1、BSI Standards Publication WB11885_BSI_StandardCovs_2013_AW.indd 1 15/05/2013 15:06 Energy performance of buildings - Method for calculation of system energy requirements and system efficiencies Part 6-9: Explanation and justification of EN 15316-4-8, Module M3-8-8 PD CEN/TR 15316-6-9:2017 TECHNICAL
2、REPORT RAPPORT TECHNIQUE TECHNISCHER BERICHT CEN/TR 15316-6-9 May 2017 ICS 27.160; 91.120.10; 91.140.10 English Version Energy performance of buildings - Method for calculation of system energy requirements and system efficiencies - Part 6-9: Explanation and justification of EN 15316-4-8, Module M3-
3、8-8 Performance nergtique des btiments - Mthode de calcul des besoins nergtiques et des rendements des systmes - Partie 6-9: Explication et justification de lEN 15316-4-8, Module M3-8-8 Heizungsanlagen und Wasserbasierte Khlanlagen in Gebuden - Verfahren zur Berechnung der Energieanforderungen und N
4、utzungsgrade der Anlagen - Teil 6-9: Begleitender TR zur EN 15316-4-8 (Wrmeerzeugung von Warmluft- und Strahlungsheizsystemen) This Technical Report was approved by CEN on 27 February 2017. It has been drawn up by the Technical Committee CEN/TC 228. CEN members are the national standards bodies of A
5、ustria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, S
6、pain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels 2017 CEN All rights of exploitation in any form and by any means reserved worldw
7、ide for CEN national Members. Ref. No. CEN/TR 15316-6-9:2017 E National foreword This British Standard is the UK implementation of CEN/TR 15316-6-9:2017. The UK participation in its preparation was entrusted to Technical Committee RHE/24, Heating systems and water based cooling systems in buildings.
8、 A list of organizations represented on this committee can be obtained on request to its secretary. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. The British Standards Institution 2017 Published by BSI Stan
9、dards Limited 2017 ISBN 978 0 580 95251 7 ICS 91.140.10; 91.120.10; 27.160 Compliance with a British Standard cannot confer immunity from legal obligations. This Published Document was published under the authority of the Standards Policy and Strategy Committee on 30 June 2017. Amendments/corrigenda
10、 issued since publication Date Text affected PUBLISHED DOCUMENT PD CEN/TR 15316-6-9:2017 TECHNICAL REPORT RAPPORT TECHNIQUE TECHNISCHER BERICHT CEN/TR 15316-6-9 May 2017 ICS 27.160; 91.120.10; 91.140.10 English Version Energy performance of buildings - Method for calculation of system energy require
11、ments and system efficiencies - Part 6-9: Explanation and justification of EN 15316-4-8, Module M3-8-8 Performance nergtique des btiments - Mthode de calcul des besoins nergtiques et des rendements des systmes - Partie 6-9: Explication et justification de lEN 15316-4-8, Module M3-8-8 Heizungsanlagen
12、 und Wasserbasierte Khlanlagen in Gebuden - Verfahren zur Berechnung der Energieanforderungen und Nutzungsgrade der Anlagen - Teil 6-9: Begleitender TR zur EN 15316-4-8 (Wrmeerzeugung von Warmluft- und Strahlungsheizsystemen) This Technical Report was approved by CEN on 27 February 2017. It has been
13、 drawn up by the Technical Committee CEN/TC 228. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuani
14、a, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Avenue Marnix 1
15、7, B-1000 Brussels 2017 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. CEN/TR 15316-6-9:2017 E PD CEN/TR 15316-6-9:2017CEN/TR 15316-6-9:2017 (E) 2 Contents Page European foreword . 4 Introduction 5 1 Scope 7 2 Normative references 9
16、3 Terms and definitions . 9 4 Symbols and subscripts 9 4.1 Symbols . 9 4.2 Subscripts 10 5 Information on the methods 10 5.1 Output of the method 10 5.2 Alternative methods . 10 5.3 Connection with building needs and zoning 11 5.4 Application data 11 5.5 Using net and gross calorific values 11 6 Sin
17、gle stage heaters . 12 6.1 Rationale . 12 6.1.1 General . 12 6.1.2 Losses calculation principle . 12 6.1.3 Auxiliary energy . 13 6.1.4 Expression of heat losses . 14 6.1.5 Recoverable, recovered and unrecoverable heat losses . 14 6.1.6 Input data 14 6.1.7 Characterization of a heater . 15 6.1.8 Char
18、acterization of local heaters include into lot 20 of Ecodesign regulation 15 6.1.9 Operating conditions characterization 15 6.1.10 Energy balance diagram 16 6.1.11 Assumptions . 18 6.2 Calculation intervals . 18 6.3 Input data 18 6.3.1 Product data . 18 6.3.2 System design data 21 6.3.3 Operating co
