1、 ABSGUIDE FOR AUTOMATIC OR REMOTE CONTROL AND MONITORING ON OFFSHORE INSTALLATIONS .2003 1 GUIDE FOR BUILDING AND CLASSING AUTOMATIC OR REMOTE CONTROL AND MONITORING FOR MACHINERY AND SYSTEMS (OTHER THAN PROPULSION) ON OFFSHORE INSTALLATIONS MARCH 2003 NOTICE NO. 1 October 2008 The following Rule Ch
2、anges become EFFECTIVE AS OF 1 JANUARY 2009. (See http:/www.eagle.org/rules/downloads.html for the consolidated version of the Guide for Automatic or Remote Control and Monitoring for Machinery and Systems (other then Propulsion) on Offshore Installations, with all Notices and Corrigenda incorporate
3、d.) Notes - The date in the parentheses means the date that the Rule becomes effective for new construction based on the contract date for construction, unless otherwise noted. (See 1-1-4/3.3 of the ABS Rules for Conditions of Classification Offshore Units and Structures (Part 1).) SECTION 2 AMCC NO
4、TATION (Revise Item A3 of Section 2, Table 12, as follows.) TABLE 12 Diesel Engines (2009) System Alarm Display Automatic shut-down with alarm Notes (2009) Oil mist in crankcase, mist concentration high; or Bearing Temperature high; or Alternative arrangements A3 (2009) High (2009) High for AMCCU. (
5、Not mandatory for AMCC). (2009) For engines having a power of 2250 kW (300 hp) and above or cylinder bore of more than 300 mm (11.8 in.). Single sensor having two independent outputs for initiating alarm and for shutdown will satisfy independence of alarm and shutdown. See 4-2-1/7.2 of the Steel Vessel Rules.