ASTM C969-17 Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines.pdf

上传人:李朗 文档编号:286786 上传时间:2019-07-10 格式:PDF 页数:3 大小:66.64KB
下载 相关 举报
ASTM C969-17 Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines.pdf_第1页
第1页 / 共3页
ASTM C969-17 Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines.pdf_第2页
第2页 / 共3页
ASTM C969-17 Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines.pdf_第3页
第3页 / 共3页
亲,该文档总共3页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation: C969 17Standard Practice forInfiltration and Exfiltration Acceptance Testing of InstalledPrecast Concrete Pipe Sewer Lines1This standard is issued under the fixed designation C969; the number immediately following the designation indicates the year oforiginal adoption or, in the case of

2、 revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.1. Scope1.1 This prac

3、tice covers procedures for testing installedprecast concrete pipe sewer lines using either water infiltrationor exfiltration acceptance limits to demonstrate the integrity ofthe installed materials and construction procedure.1.2 This practice is the inch-pound companion to PracticeC969M; therefore,

4、no SI equivalents are presented in thepractice.NOTE 1The owner shall specify the following: who will conduct,observe, and furnish labor, furnish material and measuring devices, andpay for the tests; who is responsible for determining local groundwaterconditions; and which test is to be conducted, th

5、at is, an infiltration test oran exfiltration test.NOTE 2The user of this practice is advised that test criteria presentedin this practice are similar to those in general use. Pipe, 24-in. diameter orlarger, may be accepted by visual inspection when testing for infiltration.1.3 This standard does no

6、t purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.4 This international standard was deve

7、loped in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Doc

8、uments2.1 ASTM Standards:2C822 Terminology Relating to Concrete Pipe and RelatedProducts3. Terminology3.1 DefinitionsFor definitions of terms relating to concretepipe, see Terminology C822.4. Summary of Practice4.1 Determine the groundwater conditions surrounding thesection of sewer to be tested and

9、 select the type of test to beconducted.4.2 For the infiltration test, the amount of water leaking intothe sewer line is measured, and the rate of infiltration isdetermined. If the rate is less than or equal to the allowablelimit, the section of sewer tested is acceptable.4.3 For the exfiltration te

10、st, the sewer line is filled withwater to the specified test head and the rate of water loss isdetermined. If the rate is less than or equal to the allowablelimit, the section of sewer tested is acceptable.5. Significance and Use5.1 This is not a routine test. The values recorded areapplicable only

11、to the sewer being tested and at the time oftesting.6. Preparation of the Sewer Line6.1 The sewer shall should be free of debris prior to testing.6.2 The manholes, the ends of the branches, laterals, wyesand stubs to be included in the test shall be plugged. All plugsshall be secured to prevent leak

12、age blowout due to testingpressure.7. Procedure7.1 Infiltration Testing:7.1.1 Conduct testing from manhole to manhole or betweenmore than two manholes. The length of main tested shall notexceed 700 ft.7.1.2 Stop all dewatering operations and allow the ground-water to return to its normal level. Infi

13、ltration testing shall notbe used unless the groundwater level is at least 2 ft above thecrown of the pipe for the entire length of the test section.7.1.3 Plug all pipe outlets discharging into the upstreammanhole.1This practice is under the jurisdiction of ASTM Committee C13 on ConcretePipe and is

14、the direct responsibility of Subcommittee C13.09 on Methods of Test.Current edition approved April 15, 2017. Published May 2017. Originallyapproved in 1982. Last previous edition approved in 2009 as C969 02(2009). DOI:10.1520/C0969-17.2For referenced ASTM standards, visit the ASTM website, www.astm.

15、org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis internat

16、ional standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Commit

17、tee.17.1.4 Measure the groundwater elevation and determine theaverage head over the test section.7.1.5 Measure infiltration leakage at the outlet of the testsection. Because leakage allowances are small, measurementsare best made by either timing the filling of a small containerof known volume, or b

18、y directing flow into a container for aspecified time and measuring the content, or by using smallweirs.7.1.6 If the measured rate of leakage is less than or equal tothe allowable leakage in accordance with 8.1, the section ofsewer tested is acceptable.7.1.7 If the test section fails, it is not proh

19、ibited that it berepaired and retested in accordance with this practice.7.2 Exfiltration Testing:7.2.1 Conduct testing from manhole to manhole or betweenmore than two manholes. The length of main tested shall notexceed 700 ft.7.2.2 Determine the groundwater elevation at both ends ofthe test section.

20、 If the groundwater level is less than 2 ft abovethe crown of the pipe measured from the highest elevation ofthe sewer, the exfiltration test shall be used.7.2.3 Plug all pipe outlets discharging into the upstreammanhole and the test section outlet. Fill the sewer line withwater.7.2.4 At the upstrea

21、m manhole the test head shall beestablished as minimum of 2 ft above the crown of the pipe, orat least 2 ft above existing groundwater, whichever is higher.7.2.5 Allow the pipe to remain saturated for a period longenough to allow water absorption in the pipe, a minimum of 4h and up to a maximum of 7

22、2 h. After the absorption period,refill the pipe to the required test head.7.2.6 Measure the leakage loss over a timed test period. Theminimum test period shall be 15 min and the maximum shallnot exceed 24 h.7.2.7 If the measured rate of leakage is less than or equal tothe allowable leakage in accor

