ANSI ISA 61241-2-2006 Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization pD (12.10.06).pdf

上传人:李朗 文档编号:436931 上传时间:2018-11-14 格式:PDF 页数:38 大小:572.95KB
下载 相关 举报
ANSI ISA 61241-2-2006 Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization pD (12.10.06).pdf_第1页
第1页 / 共38页
ANSI ISA 61241-2-2006 Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization pD (12.10.06).pdf_第2页
第2页 / 共38页
ANSI ISA 61241-2-2006 Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization pD (12.10.06).pdf_第3页
第3页 / 共38页
ANSI ISA 61241-2-2006 Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization pD (12.10.06).pdf_第4页
第4页 / 共38页
ANSI ISA 61241-2-2006 Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization pD (12.10.06).pdf_第5页
第5页 / 共38页
亲,该文档总共38页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、 AMERICAN NATIONAL STANDARD ISA-61241-2 (12.10.06)-2006 (R2015) Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization “pD” Reaffirmed 29 September 2015 ANSI/ISA-61241-2 (12.10.06)-2006 (R2015) Electrical Apparatus for Use in Zone 21 and Zon

2、e 22 Hazardous (Classified) Locations Protection by Pressurization “pD” ISBN: 978-1-941546-39-0 Copyright 2015 by ISA. All rights reserved. Not for resale. Printed in the United States of America. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form

3、 or by any means (electronic mechanical, photocopying, recording, or otherwise), without the prior written permission of the Publisher. ISA 67 Alexander Drive P.O. Box 12277 Research Triangle Park, North Carolina 27709 - 3 - ANSI/ISA-61241-2 (12.10.06)-2006 (R2015) Preface This preface, as well as a

4、ll footnotes and annexes, is included for information purposes and is not part of ANSI/ISA-61241-2 (12.10.06)-2006 (R2015). This document has been prepared as part of the service of ISA towards a goal of uniformity in the field of instrumentation. To be of real value, this document should not be sta

5、tic but should be subject to periodic review. Toward this end, the Society welcomes all comments and criticisms and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549-8411; Fax (

6、919) 549-8288; E-mail: standardsisa.org. The ISA Standards and Practices Department is aware of the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. The Department is furthe

7、r aware of the benefits to USA users of ISA standards of incorporating suitable references to the SI (and the metric system) in their business and professional dealings with other countries. Toward this end, this Department will endeavor to introduce SI-acceptable metric units in all new and revised

8、 standards, recommended practices, and technical reports to the greatest extent possible. Standard for Use of the International System of Units (SI): The Modern Metric System, published by the American Society for Testing b) the maximum surface temperatures of internal parts that are protected by a

9、type of protection in accordance with IEC 61241-1-2.ANSI/ISA-61241-0 and which remain energized when the supply of protective gas for pressurization is removed or fails, for example electric heaters. If, during normal service, the temperatures of internal surfaces which may be exposed to an explosiv

10、e dust atmosphere exceed the maximum values permitted in IEC 61241-1-1 ANSI/ISA-61241-0, for the temperature class of the equipment, appropriate measures shall be taken to ensure that, if pressurization ceases, any explosive dust atmosphere which may exist is ANSI/ISA-61241-2 (12.10.06)-2006 (R2015)

11、 - 20 - prevented from making contact with that surface before it has cooled below the permitted maximum value. This may be achieved either by design and construction of the joints of the pressurized enclosure and ducts by other means, for example, by bringing alternative (or auxiliary) sources of p

12、rotective gas into operation, or by arranging that the hot surface within the enclosure is in a dust-tight or encapsulated housing. When determining the temperature for rotating electrical machines, the duty type according to IEC 60034-1 as specified by the manufacturer shall also be considered. 7 S

13、afety provisions and safety devices (except for static pressurization) 7.1 General Protective measures shall be adopted to prevent the electrical apparatus installed in a pressurized enclosure from being energized before pressurization is established. All safety devices shall either be a) protected

14、by an appropriate type of explosion-protection in accordance with IEC 61241-1-2 ANSI/ISA-61241-0, or b) non-electrical and not capable of causing ignition, or c) located in a non-hazardous area. The safety devices required by this standard form safety-related parts of a control system. It is the res

