AS NZS 1851 16-1997 Maintenance of fire protection equipment - Pyrogen fire extinguishing aerosol systems《消防系统和设备的维修 热源灭火气雾剂设备》.pdf

上传人:arrownail386 文档编号:449964 上传时间:2018-11-18 格式:PDF 页数:15 大小:118.58KB
下载 相关 举报
AS NZS 1851 16-1997 Maintenance of fire protection equipment - Pyrogen fire extinguishing aerosol systems《消防系统和设备的维修 热源灭火气雾剂设备》.pdf_第1页
第1页 / 共15页
AS NZS 1851 16-1997 Maintenance of fire protection equipment - Pyrogen fire extinguishing aerosol systems《消防系统和设备的维修 热源灭火气雾剂设备》.pdf_第2页
第2页 / 共15页
AS NZS 1851 16-1997 Maintenance of fire protection equipment - Pyrogen fire extinguishing aerosol systems《消防系统和设备的维修 热源灭火气雾剂设备》.pdf_第3页
第3页 / 共15页
AS NZS 1851 16-1997 Maintenance of fire protection equipment - Pyrogen fire extinguishing aerosol systems《消防系统和设备的维修 热源灭火气雾剂设备》.pdf_第4页
第4页 / 共15页
AS NZS 1851 16-1997 Maintenance of fire protection equipment - Pyrogen fire extinguishing aerosol systems《消防系统和设备的维修 热源灭火气雾剂设备》.pdf_第5页
第5页 / 共15页
亲,该文档总共15页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、AS/NZS 1851.16:1997Australian/New Zealand StandardMaintenance of fire protectionequipmentPart 16: Pyrogen fire extinguishingaerosol systemsAccessed by ISONET - CHINA STATE BUREAU OF TECHNICAL SUPERVIS on 28 Feb 2006 AVAILABLE SUPERSEDEDAS/NZS 1851.16:1997This Joint Australian/New Zealand Standard wa

2、s prepared by Joint TechnicalCommittee FP/11, Fire Extinguishing Systems. It was approved on behalf of theCouncil of Standards Australia on 25 July 1997 and on behalf of the Council ofStandards New Zealand on 11 July 1997. It was published on 5 September 1997.The following interests are represented

3、on Committee FP/11:Australian Chamber of Commerce and IndustryFire Protection Association, AustraliaCommonwealth Fire Board, AustraliaDepartment of Defence, AustraliaFire Trainers Association of AustraliaInstitute of Security ExecutivesNew Zealand Fire Equipment AssociationNew Zealand Fire Protectio

4、n AssociationScientific Services Laboratory AGAL, Department of Administrative ServicesSociety of Fire Protection Engineers, Australasian ChapterStandards New ZealandTelstra CorporationWaterways Authority (N.S.W.)Review of Standards. To keep abreast of progress in industry, Joint Australian/New Zeal

5、and Standards are subject to periodic review and are kept up to date by the issueof amendments or new editions as necessary. It is important therefore that Standards usersensure that they are in possession of the latest edition, and any amendments thereto.Full details of all Joint Standards and rela

6、ted publications will be found in the StandardsAustralia and Standards New Zealand Catalogue of Publications; this information issupplemented each month by the magazines The Australian Standard and StandardsNew Zealand, which subscribing members receive, and which give details of newpublications, ne

7、w editions and amendments, and of withdrawn Standards.Suggestions for improvements to Joint Standards, addressed to the head office of eitherStandards Australia or Standards New Zealand, are welcomed. Notification of anyinaccuracy or ambiguity found in a Joint Australian/New Zealand Standard should

8、be madewithout delay in order that the matter may be investigated and appropriate action taken.This Standard was issued in draft form for comment as DR 96347.Accessed by ISONET - CHINA STATE BUREAU OF TECHNICAL SUPERVIS on 28 Feb 2006 AVAILABLE SUPERSEDEDAS/NZS 1851.16:1997Australian/New Zealand Sta