23、dance with 8.2, the section ofsewer tested is acceptable.7.2.8 If the test section fails, it is not prohibited that it berepaired and retested in accordance with this practice. Thegroundwater elevation shall be redetermined prior to a secondtest and the test head adjusted, if necessary, in accordanc

24、e with7.2.4.8. Leakage Criteria8.1 Infiltration Testing:8.1.1 For infiltration testing, the allowable leakage limitincluding manholes is 200 gal/(in. of internal diameter) (mileof sewer) (24 h) when the average head on the test section is 6ft or less.NOTE 3The average head on the test section is the

25、 head above thecrown of the pipe at the upstream manhole plus the head above the crownof the pipe at the downstream manhole divided by two.8.1.2 When the average groundwater head on the testsection is greater than 6 ft, the allowable leakage shall beincreased in proportion to the ratio of the square

26、 root of theaverage groundwater head to the square root of the base headof 6 ft.8.1.3 Manholes shall be tested separately and independentlyor with the pipeline with the allowance of 0.1 gal/(ft ofdiameter) (ft of head) (h). If building or house leads areconnected to the main line being tested, allow

27、ance shall bemade for permissible leakage in such leads.8.2 Exfiltration Testing:8.2.1 For exfiltration testing the allowable leakage limitincluding manholes is 200 gal/(in. of internal diameter) (mileof sewer) (24 h) when the average head on the test section is 3ft or less.8.2.2 When the average he

28、ad on the test section is greaterthan 6 ft, the allowable leakage shall be multiplied by the ratioof the square root of the average test head and the square rootof the base head of 6 ft.8.2.3 Manholes shall be tested separately and independentlyor with the pipeline with an allowance of 0.1 gal/(ft o

29、fdiameter) (ft of head) (h).9. Calculation9.1 Sample calculations are presented in Appendix X1.10. Precision and Bias10.1 No justifiable statement is presently capable of beingmade either on precision or on bias of these procedures sincethe test results merely state whether there is conformance to t

30、hecriteria for the success specified. Due to the sealing effects ofgroundwater, internal flow in the sewerline, and test water, thetest conditions and results are not reproducible.C969 172APPENDIX(Nonmandatory Information)X1. APPLICATION OF THE PRACTICEX1.1 The following examples have been prepared

31、to dem-onstrate the technique of applying this practice:X1.1.1 Example 1: A sewer line is to be tested for infiltra-tion. The sewer line is a 12-in. diameter pipe with thegroundwater head over the upstream manhole of 9 ft and agroundwater head over the downstream manhole of 11 ft. Thedistance betwee

32、n manholes is 400 ft.X1.1.1.1 Find: The appropriate allowable rate of infiltrationleakage per hour of test.X1.1.1.2 Solution: The average test head in feet is:Test head 5 9111!/2# 5 10 (X1.1)Since the test head is greater than the base head (6 ft), theallowable rate of 200 gal/(in. diameter) (mile)

33、(24 h) must bemultiplied by the ratio of the square root of the averagegroundwater head (10 ft) and the square root of the base head(6 ft) or:Allowable leakage 5 200 3=10=6(X1.2)5258 gal/in. diameter!mile!24 h!Conversion of this rate to the allowable leakage for theabove line in gallons per hour giv

34、es:Allowable leakage:258 12 diameter! (X1.3)3 400 ft! /24 h! 3 5280 ft/mile!#59.77X1.1.1.3 Answer: 9.77 gal/h.X1.1.2 Example 2: A sewer line is to be tested for exfiltra-tion as the groundwater level is below the crown of the pipe atthe upstream manhole. The sewer line is an 18-in. diameterpipe with

35、 a specified test head of 2 ft over the crown of the pipeat the upstream manhole. The sewer line test section is 400 ftlong between manholes on a slope of 1.0 %.X1.1.2.1 Find: The appropriate allowable rate of exfiltrationleakage per hour of test.X1.1.2.2 Solution: The average test head in feet is:T

36、est head 5400 30.0112!1225 4 (X1.4)Since the test head is greater than the base head (3 ft), theallowable rate of 200 gal/(in. diameter) (mile) (24 h) must bemultiplied by the ratio of the square root of the test head andthe square root of the base head (3 ft) or:Allowable leakage 5 200 3=4=3(X1.5)5

37、231 gal/in. diameter!mile!24 h!Conversion of this rate to the allowable leakage for theabove line in gallons per hour gives:Allowable leakage 5 231 18 diameter! 3400 ft!/24 h!35280 ft/mile!# 5 13.1 (X1.6)X1.1.2.3 Answer: 13.1 gal/h.ASTM International takes no position respecting the validity of any

38、patent rights asserted in connection with any item mentionedin this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the riskof infringement of such rights, are entirely their own responsibility.This standard is subject to revis

39、ion at any time by the responsible technical committee and must be reviewed every five years andif not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standardsand should be addressed to ASTM International Headquarters. Your c

40、omments will receive careful consideration at a meeting of theresponsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you shouldmake your views known to the ASTM Committee on Standards, at the address shown below.This standard is copyrig

41、hted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org). Permission rights to photocopy the standard may also be secured from the Copyright Clearance Center, 222Rosewood Drive, Danvers, MA 01923, Tel: (978) 646-2600; http:/ 173

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ASTM

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1