15、ponsibility of the manufacturer and the user to assess that the safety and integrity of the control system is appropriate. The safety devices shall be provided by the manufacturer of the apparatus or by the user. In the latter case, the apparatus shall be marked “X“ in accordance with 29.2 of ANSI/I

16、SA-61241-0 and the description documents shall contain all the necessary information required by the user to ensure conformity with the requirements of the standard. The enclosure shall be cleaned before the electrical supply to the system is connected or restored in order to remove any accumulated

17、combustible dust left in the enclosure, either accidentally following failure of the pressurization system, or following normal shutdown. Th e manufacturer shall provide the necessary instructions to the user detailing the requirements for cleaning the enclosure. The manufacturer shall specify the m

18、aximum and minimum action levels and tolerances of the safety devices. The safety devices shall be used within the normal operational limits as specified by the manufacturer taking due account of the most onerous conditions specified for normal service. 7.2 Pressure- or flow-activated devices Pressu

19、re-activated devices provided for the operation of alarm and electrical trip devices shall operate when the pressure within the enclosure falls below the permitted minimum value or exceeds the permitted maximum pressure. Flow-monitoring devices provided for the operation of alarm and electrical trip

20、 devices shall operate when the pressure within the enclosure falls below the permitted minimum value, or exceeds the permitted maximum pressure, and shall be located at the outlet. - 21 - ANSI/ISA-61241-2 (12.10.06)-2006 (R2015) An electrical interlock on the fan motors or controls is not suitable

21、to indicate failure of pressurization. It does not give an indication in the event of the fan belt slipping, the fan becoming loose on the shaft or reverse rotation of the fan. 7.3 Electrical supply Where protection is not provided to prevent the ingress of dust following the shutdown or failure of

22、the pressurization system, a warning label shall be fixed stating that dust shall be removed from the interior prior to switching on the electrical supply. 7.4 Switching off electrical supply When required by this standard, the switching-off of the electrical supply shall require the isolation of al

23、l live conductors, including the neutral, in accordance with IEC 61241-1-2ANSI/ISA-61241-0. 7.5 Failure of pressurization The design of a pressurization system relies on the principle that a failure of the pressurization automatically disconnects the system from the electricity supply and/or initiat

24、es alarms. To guard against the possibility that electrical apparatus protected by pressurization may cause an explosion in the case of the protective gas supply failure, the following measures shall be incorporated. They take into account the characteristics of the apparatus, prevailing environ -me

25、ntal conditions, and the use of devices for monitoring and warning purposes. 7.5.1 Protection requirements Requirements applicable to apparatus protected by pressurization vary according to the level of hazard, being dependent on the type of apparatus used, and the classification of the area, and sp

26、ecific installation and process requirements. These factors require either switching off the electrical supply and giving an alarm, or giving an alarm only. Whatever protective measures are adopted, the following provisions shall also be made. a) All electrical apparatus which is to be energized in

27、the absence of pressurization shall be suitable for use in the explosive dust atmosphere corresponding to its position. b) Visible or audible alarms shall be located where they will immediately be seen or heard by the responsible personnel who will take the necessary action. c) Either a pressure-mon

28、itoring device, flow-monitoring device, or both, shall be used to monitor the satisfactory functioning of the pressurization. ANSI/ISA-61241-2 (12.10.06)-2006 (R2015) - 22 - Table 1 Requirements on failure of pressurization Type of apparatus in the enclosure Area classification Ignition-capable appa

29、ratus Apparatus with no sources of ignition in normal operation Zone 20 Not applicable a Not applicable a Zone 21 7.5.1.1 7.5.1.2 Zone 22 7.5.1.2 Internal pressurization not required a Requirements for ALL apparatus for use in zone 20 have not yet been finalized. 7.5.1.1 Switching off electrical sup

30、ply The following requirements apply. a) An automatic device shall be provided to switch off all electrical supplies to the equipment protected by the apparatus, unless it is protected by one or more of the concepts described in the IEC ISA-61241 series, and initiates an audible and/or visible alarm

31、 when the overpressure and/or protective gas flow fall below the minimum prescribed value. In special cases, when the apparatus is intended for use in an installation where the switching-off may jeopardize the safety of the installation or persons, this requirement may be rearranged to provide a con

