AHRI 365 I-P-2009 Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units.pdf

上传人:diecharacter305 文档编号:422525 上传时间:2018-11-06 格式:PDF 页数:18 大小:252.07KB
下载 相关 举报
AHRI 365 I-P-2009 Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units.pdf_第1页
第1页 / 共18页
AHRI 365 I-P-2009 Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units.pdf_第2页
第2页 / 共18页
AHRI 365 I-P-2009 Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units.pdf_第3页
第3页 / 共18页
AHRI 365 I-P-2009 Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units.pdf_第4页
第4页 / 共18页
AHRI 365 I-P-2009 Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units.pdf_第5页
第5页 / 共18页
亲,该文档总共18页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、 2009 Standard for Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units AHRI Standard 365 (I-P) Price $15.00 (M) $30.00 (NM) Copyright 2009, by Air-Conditioning, Printed in U.S.A. Heating, and Refrigeration Institute Registered United States Patent and Trademark

2、Office IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, c

3、onstructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry pract

4、ices. AHRI does not certify or guarantee that any tests conducted under the standards/guidelines will not be non-hazardous or free from risk. AHRI CERTIFICATION PROGRAM PROVISIONS Scope of the Certification Program The Certification Program includes Commercial and Industrial Unitary Air-Conditioning

5、 Condensing Units rated at or above 135,000 Btu/h but below 250,000 Btu/h at the AHRI Standard Rating Conditions (Cooling). Certified Ratings The following Certification Program ratings are verified by test: 1. Single Number Rating Cooling Capacity, Btu/h 2. Single Number Rating Energy Efficiency Ra

6、tio, EER, Btu/(Wh) 3. Integrated Energy Efficiency Ratio, IEER (effective January 1, 2010) or Integrated Part-Load Value, (IPLV) (effective through December 31, 2009) Conformance to the requirements of the Maximum Operating Conditions Tests (Section 8) is also verified by test. Note: This standard s

7、upersedes ARI Standard 365-2002. For SI ratings, see AHRI Standard 366 (SI)-2009. TABLE OF CONTENTS PAGE Section 1. Purpose . 1 Section 2. Scope 1 Section 3. Definitions 1 Section 4. Classifications . 2 Section 5. Test Requirements 2 Section 6. Rating Requirements 3 Section 7. Minimum Data Requireme

8、nts for Published Ratings . 7 Section 8. Operating Requirements . 8 Section 9. Marking and Nameplate Data . 9 Section 10. Conformance Conditions 9 TABLES Table 1. Classifications of Commercial and Industrial Air-Conditioning Condensing Units . 2 Table 2. Standard Rating Conditions 3 Table 3. IEER Pa

9、rt-Load Rating Conditions 5 APPENDICES Appendix A. References - Normative 10 Appendix B. References Informative . 10 Appendix C. Method and Example of Calculating Integrated Part-Load Values (IPLV) Normative . 11AHRI STANDARD 365 (I-P)-2009 1 PERFORMANCE RATING OF COMMERCIAL AND INDUSTRIAL UNITARY A

10、IR-CONDITIONING CONDENSING UNITS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Commercial and Industrial Unitary Air-Conditioning Condensing Units: definitions; classifications; test requirements; rating requirements; minimum data requirements for Published Ratings

11、; operating requirements; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendm

12、ent as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory-made Commercial and Industrial Unitary Air-Conditioning Condensing Units greater than or equal to 135,000 Btu/h as defined in Section 3. 2.1.1 Energy Source. This standard applies only to electrically-driven, me

13、chanical compression-type condensing units. 2.2 Exclusions. This standard does not apply to the testing and rating of condensing units for refrigeration purposes, as defined in AHRI Standard 520. Section 3. Definitions All terms in this document shall follow the standard industry definitions in the

14、current edition of ASHRAE Terminology of Heating, Ventilation, Air-Conditioning and Refrigeration unless otherwise defined in this section. 3.1 Bubble Point. Refrigerant liquid saturation temperature at a specified pressure. 3.2 Commercial and Industrial Unitary Air-Conditioning Condensing Unit. A f

15、actory-made assembly of refrigeration components designed to compress and liquefy a specific refrigerant. It consists of one or more refrigerant compressors, refrigerant condensers (air-cooled, evaporatively cooled, and/or water-cooled), condenser fans and motors (where used) and factory-supplied ac

16、cessories. 3.3 Cooling Capacity. The capacity in Btu/h obtained at specific conditions. It is equal to the increase in total enthalpy between the liquid refrigerant entering the expansion valve and superheated return gas multiplied by the mass flow rate of the refrigerant. 3.4 Dew Point. Refrigerant

