ANSI ASTM F2975-2012 Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems《商用厨房通风系统的野外使用特性测量方法》.pdf

上传人:roleaisle130 文档编号:433237 上传时间:2018-11-11 格式:PDF 页数:13 大小:222.21KB
下载 相关 举报
ANSI ASTM F2975-2012 Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems《商用厨房通风系统的野外使用特性测量方法》.pdf_第1页
第1页 / 共13页
ANSI ASTM F2975-2012 Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems《商用厨房通风系统的野外使用特性测量方法》.pdf_第2页
第2页 / 共13页
ANSI ASTM F2975-2012 Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems《商用厨房通风系统的野外使用特性测量方法》.pdf_第3页
第3页 / 共13页
ANSI ASTM F2975-2012 Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems《商用厨房通风系统的野外使用特性测量方法》.pdf_第4页
第4页 / 共13页
ANSI ASTM F2975-2012 Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems《商用厨房通风系统的野外使用特性测量方法》.pdf_第5页
第5页 / 共13页
点击查看更多>>
资源描述

1、Designation: F2975 12 (Reapproved 2017) An American National StandardStandard Test Method forMeasuring the Field Performance of Commercial KitchenVentilation Systems1This standard is issued under the fixed designation F2975; the number immediately following the designation indicates the year oforigi

2、nal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method can be used to measure and validatesuccessful d

3、esign, installation and commissioning of commer-cial kitchen HVAC and makeup air systems for specificinstallations.1.2 This test method field evaluates commercial kitchenventilation system airflows and pressures.1.3 This test method field evaluates visual hood capture andcontainment performance.1.4

4、The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are for informa-tion only.1.5 The data generated is specific to the field conditions asinstalled.1.6 This test method may involve hazardous materials,gasses (for example, CO) operations, and equipmen

5、t. Thisstandard does not purport to address all of the safety concerns,if any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices and determine the applicability of regulatory limita-tions prior to use.1.7 This internatio

6、nal standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Commit

7、tee.2. Referenced Documents2.1 ASTM Standards:2F1704 Test Method for Capture and Containment Perfor-mance of Commercial Kitchen Exhaust Ventilation Sys-tems2.2 Other Standards:ANSI/ASHRAE Standard 111-2008 Measurement, Testing,Adjusting and Balancing of Building HVAC Systems3ANSI/ASHRAE Standard 154

8、 Ventilation for CommercialCooking Operations3Testing, Adjusting and Balancing, Chapter 37 2007 HVACApplications Handbook4Kitchen Ventilation, Chapter 31 2007 HVAC ApplicationsHandbook43. Terminology3.1 Definitions:3.1.1 airflow ratevolumetric flow rate of air in units offt3/min (cfm) or m3/s. When

9、adjusted for standard air densitythe flow rate is designated by scfm.3.1.2 appliancecooking device used in kitchen and pow-ered by gas, and/or electricity and/or solid fuel.3.1.3 barometric pressureabsolute pressure of the airmeasured by a barometer or absolute pressure measuringdevice.3.1.4 capture

10、 and containment (C the performance ofthe ventilation system should be checked to verify that thedesign is adequate for the actual operation, particularly atmaximum cooking and at outdoor environmental extremes.Any necessary changes should be made, and all the recordsshould be updated to show the ch

11、anges. Rechecking the airbalance should not be necessary more than once every 2 yearsunless significant changes are made in facility operation. Ifthere are major changes, such as a new type of cookingequipment or added or deleted exhaust connections, the systemshould be modified accordingly and reba

12、lanced.10.2 Exhaust Air Flow Rate Measurements Through KitchenExhaust Hoods:10.2.1 The total air flow rate through each exhaust hoodshall be determined using one of the following methods withthe cooking appliances turned at hot ready-to-cooking condi-tion.10.2.1.1 When a specific air flow rate measu

13、rement protocolis specified by the hood or filter manufacturer, the protocoldeveloped by the manufacturer shall be followed.10.2.1.2 When the filters under test have no protocol fromthe manufacturer but has a protocol specified in this document,the method of test specified in this document shall be

14、followed.10.2.1.3 When the filters under test have no protocol fromthe manufacturer and do not have a protocol specified in thisdocument, or one or more obstructions prevents proper use offace velocity measuring instruments, a duct traverse methodshall be used to determine the total air flow rate th

15、rough anexhaust hood using a Pitot-static tube. The Log-Tchebycheffrule shall be used for rectangular ducts and the Log-linear rulefor circular ducts as specified in ANSI/ASHRAE Standard111-2008, ”Measurement, testing, adjusting and balancing ofbuilding HVAC systems”.10.2.2 Hoods with Baffle Filters

