitable for polar solvents 3.5 fire extinguisher extinguisher appliance containing an extinguishing medium which can be discharged and directed onto a fire by the action of internal pressure NOTE 1 See ISO

30、 7165. NOTE 2 The internal pressure may be provided by a stored pressure (pressurization of the extinguishing medium container at the time of charging), or a gas cartridge (pressurization at the time of use through the release of gas from a separate cylinder into the medium container). NOTE 3 Adapte

31、d from ISO 7165:2009, definition 3.11. 3.6 high-pressure cylinder cylinder having a service pressure higher than 2,5 MPa at 20 C 3.7 inspection brief examination to ensure that an extinguisher is available and will operate NOTE This is intended to give reasonable assurance that the extinguisher is f

32、ully charged and operable. This is done by seeing that it is in its designated place, that it has not been actuated or tampered with, and that there is no obvious damage or condition to prevent its operation. 3.8 low-pressure cylinder cylinder having a service pressure of 2,5 MPa or lower at 20 C 3.

33、9 maintenance thorough examination of the extinguisher NOTE This is intended to give maximum assurance that an extinguisher will operate effectively and safely. It includes a thorough examination and any necessary repair or replacement. It will normally reveal if hydrostatic testing is required. ISO

34、/TS 11602-2:2010(E) ISO 2010 All rights reserved 33.10 non-rechargeable extinguisher non-refillable extinguisher fire extinguisher that is not capable of (or intended for) undergoing complete maintenance or hydrostatic testing, nor of being restored to its full operating capability by means of the s

35、tandard practices used by fire equipment service companies 3.11 portable fire extinguisher fire extinguisher that is designed to be carried and operated by hand and that in working order has a mass of not more than 20 kg NOTE Subject to local acceptance, extinguishers having a total mass of 25 kg wh

36、en fully charged are permitted. ISO 7165:2009, 3.15 3.12 rating comparative number associated with the classification assigned to an extinguisher and indicative of its capability in the extinguishment of a standard fire 3.13 rechargeable extinguisher refillable extinguisher fire extinguisher that is

37、 capable of undergoing complete maintenance, including internal inspection of the pressure vessel, replacement of all substandard parts and seals, and hydrostatic testing, and of being recharged with media and propellant and restored to its full operating capability by means of the standard practice

38、s used by fire equipment service companies NOTE Rechargeable/refillable extinguishers are marked “Recharge Immediately After Any Use” or with a similar equivalent marking. 3.14 recharging replacement of the extinguishing medium NOTE This also includes the propellant for certain types of extinguisher

39、s. 3.15 self-expelling-medium extinguisher extinguisher in which the medium has sufficient vapour pressure at normal operating temperatures to expel itself 3.16 service servicing process that includes maintenance, recharging or hydrostatic testing, or more than one of these 3.17 service pressure nor

40、mal operating pressure at 20 C, as indicated on the pressure gauge or indicator and nameplate of a stored pressure extinguisher, or the pressure developed in a cartridge-operated extinguisher upon release of the gas from the cartridge into the medium container at a temperature of 20 C 3.18 test pres

41、sure pressure at which the extinguisher or its components were tested at the time of manufacture NOTE The pressure at which the shell was tested is shown on the nameplate or the extinguisher body. ISO/TS 11602-2:2010(E) 4 ISO 2010 All rights reserved3.19 water-type extinguisher fire extinguisher whi

42、ch contains a water-based medium, such as water, aqueous film-forming foam (AFFF) or film-forming fluoroprotein (FFFP) foam and/or antifreeze 3.20 wet chemical extinguisher fire extinguisher which contains aqueous solutions of potassium acetate, potassium carbonate, potassium citrate, or combination

43、s of these materials 3.21 wheeled extinguisher fan appliance on wheels having a total mass of more than 20 kg but not greater than 450 kg, which is designed to be transported to the fire and operated by one person NOTE See ISO 11601. 4 Inspection, maintenance and recharging 4.1 General 4.1.1 The own

44、er or designated agent or occupant of a property in which extinguishers are located shall be responsible for inspection, maintenance and recharging. 4.1.2 The procedure for inspection and maintenance of extinguishers varies considerably. Minimal knowledge is necessary to perform a monthly inspection

45、 procedure as outlined in 4.2. Only competent persons shall service extinguishers, as outlined in 4.3 and 4.4. See Annex A. 4.1.3 Maintenance and recharging shall be performed in accordance with the appropriate manual(s), using the proper types of tools, recharge materials, lubricants, and the manuf

46、acturers recommended and identified replacement parts. 4.1.4 Extinguishers out of service for maintenance or recharge shall be replaced at once by spare extinguishers of the same type and at least equal classification and rating. 4.2 Inspection 4.2.1 Extinguishers shall be checked when initially pla

47、ced in service and thereafter should be checked at approximately 30-day intervals. Extinguishers shall be checked at more frequent intervals when circumstances require. 4.2.2 Periodic checks shall be made to ensure that a) the extinguisher is located in the designated place, b) the extinguisher is u

48、nobstructed and visible, with its operating instructions facing outwards, c) operating instructions are legible, d) seals and tamper indicators are not broken or missing, e) the extinguisher is full (by weighing or lifting), f) the extinguisher is not obviously damaged, corroded or leaking and does

49、not have a clogged nozzle, and g) where provided, the pressure gauge reading or indicator is in the operable range or position. ISO/TS 11602-2:2010(E) ISO 2010 All rights reserved 54.2.3 When a check of any extinguisher reveals a deficiency in the conditions listed as a) and b) of 4.2.2, immediate corrective action shall be taken. 4.2.4 When a check of any rechargeable extinguisher reveals a deficiency in any of the conditions c), d), e), f) or g) of 4.2.2, it shall be subjected to appropr