资源描述

1、 Price $15.00 (M) $30.00 (NM) 8Copyright 1994, by Air-Conditioning and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office 2008 Standard for Performance Rating of Heat Pump Pool Heaters ARI Standard 1160Copyright Air-Conditioning, Heating and Refrigeration

2、Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-Price $10.00 (M) $20.00 (NM) Copyright 2008, by Air-Conditioning and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office Note

3、: This standard supersedes ARI Standard 1160-2007. ARI CERTIFICATION PROGRAM PROVISIONS Scope of the Certification Program The certification program includes only Heat Pump Pool Heaters that are electrically driven, mechanical compression type systems as defined in the standard. Equipment covered: T

4、he program applies to Heat Pump Pool Heaters having 60 Hz single-phase or three-phase compressors. Certified Ratings The following ratings are verified by test: a. Standard Rating Heating Capacity - High Air Temperature, Btu/h W b. Standard Rating COP - High Air Temperature, watts/watt W/W c. Standa

5、rd Rating Heating Capacity - Low Air Temperature, Btu/h W d. Standard Rating COP - Low Air Temperature, watts/watt W/W IMPORTANT SAFETY DISCLAIMER ARI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed

6、or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AR

7、I uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. ARI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Copyright Air-Conditioning, Heating and Refrigeration

8、 Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION PAGE Section 1. Purpose .1 Section 2. Scope 1 Section 3. Definitions1 Section 4. Classifications 2 Section 5. Test Requirements .3 Section 6.

9、 Rating Requirements 3 Section 7. Minimum Data Requirements for Published Ratings 4 Section 8. Operating Requirements 4 Section 9. Marking and Nameplate Data 5 Section 10. Conformance Conditions .5 TABLES Table 1. Classifications of Heat Pump Pool Heaters .2 Table 2. Standard Rating Conditions .3 AP

10、PENDICES Appendix A. References Normative .6 Appendix B. References Informative .6 Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-Copyright Air-Conditioning, Hea

11、ting and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 1160-2008 1 PERFORMANCE RATING OF HEAT PUMP POOL HEATERS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establis

12、h for Heat Pump Pool Heaters: definitions; classifications; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industr

13、y, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to the rating and testing of complete factory-made Heat Pump Pool Heater re

14、frigeration systems as defined in Section 3. 2.1.1 Energy Source. This standard applies only to air-source, electrically driven, mechanical compression type systems. 2.2 Exclusions. This standard does not apply to the following: 2.2.1 Individual assemblies. 2.2.2 Unitary Air-Conditioners as defined

15、in ARI Standard 210/240, Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment, with capacities less than 65,000 Btu/h 19,000 W. 2.2.3 Unitary heat operated air-conditioning equipment. 2.2.4 Water-Source Heat Pumps as defined in ANSI/ARI/ASHRAE/ISO 13256-1, Water-Source H

16、eat Pumps Testing and Rating for Performance Part I: Water-to-Air and Brine-to-Air Heat Pumps. 2.2.5 Commercial and Industrial Unitary Air Conditioning and Heat Pump Equipment with capacities of 65,000 Btu/h 19,000 W or greater as defined in ARI Standard 340/360, Performance Rating of Unitary Air Co

17、nditioning and Heat Pump Equipment. 2.2.6 Single Package Vertical Air-Conditioners and Heat Pumps as defined in ARI Standard 390, Performance Rating of Single Package Vertical Air-Conditioners and Heat Pumps. 2.2.7 Package Terminal Air-Conditioners and Heat Pumps as defined in ARI Standard 310/380,

18、Standard for Packaged Terminal Air-Conditioners and Heat Pumps, (CSA-C744-04). Section 3. Definitions All terms in this document follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined

19、in this section. 3.1 Coefficient of Performance (COP). A ratio of the Heating Capacity in watts W to the power input values in watts W at any given set of Rating Conditions expressed in watts/watt W/W. For heating COP, supplementary resistance heat shall be excluded. Copyright Air-Conditioning, Heat

20、ing and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 1160-2008 2 3.1.1 Standard Coefficient of Performance. A ratio of the capacity to power input value obtained at Standard Rating Condi

21、tions. 3.2 Heat Pump Pool Heater. A factory-made assembly, which contains the air moving device, compressor, refrigerant-to-water heat exchanger and air-to-refrigerant heat exchanger using ambient air as the heat source. Models may consist of more than one assembly to be used together for the purpos

22、e of cooling and heating air. Models with separated assemblies shall be designed to be used together, and the requirements of rating outlined in this standard are based upon the use of matched assemblies. 3.2.1 Functions. Heat Pump Pool Heaters shall provide the function of heating pool water to ach

23、ieve a controlled temperature, but may include the functions of pool water cooling, air-heating, air cooling, air-circulating, air-cleaning, or dehumidifying. 3.3 Heating Capacity. The capacity associated with the change in water temperature, expressed in Btu/h W. 3.4 Published Rating. A statement o

24、f the assigned values of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal capacity and type (identification) produced by the same manufacturer. As used herein, the term Published R

25、ating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufacturer, at stated Rating Conditions. 3.4.1 Application Rating. A rating based on tests performed at application Rating Conditions (ot

26、her than Standard Rating Conditions). 3.4.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.5 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.5.1 Stand

27、ard Rating Conditions. Rating Conditions used as the basis of comparison for performance characteristics. 3.6 “Shall“ or “Should“. “Shall“ or “should“ shall be interpreted as follows: 3.6.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if complian

28、ce with the standard is claimed. 3.6.2 Should. “Should“ is used to indicate provisions which are not mandatory but which are desirable as good practice. Section 4. Classifications 4.1 Classifications. A Heat Pump Pool Heater within the scope of this standard shall be classified as shown in Table 1.