16、:10.2.2.1 These measurements are limited to the use ofa4in.rotating vane anemometer with its body parallel to andpositioned flush to the filter face.FIG. 1 Baffle FilterF2975 12 (2017)510.2.2.2 Each filter in an exhaust hood must be evaluatedseparately and the flow rate through each filter added tod

17、etermine the total airflow rate through the entire exhausthood.10.2.2.3 The dimensions of the open portion, height andwidth (H and W), of each filter shall be measured with anaccuracy of 614 inch and the results recorded.10.2.2.4 The center of the rotating vane anemometer shalltraverse the entire fa

18、ce of the filter in a back-and forth motion.The minimum time to traverse the entire filter face shall be 30s. An example is shown in Fig. 2. Average velocity readingsshall be measured and recorded at each location.10.2.2.5 The body of the instrument shall remain flush to theexterior surface of the f

19、ilters, and be kept parallel to it.10.2.2.6 Airflow through the instrument shall not be ob-structed by the operators hand or fingers.10.2.2.7 The velocity measurements in a filter bank shall bemeasured beginning with the filter at one end of the filter bankand ending with the filter at the opposite

20、end.10.2.2.8 The procedure described above shall be repeatedtwice more to obtain the average velocity for all three readingsat each location in feet per minute (FPM).10.2.3 Hoods with Cyclone Filters:10.2.3.1 These measurements are limited to the use of a234-in. diameter rotating vane anemometer wit

21、h its bodyparallel to and positioned 2 in. from the filter face.10.2.3.2 Each filter in an exhaust hood must be evaluatedseparately and the flow rate through each filter added togetherto determine the total airflow rate through the entire exhausthood.10.2.3.3 The gross dimensions (height and width)

22、of theopening areas of each filter shall be measured and recorded.10.2.3.4 The velometer shall traverse each opening a mini-mum of 30 s. Fig. 4 shows the positions by “X” for an entirefilter bank of cyclone filters.Average velocity readings shall bemeasured and recorded at each location.10.2.3.5 The

23、 body of the anemometer must remain 2 in.from the exterior surface of the filters, and be kept parallel toit.Asmall indicator shall be attached to the exterior body of theanemometer to maintain the 2 in. spacing.10.2.3.6 The vane must attain full speed at each positionbefore the velocity is recorded

24、.10.2.3.7 The airflow through the anemometer shall not beobstructed by the operators hand or fingers.10.2.3.8 The velocity measurements in a filter bank shall bemeasured beginning with the filter at one end of the filter bankand ending with the filter at the opposite end.10.2.3.9 The procedure descr

25、ibed above shall be repeatedtwice more to obtain the average velocity for all three readingsat each measurement position in feet per minute (FPM).10.2.4 Hoods with Slot Filters (CartridgeRemovable orStationary):10.2.4.1 These measurements are limited to the use of a 2.75in. rotating vane anemometer

26、positioned at the slot opening.Each filter in an exhaust hood must be evaluated separately andthe flow rates through each filter added together to determinethe total airflow rate through the entire exhaust hood.10.2.4.2 The body of the anemometer must remain parallelto the slot opening with one side

27、 in the same plane as theopening.10.2.4.3 The center of the anemometer shall be traversedacross the center of the slot opening.10.2.4.4 Velocity measurements shall be made as a traversethrough the center of each of the slot areas. The minimum timeto uniformly traverse a slot opening shall be 30 s.10

28、.2.4.5 The airflow through the anemometer shall not beobstructed by the operators hand or fingers.10.2.4.6 The fan blade shall attain full speed before record-ing any velocity data.10.2.4.7 The average velocity through each slot filter shallbe measured starting at a filter at one end of the filter b

29、ank andending with the filter at the other end of the bank.10.2.4.8 The procedure shall be repeated twice more toobtain the average velocity for all three readings for each filterin feet per minute (FPM).10.2.5 Exhaust Duct Velocity Traverse:10.2.5.1 This method shall be used to determine the total

30、airflow rate through an exhaust hood when velocity measure-ments at the filter face are not possible or have no establishedprotocols.10.2.5.2 Instrumentation is limited to a Pitot-static tubeconnected to a differential pressure measuring device.10.2.5.3 The number and position of velocity measuremen

31、tpoints within the duct shall conform to the values documentedin ANSI/ASHRAE Standard 111-2008.FIG. 2 The Start of the Traverse of the 4 in. Rotating Vane An-emometer is Denoted by “X”FIG. 3 Cyclone FilterF2975 12 (2017)610.2.5.4 An accessible straight section of duct is requiredfor the traverse.10.