17、 vapor saturation temperature at a specified pressure. 3.5 Energy Efficiency Ratio (EER). A ratio of the Cooling Capacity in Btu/h to the power input values in watts at any given set of Rating Conditions expressed in Btu/(Wh). 3.6 Integrated Energy Efficiency Rating (IEER). A single number part-load

18、 efficiency figure of merit calculated per the method described in this standard. 3.7 Integrated Part-Load Value (IPLV). A single number cooling part-load figure of merit calculated per the method described in Appendix C. AHRI STANDARD 365 (I-P)-2009 2 3.8 Published Rating. A statement of the assign

19、ed values of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes t

20、he rating of all performance characteristics shown on the unit or published in specifications, advertising, or other literature controlled by the manufacturer, at stated Rating Conditions. 3.8.1 Application Rating. A rating based on tests performed at application Rating Conditions (other than Standa

21、rd Rating Conditions). 3.8.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.9 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.9.1 Standard Rating Cond

22、itions. Rating Conditions used as the basis of comparison for performance characteristics. 3.10 “Shall“ or “Should.“ “Shall“ or “should“ shall be interpreted as follows: 3.10.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the s

23、tandard is claimed. 3.10.2 Should. “Should“ is used to indicate provisions which are not mandatory but which are desirable as good practice. 3.11 Single Number Rating. The Cooling Capacity and EER determined by the results of the tests at Rating Condition No. 1 for air-cooled and evaporatively-coole

24、d condensing units and at Rating Condition No. 3 for water-cooled condensing units (Section 6). Section 4. Classifications Equipment covered within the scope of this standard shall be classified as shown in Table 1: Table 1. Classifications of Commercial and Industrial Air-Conditioning Condensing Un

25、its Designation AHRI Type Condenser Type Arrangement Remote Condensing Unit (RCU) RCU-A Air COMP COND RCU-E Evaporatively RCU-W Water Section 5. Test Requirements 5.1 Test Requirements. All Standard Ratings shall be verified by tests conducted in accordance with ANSI/ASHRAE Standard 23 and with the

26、test methods and procedures as described in this standard. 5.1.1 An alternate method of verification may be by tests conducted in accordance with ANSI/ASHRAE Standard 37 provided that the suction dew point temperature and the return gas temperature are determined from the procedures in this standard

27、. AHRI STANDARD 365 (I-P)-2009 3 Section 6. Rating Requirements 6.1 Standard Ratings. Published Ratings shall be obtained at one or more of the Standard Rating Conditions as shown in Table 2. Power input shall be the total power input to the compressor(s), fan(s), controls, and any other components

28、included as part of the condensing unit. Table 2. Standard Rating Conditions Air- and Evaporatively-Cooled Condensing Units Rating Condition Air Temperature Entering and Surrounding Unit Refrigerant Temperature Entering Condensing Unit 1Dry-Bulb Wet-Bulb 2Suction Dew Point Return Gas F F F F 1 3 295

29、.0 80.0 75.0 67.0 45.0 45.0 60.0 60.0 Water-Cooled Condensing Units Rating Condition Water Temperature Refrigerant Temperature Entering Condensing Unit 1 Entering Leaving Suction Dew Point Return Gas F F F F 3 3 4 85.0 75.0 95.0 45.0 45.0 60.0 60.0 Same water flow rate as established above. Notes: 1

30、The liquid temperature and pressure leaving the condensing unit shall be reported by the manufacturer in its ratings. 2 Required for evaporatively-cooled condensing units only. 3The Single Number Ratings are determined by the results of the tests at Rating Condition No. 1 or at Rating Condition No.

31、3. 6.1.1 Values of Standard Cooling Capacity Ratings. These ratings shall be expressed only in terms of thousands of Btu/h in multiples of 2,000 Btu/h for units with Standard Ratings of 400,000 Btu/h and under. For units with Standard Ratings of over 400,000 Btu/h, the ratings shall be expressed in

32、multiples of 5,000 Btu/h. 6.1.2 Values of Standard Efficiency Ratings. EER, in Btu/(Wh), and IEER shall be expressed in multiples of 0.1. 6.1.3 Single Number Ratings. The reported values shall be determined by the results obtained at Rating Condition No. 1 or at Rating Condition No. 3. 6.1.4 Electri

33、cal Conditions. Standard Rating tests shall be performed at the nameplate rated voltage(s) and frequency. For condensing units with dual nameplate voltage ratings, Standard Rating tests shall be performed at both voltages, or at the lower of the two voltages, if only a single Standard Rating is to b

34、e published. 6.1.5 Condenser Airflow Rate. All Standard Ratings for condensing units shall be determined at the condenser airflow rate specified by the manufacturer where the fan drive is adjustable. Where the fan drive is direct-connected, Standard Ratings shall be determined at the condenser airfl