32、tinuous audible or visible alarm until pressurization is restored or other appropriate measures are taken. b) Doors and covers, which can be opened without the use of a tool, shall be interlocked so that, on opening any door or cover, the electrical supplies are switched off from all parts not prote

33、cted by one or more of the concepts of the IEC ISA-61241 series. This includes all phases and the neutral if available. The supply must be prevented from being switched on again until all doors and covers have been re-closed. c) A warning shall be prominently mounted on the apparatus stating the fol

34、lowing or equivalent: WARNING: REMOVE ALL DUST FROM THIS ENCLOSURE BEFORE CONNECTING OR RESTORING THE ELECTRICAL SUPPLY 7.5.1.2 Alarm only The following requirements apply. a) An automatic device shall be provided to either audibly and/or visibly warn the operator when the overpressure and/or protec

35、tive gas flow fall below the minimum prescribed value to enable him to take appropriate measures. b) All doors and covers which can be opened without the use of a tool shall be marked carry the following warning: WARNING: DO NOT OPEN WHILE ENERGIZED UNLESS IT IS OBVIOUS THAT NO COMBUSTIBLE DUST IS P

36、RESENT c) A warning shall be prominently mounted on the apparatus stating the following or equivalent: WARNING: REMOVE ALL DUST FROM THE INSIDE OF THE ENCLOSURE BEFORE CONNECTING OR RESTORING THE ELECTRICAL SUPPLY - 23 - ANSI/ISA-61241-2 (12.10.06)-2006 (R2015) 7.6 Level of overpressure A minimum ov

37、erpressure of 50 Pa (0,5 mbar) shall be maintained relative to the external atmosphere at every point within the enclosure and its associated ducts where leakage can occur. Examples of the distribution of pressure in different systems of enclosures and ducts are illustrated in figures A.1 and A.2. N

38、OTE Rotating machines should be of the enclosed type. Consideration should be given in the application of pressurized apparatus having an internally enclosed cooling circuit in which circulation is assisted by an internal fan, since the effect of such fans may be to produce a negative pressure in pa

39、rts of the casing with consequent risk of ingress of dust if pressurization ceases (see figure A.2). 7.7 Possible sources of ignition When the protected apparatus incorporates components such as batteries, which remain sources of ignition, suitable precautions shall be taken in the design of the app

40、aratus to prevent the accidental production of sparks, by ensuring that these components are designed with a type of protection appropriate to the characteristics of the prevailing external and internal atmospheres. Such components shall be clearly identified. 7.8 Enclosed components Any components

41、inside the enclosure which remain in operation in the absence of the protective gas, for example devices for heating the equipment when it is not in operation, shall be protected by one of the types of protection for electrical equipment in combustible dust atmospheres in accordance with IEC 61241-1

42、-2ANSI/ISA-61241-0, with the type of protection suitable for the particular hazardous area. 7.9 Separate enclosures Where the apparatus is intended to form part of a multi-enclosure installation with a common protective gas supply, the resulting design shall take into account the most unfavourable c

43、onditions of the whole installation. If the protective safety devices are intended to be common, the opening of a door or cover need not necessarily switch off the whole electrical supply or initiate the alarm provided that a) the opening of a door or cover is preceded by switching off the supplies

44、to the apparatus located in that particular enclosure that is not protected by a suitable concept of dust ignition protection, or the door is interlocked with the supplies to achieve the same end; and b) the common protective safety device continues to monitor the rest of the installation. 8 Safety

45、provisions and safety devices for static pressurization Additional requirements for static pressurization. The pressurized enclosure shall be filled with an inert gas in a non-hazardous area using the procedure specified by the manufacturer. Automatic device(s) shall be provided to operate when the

46、overpressure falls below the minimum value specified by the manufacturer. It shall be possible to check the correct operation ANSI/ISA-61241-2 (12.10.06)-2006 (R2015) - 24 - of the device(s) when the apparatus is in service. The automatic device(s) shall only be capable of being reset by the use of

47、a tool or a key. NOTE 1 The purpose for which the automatic device(s) is (are) used (i.e. to disconnect power or to sound an alarm or otherwise ensure the safety of the installation) is the responsibility of the user. The minimum level of overpressure shall be greater than the maximum pressure loss

48、in normal service, measured over a period not less than 100 times the time necessary for the cooling of the enclosed components below the maximum permissible surface temperature for the dust concerned, with a minimum of 1 h. The minimum level of overpressure shall not be less than 50 Pa above the ex