19、nditions 21 6.3.4 Constants and physical data . 21 6.4 Calculation procedure 22 6.4.1 Applicable timestep . 22 6.4.2 Time with burner ON and OFF . 22 6.4.3 Loss factors calculation 22 6.4.4 Recovered auxiliary energy 23 6.4.5 Energy calculation . 23 7 Multistage and modulating heaters . 24 7.1 Outpu
20、t data . 24 7.2 Calculation intervals . 24 7.3 Input data 24 PD CEN/TR 15316-6-9:2017CEN/TR 15316-6-9:2017 (E) 3 7.3.1 Product data . 24 7.3.2 System design data . 24 7.3.3 Operating conditions . 24 7.3.4 Constants and physical data . 24 7.4 Calculation procedure . 24 7.4.1 Applicable calculation in
21、terval 24 7.4.2 Operating conditions calculation 24 7.4.3 Time with burner ON and OFF . 24 7.4.4 Loss factors calculation 24 7.4.5 Auxiliary energy at minimum power 25 7.4.6 Energy calculation 25 8 Stoves and local heaters . 25 8.1 General . 25 8.2 Stoves without connection to a water based system .
22、 26 8.2.1 Output data . 26 8.2.2 Input data 26 8.2.3 Special cases . 26 8.2.4 Data input for solid fuel local heaters included in Lot 20 of Ecodesign regulation 26 8.3 Stoves and local heaters with a connection to a water based heating system . 26 9 Method selection . 27 10 Worked out examples . 27
23、11 Application range . 27 12 Regulation use . 27 13 Information on the accompanying spreadsheet 27 14 Results of the validation tests 27 15 Quality issues . 28 Annex A (informative) Calculation flowchart 29 A.1 Single stage heater . 29 A.2 Multi-stage and modulating heaters 30 Annex B (informative)
24、Balance formulae and origin of iteration formulae . 31 B.1 General . 31 B.2 Energy balance for single stage heaters . 31 B.3 Multi-stage or modulating . 32 B.3.1 Expression of losses . 32 B.3.2 Multi-stage or modulating on/off attempt . 34 B.3.3 Multi-stage or modulating average power calculation 35
25、 Annex C (informative) Example: On-Off heater 36 Bibliography . 44 PD CEN/TR 15316-6-9:2017CEN/TR 15316-6-9:2017 (E) 4 European foreword This document (CEN/TR 15316-6-9:2017) has been prepared by Technical Committee CEN/TC 228 “Heating systems and water based cooling systems in buildings”, the secre
26、tariat of which is held by DIN. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given
27、to CEN by the European Commission and the European Free Trade Association. PD CEN/TR 15316-6-9:2017CEN/TR 15316-6-9:2017 (E) 5 Introduction The set of EPB standards, technical reports and supporting tools: In order to facilitate the necessary overall consistency and coherence, in terminology, approa
28、ch, input/output relations and formats, for the whole set of EPB-standards, the following documents and tools are available: a) a document with basic principles to be followed in drafting EPB-standards: CEN/TS 16628, Energy Performance of Buildings Basic Principles for the set of EPB standards 1; b)
29、 a document with detailed technical rules to be followed in drafting EPB-standards; CEN/TS 16629, Energy Performance of Buildings Detailed Technical Rules for the set of EPB- standards 2; c) the detailed technical rules are the basis for the following tools: 1) a common template for each EPB-standar
30、d, including specific drafting instructions for the relevant clauses; 2) a common template for each technical report that accompanies an EPB standard or a cluster of EPB standards, including specific drafting instructions for the relevant clauses; 3) a common template for the spreadsheet that accomp
31、anies each EPB standard, to demonstrate the correctness of the EPB calculation procedures. Each EPB-standards follows the basic principles and the detailed technical rules and relates to the overarching EPB-standard, EN ISO 52000-1:2017. One of the main purposes of the revision of the EPB-standards
32、is to enable that laws and regulations directly refer to the EPB-standards and make compliance with them compulsory. This requires that the set of EPB-standards consists of a systematic, clear, comprehensive and unambiguous set of energy performance procedures. The number of options provided is kept
33、 as low as possible, taking into account national and regional differences in climate, culture and building tradition, policy and legal frameworks (subsidiarity principle). For each option, an informative default option is provided (Annex B). Rationale behind the EPB technical reports: There is a ri
34、sk that the purpose and limitations of the EPB standards will be misunderstood, unless the background and context to their contents and the thinking behind them is explained in some detail to readers of the standards. Consequently, various types of informative contents are recorded and made availabl