32、2.5.5 If the duct is insulated, the insulation shall beremoved to expose the exterior surface of the duct to allowholes to be drilled at the appropriate locations.10.2.5.6 Conduct the velocity measurements according toANSI/ASHRAE Standard 111-2008.10.2.5.7 Repeat the velocity measurements twice more

33、 fortriplicate readings.10.2.5.8 Upon completion of all duct velocitymeasurements, seal the holes used for the traverse measure-ments (weld liquid-tight or install UL Listed fittings).10.2.5.9 If the duct is insulated, any insulation removedshall be replaced and resealed.10.3 Exhaust Airflow Rate Ad

34、justments:10.3.1 All kitchen exhaust air flow rates shall be within 65% of the specified value. If an initial value falls below5%ofthe specified value, the air flow rate shall be adjusted to fallwithin5%ofthespecification.10.3.2 Raise or lower the exhaust fan speed to achieve thespecified airflow ra

35、te.10.3.2.1 To adjust the fan speed for belt-driven fans, shutthe fan off, loosen the tension on the belt and remove it. Loosenthe set screw on the adjustable motor pulley and screw the twohalves toward each other to increase speed, and screw themaway from each other to reduce speed. Be sure to tigh

36、ten theset screw only on a flat on the pulley hub to avoid damaging thethreads.10.3.3 Measure the exhaust airflow rate into the exhausthood using one of the procedures described in section 10.2.10.3.4 Continue to adjust the fan speed until the measuredair flow rate is within5%ofthespecified value.10

37、.3.5 Record the date, exhaust fan RPM setting measuredwith a tachometer, and the motor amp draw measured with aclamp-on ammeter at the correct exhaust flow rate, and use thisfor quick reference in the future (mark in indelible ink insideeach motor dome for future reference).10.3.6 After the final ex

38、haust fan RPM has been set, (1)check that the fan and motor shafts in parallel and if not, adjustthe motor or fan position by loosening and tightening themounting bolts to achieve parallel shaft alignment, and (2) setthe fan pulley and motor pulley on the same horizontal plane sothe belt rides flat.

39、10.3.7 Secure the motor dome to the fan, making sure thedome seals out water from the motor compartment.10.3.8 Repeat items 10.3.1 through 10.3.7 for all exhaustfans that require airflow rate adjustment.10.4 Proper Exhaust Fan Operation:10.4.1 The Venturi inlet of each fan shall seal completelyagain

40、st the gasket on the adapter plate.10.4.2 The fan shall rotate in the direction of the arrow onthe motor compartment plate.10.4.3 The fan shall turn freely without binding on theVenturi rim.10.4.4 The fan shaft bearings shall be properly lubricated.10.5 Supply and Makeup Air Flow Rate Measurements:1

41、0.5.1 Supply Air Flow Rate Measurement:10.5.1.1 The supply air volumetric flow rate through eachdiffuser shall be measured using a flow hood with the open endof the hood sealed to prevent air flow from escaping.10.5.1.2 Measurements shall be made with the internalbaffle open and closed and the resul

42、ts used to estimate the flowrate when the hood is not present.10.5.1.3 Measurements at each diffuser shall be made intriplicate and the average flow rate recorded.10.5.1.4 The total supply air flow rate into the kitchen shallbe the sum of the individual diffuser measurements.10.5.2 Makeup Air Flow R

43、ate Measurement:10.5.2.1 The total air flow rate through each makeup airdevice shall be determined using one of the following methodswith the cooking appliances idle/ready-to-cook.(1) When a specific air flow rate measurement protocol isspecified by the manufacturer, the protocol developed by theman

44、ufacturer shall be followed.FIG. 4 Measurement Positions for a 234-in. Rotating Vane Anemometer Indicated by “X” on a Cyclone Filter Bank With Two DifferentSized FiltersFIG. 5 Slot FilterF2975 12 (2017)7(2) When the makeup air device under test has no protocolfrom the manufacturer but has a protocol

45、 specified in thisdocument, the method of test specified in this document shallbe followed.(3) When the makeup air device under test has no protocolfrom the manufacturer and does not have a protocol specifiedin this document, or one or more obstructions prevents properuse of face velocity measuring

46、instruments, a duct traversemethod shall be used to determine the total air flow ratethrough the device using a Pitot-static tube. The Log-Tchebycheff rule shall be used for rectangular ducts and theLog-linear rule for circular ducts as specified in ANSI/ASHRAE Standard 111-2008, ”Measurement, testi

47、ng, adjust-ing and balancing of building HVAC systems”.10.5.2.2 Measurements at each device shall be made intriplicate and the average flow rate recorded for each.10.5.2.3 The total makeup air flow rate into the kitchen shallbe the sum of the individual makeup air device measurements.10.5.2.4 Front