49、ternal pressure under the most onerous conditions specified for normal service. NOTE 2 If the overpressure falls below the minimum specified, it is the users responsibility to ensure that the pressurized enclosure is removed to a non-hazardous area before refilling. 9 Supply of protective gas 9.1 Type of gas A protective gas shall be used for maintaining pressurization in the enclosure. The gas shall be non-flammable and shall not, by reason of its chemical characteristics or the impurities that it may contain, reduce the level of protection below that sought, or affect the sa

展开阅读全文
相关资源
  • ANSI Z97 1-2009 American National Standard for Safety Glazing Materials used in Buildings - Safety Performance Specifications and Methods of Test《建筑物中窗用玻璃材料安全性用.pdfANSI Z97 1-2009 American National Standard for Safety Glazing Materials used in Buildings - Safety Performance Specifications and Methods of Test《建筑物中窗用玻璃材料安全性用.pdf
  • ANSI Z97 1 ERTA-2010 Re ANSI Z97 1 - 2009 Errata《修订版 美国国家标准学会Z97 1-2009标准的勘误表》.pdfANSI Z97 1 ERTA-2010 Re ANSI Z97 1 - 2009 Errata《修订版 美国国家标准学会Z97 1-2009标准的勘误表》.pdf
  • ANSI Z21 40 2a-1997 Gas-Fired Work Activated Air-Conditioning and Heat Pump Appliances (Same as CGA 2 92a)《燃气、工作激活空气调节和热泵器具(同 CGA 2 92a)》.pdfANSI Z21 40 2a-1997 Gas-Fired Work Activated Air-Conditioning and Heat Pump Appliances (Same as CGA 2 92a)《燃气、工作激活空气调节和热泵器具(同 CGA 2 92a)》.pdf
  • ANSI Z124 9-2004 American National Standard for Plastic Urinal Fixtures《塑料小便器用美国国家标准》.pdfANSI Z124 9-2004 American National Standard for Plastic Urinal Fixtures《塑料小便器用美国国家标准》.pdf
  • ANSI Z124 4-2006 American National Standard for Plastic Water Closet Bowls and Tanks《塑料抽水马桶和水箱用美国国家标准》.pdfANSI Z124 4-2006 American National Standard for Plastic Water Closet Bowls and Tanks《塑料抽水马桶和水箱用美国国家标准》.pdf
  • ANSI Z124 3-2005 American National Standard for Plastic Lavatories《塑料洗脸盆用美国国家标准》.pdfANSI Z124 3-2005 American National Standard for Plastic Lavatories《塑料洗脸盆用美国国家标准》.pdf
  • ANSI T1 659-1996 Telecommunications - Mobility Management Application Protocol (MMAP) RCF-RACF Operations《电信 可移动管理应用协议(MMAP) RCF-RACF操作》.pdfANSI T1 659-1996 Telecommunications - Mobility Management Application Protocol (MMAP) RCF-RACF Operations《电信 可移动管理应用协议(MMAP) RCF-RACF操作》.pdf
  • ANSI T1 651-1996 Telecommunications – Mobility Management Application Protocol (MMAP)《电信 可移动性管理应用协议》.pdfANSI T1 651-1996 Telecommunications – Mobility Management Application Protocol (MMAP)《电信 可移动性管理应用协议》.pdf
  • ANSI T1 609-1999 Interworking between the ISDN User-Network Interface Protocol and the Signalling System Number 7 ISDN User Part《电信 ISDN用户间网络接口协议和7号信令系统ISDN用户部分.pdfANSI T1 609-1999 Interworking between the ISDN User-Network Interface Protocol and the Signalling System Number 7 ISDN User Part《电信 ISDN用户间网络接口协议和7号信令系统ISDN用户部分.pdf
  • ANSI T1 605-1991 Integrated Services Digital Network (ISDN) - Basic Access Interface for S and T Reference Points (Layer 1 Specification)《综合服务数字网络(ISDN) S和T基准点的.pdfANSI T1 605-1991 Integrated Services Digital Network (ISDN) - Basic Access Interface for S and T Reference Points (Layer 1 Specification)《综合服务数字网络(ISDN) S和T基准点的.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > ANSI

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1