35、e for users to properly understand, apply and nationally or regionally implement the EPB standards. If this explanation would have been attempted in the standards themselves, the result is likely to be confusing and cumbersome, especially if the standards are implemented or referenced in national or
36、 regional building codes. Therefore each EPB standard is accompanied by an informative technical report, like this one, where all informative content is collected, to ensure a clear separation between normative and informative contents (see CEN/TS 16629 2): - to avoid flooding and confusing the actu
37、al normative part with informative content, PD CEN/TR 15316-6-9:2017CEN/TR 15316-6-9:2017 (E) 6 - to reduce the page count of the actual standard, and - to facilitate understanding of the set of EPB standards. This was also one of the main recommendations from the European CENSE project 4 that laid
38、the foundation for the preparation of the set of EPB standards. PD CEN/TR 15316-6-9:2017CEN/TR 15316-6-9:2017 (E) 7 1 Scope This Technical Report refers to EN 15316-4-8:2017, module M3-8.8. It contains information to support the correct understanding, use and national adaptation of EN 15316-4-8:2017
39、. This Technical Report does not contain any normative provision. The scope of EN 15316-4-8:2017 includes three categories of products: air heating systems means a system with one or more warm air generators for heating purpose. The hot air may be diffused in the installation space from the generato
40、r or distributed via a ductwork. overhead radiant heating systems, means systems using gas and designed to provide heat into the installation room. Radiation may be generated directly by the flame (overhead radiant luminous heaters) or by circulation of flue gas in a ductwork installed near the ceil
41、ing (overhead radiant tube heaters). stoves and local heaters means local devices that provide heat by transferring the heat generated by combustion into the surrounding environment. The typical devices are shown in Figures 1 to 4. Figure 1 Warm air generator for an air heating system PD CEN/TR 1531
42、6-6-9:2017CEN/TR 15316-6-9:2017 (E) 8 Figure 2 Overhead radiant luminous heater Figure 3 Overhead radiant tube heater a) b) Figure 4 Examples of local space heater: pellet stove and inset PD CEN/TR 15316-6-9:2017CEN/TR 15316-6-9:2017 (E) 9 2 Normative references The following documents, in whole or
43、in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 15316-1, Energy performance of buildings
44、Method for calculation of system energy requirements and system efficiencies Part 1: General and Energy performance expression, Module M3-1, M3-4, M3-9, M8-1, M8-4 EN 15316-4-8:2017, Energy performance of buildings Method for calculation of system energy requirements and system efficiencies Part 4-8
45、: Space heating generation systems, air heating and overhead radiant heating systems, including stoves (local), Module M3-8-8 EN ISO 7345:1995, Thermal insulation Physical quantities and definitions (ISO 7345:1987) EN ISO 52000-1:2017, Energy performance of buildings Overarching EPB assessment Part
46、1: General framework and procedures (ISO 52000-1:2017) NOTE References in the text of the standard are given as module codes that are detailed in the annex. This enables flexible references (e.g. to national documents where necessary for local application) and use outside the CEN environment. 3 Term
47、s and definitions For the purposes of this document, the terms and definitions given in EN ISO 7345:1995, EN ISO 52000-1:2017 and EN 15316-4-8:2017 apply. NOTE 1 No new definition is given in this Technical Report. NOTE 2 During public enquiry, it was commented that the term “stove” is not appropria
48、te. The correct term, which is used in the product standard is “local heaters”, meaning a heater which is not attached to any distribution system. The term “stove” survived in the title, as a synonym of “local heater” because the title of a standard cannot be changed during the drafting process. 4 S
49、ymbols and subscripts 4.1 Symbols For the purposes of this document some special symbols are defined in EN 15316-4-8:2017: is used for losses factors. They are expressed as a percentage, so the usual range is 0 to 100. Some negative values or values beyond 100 are expected when dealing with condensing heaters. is used for loaf factors. They are expressed in per unit, so the usual range is 0 to 1. Typically is a value that changes at each calculation interval depending on load. has been used for