29、Table 1. Classifications of Heat Pump Pool Heaters Types of Heat Pump Pool Heaters Designation Unit Type Pool Heating Only Pool Heating and Cooling Single Package SPPH-H SPPH-H/C Split System SSPH-H SSPH-H/C Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under licens

30、e with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 1160-2008 3 Section 5. Test Requirements 5.1 All Standard Ratings shall be verified by tests conducted in accordance with ANSI/ASHRAE Standard 146. Section 6. Rating Requirements 6.1 Standard R

31、ating. Standard Ratings shall be established by tests conducted at the Standard Rating Conditions specified in Table 2. 6.1.1 Values for Standard Ratings. Standard Ratings relating to heating capacity shall be net values. If a circulating pump is within the unit and energized under normal operation,

32、 that electrical energy shall be included in the total power input to the unit. Supplementary electric heat shall not be included in the Standard Ratings of the unit. 6.1.1.1 Values for Standard Heating Capacity Ratings. Standard heating capacity ratings shall be expressed only in terms of Btu/h W i

33、n multiples of 500 150 for units with ratings less than 50,000 Btu/h 15,000 W, or multiples of 1,000 300 for units with ratings 50,000 Btu/h 15,000 W and greater. 6.1.1.2 Values for Standard Coefficients of Performance. Standard Coefficients of Performance shall be expressed in multiples of 0.1. 6.1

34、.2 Electrical Conditions. Standard rating tests shall be conducted at nameplate rated voltage and frequency. For models with dual voltage nameplate ratings, the tests shall be conducted at the higher of the two voltages. 6.1.3 Requirements for Separated Assemblies. When a model consists of two separ

35、ate assemblies, the length of the interconnecting refrigerant tubing shall not be less than 25 ft (7.6 m). The line sizes, insulation and details of installation shall be per the manufacturers installation instructions. 6.2 Application Ratings. Application Ratings shall be established by tests condu

36、cted using Rating Conditions other than those specified in Table 2. 6.3 Tolerances. To comply with this standard, measured test results for Heating Capacity and Coefficient of Performance shall not be less than 95% of Published Ratings. Table 2. Standard Rating Conditions Air Temperature Surrounding

37、 Unit Water Temperature Entering Unit Water Flow Rate (or Less if Specified by the Manufacturer) Dry-bulb F C Wet-bulb F C F C gpm L/s High Air Temperature - Mid Humidity (62% RH) 80.6 27.0 70.7 21.5 80.0 26.7 0.450 per 1000 Btu/h 0.028 per 293.1 Watts Low Air Temperature - Mid Humidity (63% RH) 50.

38、0 10.0 44.2 6.78 80.0 26.7 Same flow rate as established in High Air Temperature - Mid Humidity (62% RH) Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STAND

39、ARD 1160-2008 4 Section 7. Minimum Data Requirements for Published Ratings 7.1 Minimum Data Requirements for Published Ratings. As a minimum, Published Ratings shall include all Standard Ratings. All claims to ratings within the scope of this standard shall include the statement “Rated in accordance

40、 with ARI Standard 1160.“ All claims to ratings outside the scope of this standard shall include the statement “Outside the scope of ARI Standard 1160.“ Wherever Application Ratings are published or printed, they shall include a statement of the conditions at which the ratings apply. Section 8. Oper

41、ating Requirements 8.1 Performance Requirements. To comply with this standard, Heat Pump Pool Heaters shall be designed and produced in such a manner that any production unit will meet the requirements of this section. 8.2 Maximum Operating Conditions Test. Heat Pump Pool Heaters shall be designed a

42、nd produced to pass the following maximum operating conditions test. 8.2.1 Temperature Conditions. Air temperature surrounding unit: 86.0F 30.0C dry-bulb 68.0F 20.0C wet-bulb Water temperature entering unit: 101.0F 38.3C Water flow rate: Same flow rate as established in High Air Temperature - Mid Hu

43、midity (62% RH) in Table 2. 8.2.2 Voltages. The test shall be run at the Range A minimum utilization voltage from ARI Standard 110, Table 1, based upon the units nameplate rated voltage(s). This voltage shall be supplied at the units service connection and at rated frequency. 8.2.3 Procedure. The eq

44、uipment shall be operated for one hour at the temperature conditions and voltage specified. 8.2.4 Requirements. The equipment shall operate continuously without interruption for any reason for one hour. 8.3 Voltage Tolerance Test. Heat Pump Pool Heaters shall pass the following voltage tolerance tes

45、t with the same water flow rate as established in High Air Temperature Mid Humidity (62% RH) in Table 2. 8.3.1 Temperature Conditions. Temperature conditions shall be maintained at the steady state conditions as shown in Table 2. 8.3.2 Voltages. 8.3.2.1 Tests shall be run at the Range B minimum and

46、maximum utilization voltages from ARI Standard 110, Table 1, based upon the units nameplate rated voltage(s). These voltages shall be supplied at the units service connection and at rated frequency. A lower minimum or a higher maximum voltage shall be used, if listed on the nameplate. 8.3.2.2 The po

47、wer supplied to single phase equipment shall be adjusted just prior to the shut-down period (Section 8.3.3.2) so that the resulting voltage at the units service connection is 86% of nameplate rated voltage when the compressor motor is on locked-rotor. (For 200V or 208V nameplate rated equipment, the

48、 restart voltage shall be set at 180V when the compressor motor is on locked rotor). Open circuit voltage for three-phase equipment shall not be greater than 90% of nameplate rated voltage. Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 1160-2008 5 8.3.2.3 Within one minute after the equipment has resumed continuous operation (Section 8.3.4.3), the voltage shall be restored to the values specific in Section