48、Face With Perforated Plate Diffuser:(1) These measurements are limited to the use of a cali-brated flow hood mounted flush to the face of the diffuser or avelocity grid positioned 1.5 in. from the diffuser surface. Theflow hood shall be used except where obstructions prevent aproper seal along the e

49、ntire diffuser surface of a makeup airunit. If a flow hood cannot be used, a velocity grid shall be usedfor the makeup air unit.(2) Flow Hood:(a) When the opening of the flow hood is larger than thewidth of the diffuser preventing a tight seal on all sides, theopen area shall be blocked so that only air passing through thediffuser enters the flow hood. This can be accomplished byattaching a section of cardboard sealed to the end of the flowhood by tape.(b) The flow hood shall be mounted in a sufficient numberof positions over the perforated panel to measure all the airsuppli

展开阅读全文
相关资源
  • ANSI Z97 1-2009 American National Standard for Safety Glazing Materials used in Buildings - Safety Performance Specifications and Methods of Test《建筑物中窗用玻璃材料安全性用.pdfANSI Z97 1-2009 American National Standard for Safety Glazing Materials used in Buildings - Safety Performance Specifications and Methods of Test《建筑物中窗用玻璃材料安全性用.pdf
  • ANSI Z97 1 ERTA-2010 Re ANSI Z97 1 - 2009 Errata《修订版 美国国家标准学会Z97 1-2009标准的勘误表》.pdfANSI Z97 1 ERTA-2010 Re ANSI Z97 1 - 2009 Errata《修订版 美国国家标准学会Z97 1-2009标准的勘误表》.pdf
  • ANSI Z21 40 2a-1997 Gas-Fired Work Activated Air-Conditioning and Heat Pump Appliances (Same as CGA 2 92a)《燃气、工作激活空气调节和热泵器具(同 CGA 2 92a)》.pdfANSI Z21 40 2a-1997 Gas-Fired Work Activated Air-Conditioning and Heat Pump Appliances (Same as CGA 2 92a)《燃气、工作激活空气调节和热泵器具(同 CGA 2 92a)》.pdf
  • ANSI Z124 9-2004 American National Standard for Plastic Urinal Fixtures《塑料小便器用美国国家标准》.pdfANSI Z124 9-2004 American National Standard for Plastic Urinal Fixtures《塑料小便器用美国国家标准》.pdf
  • ANSI Z124 4-2006 American National Standard for Plastic Water Closet Bowls and Tanks《塑料抽水马桶和水箱用美国国家标准》.pdfANSI Z124 4-2006 American National Standard for Plastic Water Closet Bowls and Tanks《塑料抽水马桶和水箱用美国国家标准》.pdf
  • ANSI Z124 3-2005 American National Standard for Plastic Lavatories《塑料洗脸盆用美国国家标准》.pdfANSI Z124 3-2005 American National Standard for Plastic Lavatories《塑料洗脸盆用美国国家标准》.pdf
  • ANSI T1 659-1996 Telecommunications - Mobility Management Application Protocol (MMAP) RCF-RACF Operations《电信 可移动管理应用协议(MMAP) RCF-RACF操作》.pdfANSI T1 659-1996 Telecommunications - Mobility Management Application Protocol (MMAP) RCF-RACF Operations《电信 可移动管理应用协议(MMAP) RCF-RACF操作》.pdf
  • ANSI T1 651-1996 Telecommunications – Mobility Management Application Protocol (MMAP)《电信 可移动性管理应用协议》.pdfANSI T1 651-1996 Telecommunications – Mobility Management Application Protocol (MMAP)《电信 可移动性管理应用协议》.pdf
  • ANSI T1 609-1999 Interworking between the ISDN User-Network Interface Protocol and the Signalling System Number 7 ISDN User Part《电信 ISDN用户间网络接口协议和7号信令系统ISDN用户部分.pdfANSI T1 609-1999 Interworking between the ISDN User-Network Interface Protocol and the Signalling System Number 7 ISDN User Part《电信 ISDN用户间网络接口协议和7号信令系统ISDN用户部分.pdf
  • ANSI T1 605-1991 Integrated Services Digital Network (ISDN) - Basic Access Interface for S and T Reference Points (Layer 1 Specification)《综合服务数字网络(ISDN) S和T基准点的.pdfANSI T1 605-1991 Integrated Services Digital Network (ISDN) - Basic Access Interface for S and T Reference Points (Layer 1 Specification)《综合服务数字网络(ISDN) S和T基准点的.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > ANSI

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1