35、ow rate established when the condensing unit is operated with all of the associated inlet louvers and any duct work and attachments considered by the manufacturer as normal installation practice. Once established, the airflow circulation rate of the condensing unit shall remain unchanged throughout

36、all tests prescribed herein, except as altered by automatic controls. AHRI STANDARD 365 (I-P)-2009 4 6.2 Part-Load Rating. Integrated Part-Load Value (IPLV) is in effect until January 1, 2010. See Appendix C for the method and calculation of IPLV. Effective January 1, 2010, all units rated in accord

37、ance with this standard shall include an Integrated Energy Efficiency Ratio (IEER), even if they only have one stage of capacity control. 6.2.1 General. The IEER is intended to be a measure of merit for the part load performance of the unit. Each building may have different part load performance due

38、 to local occupancy schedules, building construction, building location and ventilation requirements. For specific building energy analysis an hour-by-hour analysis program should be used. 6.2.2 Integrated Energy Efficiency Ratio (IEER). For equipment covered by this standard, the IEER shall be calc

39、ulated using tests, derived data, and the following formula. IEER = 0.020 A + 0.617 B + 0.238 C + 0.125 D 1 Where: A = EER at 100% capacity at design conditions B = EER at 75% capacity and reduced ambient (see Table 3) C= EER at 50% capacity and reduced ambient (see Table 3) D= EER at 25% capacity a

40、nd reduced ambient (see Table 3) The IEER rating requires that the unit efficiency be determined at 100%, 75%, 50% and 25% load at the conditions specified in Table 3. If the unit, due to its capacity control logic cannot be operated at the 75%, 50%, or 25% load points, then the 75%, 50%, or 25% per

41、formance should be determined by plotting the efficiency vs. the percent load and using straight line segments to connect the actual performance points and interpolation to determine the rating performance at 75%, 50% and 25%. For the interpolation, an actual capacity point equal to or less than the

42、 required rating point must be used to plot the curves. Extrapolation of the data is not allowed. If the unit cannot be unloaded to the 75%, 50%, or 25% load, then the unit should be run at the minimum step of unloading at the condensing unit conditions defined for each of the rating load points and

43、 then adjust the efficiency for cyclic performance using the following equation. D C CF CTLFCapacityEERLF(C (P P ) P=+2 Where: Capacity = Measured capacity at the lowest machine unloading point operating at the desired part load rating condition (Btu/h) PC= Compressor power at the lowest machine unl

44、oading point operating at the desired part load rating condition (Watts) PCD = Condenser fan power, if applicable, at the minimum step of unloading at the desired part load rating condition (Watts) PCT = Control circuit power and any auxiliary loads (Watts) CD = Degradation coefficient to account fo

45、r cycling of the compressor for capacity less than the minimum step of capacity. CD should be determined using the following equation. DC ( 0.13 LF) 1.13=+ 3 Where: LF = Fractional “on” time for last stage at the desired load point %Load (Full Load Unit Capacity)100LFPart Load Unit Capacity=4 %Load

46、= Standard rating point, i.e. 75%, 50%, 25%. AHRI STANDARD 365 (I-P)-2009 5 Table 3. IEER Part-Load Rating Conditions CONDITIONS F Refrigerant Entering Condensing Unit (For All Units) Suction Mid Point Temperature 2Return Gas Temperature 45.0 60.0 Condenser (Air-Cooled) Entering Dry-Bulb Temperature

47、 and Dry-Bulb Temperature Surrounding Unit Condenser Airflow Rate (cfm) For %Load 44.4%, Outdoor Air Temperature (OAT) = 0.54 %Load + 41.0 For % Load 34.8%, EWT = 0.460 %Load + 39.0 For %Load 36.6%, EWB= 0.35 %Load + 40.0 For %Load = 36.6%, EWB = 52.8 NOTES: 1 Adjust condenser airflow as required by

48、 the unit controls for head pressure control. 2 For refrigerants with a glide, the mid-point saturated suction temperature is the average of the bubble point and dew point. 6.2.3 Example calculations. Example 1 Condensing unit has proportional capacity control and capable of being run at the 75%, 50

49、%, and 25% rating points. AHRI STANDARD 365 (I-P)-2009 6 The following data was obtained from actual unit measurements. Stage Ambient Actual % Load Saturated Suction Capacity Compr. (PC) Cond. Fan (PCF) Control (PCT) EER (F) (Capacity) (F) Btu/h W W W Btu/(Wh) 4 95.0 100 45 481,866 43,535 2,100 100 10.54 3 81.5 75 45 361,397 28,731 2,100 100 11.68 2 68.0 50 45 240,933 17,791 2,100 100 12.05 1 65.0 25 45 120,464 9,491 2,100 100 10.30 IEER = (0.02 10.54) + (0.617 11.68) + (0.238 12.05) + (0.125 10.30) = 11.58 Example