9、ndardMaintenance of fire protectionequipmentPart 16: Pyrogen fire extinguishingaerosol systemsFirst published as AS/NZS 1851.16:1997.PUBLISHED JOINTLY BY:STANDARDS AUSTRALIA1 The Crescent,Homebush NSW 2140 AustraliaSTANDARDS NEW ZEALANDLevel 10, Radio New Zealand House,155 The Terrace,Wellington 600

10、1 New ZealandISBN 0 7337 1362 9Accessed by ISONET - CHINA STATE BUREAU OF TECHNICAL SUPERVIS on 28 Feb 2006 AVAILABLE SUPERSEDEDAS/NZS 1851.16:1997 2PREFACEThis Standard was prepared by the Joint Standards Australia/Standards New ZealandCommittee FP/11 on Fire Extinguishing Systems to provide suitab

11、le requirements for theregular maintenance of Pyrogen fire extinguishing aerosol systems.The objective of this Standard is to provide users of Pyrogen fire extinguishing aerosolsystems with the necessary requirements needed in the regular maintenance of suchsystems.Pyrogen fire extinguishing aerosol

12、 systems may incorporate control and indicatingequipment (CIE) that complies with AS 1603.4, Automatic fire detection and alarmsystems,Part4:Control and indicating equipment, and is installed in accordance withAS 1670, Automatic fire detection and alarm systems System design, installation, andcommis

13、sioning. The maintenance provisions of this Standard therefore overlap those forcontrol and indicating equipment contained in AS 1851.8, Maintenance of fire protectionequipment, Part 8: Automatic fire detection and alarm systems. Where the CIE for asystem forms part of a fire indicator panel (FIP) s

14、erving other zones as well as theprotected enclosure, then maintenance in accordance with AS 1851.8 and this Standardcan be undertaken simultaneously without the need for duplication.This Standard has some variance in text from its sister document, AS 1851.8, due to thechange in the document style p

15、rocedures of Standards Australia.The term informative has been used in this Standard to define the application of theappendix to which it applies. An informative appendix is only for information andguidance. Copyright STANDARDS AUSTRALIA/ STANDARDS NEW ZEALANDUsers of Standards are reminded that cop

16、yright subsists in all Standards Australia and Standards New Zealand publications and software.Except where the Copyright Act allows and except where provided for below no publications or software produced byStandards Australia or Standards New Zealand may be reproduced, stored in a retrieval system

17、 in any form or transmitted by any meanswithout prior permission in writing from Standards Australia or Standards New Zealand. Permission may be conditional on anappropriate royalty payment. Australian requests for permission and information on commercial software royalties should be directed tothe

18、head office of Standards Australia. New Zealand requests should be directed to Standards New Zealand.Up to 10 percent of the technical content pages of a Standard may be copied for use exclusively in-house by purchasers of theStandard without payment of a royalty or advice to Standards Australia or

19、Standards New Zealand.Inclusion of copyright material in computer software programs is also permitted without royalty payment provided such programsare used exclusively in-house by the creators of the programs.Care should be taken to ensure that material used is from the current edition of the Stand

20、ard and that it is updated whenever the Standardis amended or revised. The number and date of the Standard should therefore be clearly identified.The use of material in print form or in computer software programs to be used commercially, with or without payment, or in commercialcontracts is subject

21、to the payment of a royalty. This policy may be varied by Standards Australia or Standards New Zealand at any time.Accessed by ISONET - CHINA STATE BUREAU OF TECHNICAL SUPERVIS on 28 Feb 2006 AVAILABLE SUPERSEDED3 AS/NZS 1851.16:1997CONTENTSPageSECTION 1 SCOPE AND GENERAL1.1 SCOPE . 41.2 REFERENCEDD

22、OCUMENTS 41.3 DEFINITIONS 4SECTION 2 GENERAL REQUIREMENTS2.1 MAINTENANCE 52.2 RECORDS 52.3 PRECAUTIONS. 5SECTION 3 MAINTENANCE PROCEDURES3.1 WEEKLY . 63.2 MONTHLY 63.3 YEARLY . 7SECTION 4 MAINTENANCE DOCUMENTATION4.1 GENERAL 94.2 RECORDSYSTEM 9APPENDIX A SYSTEMLOGBOOKREPORT 10Accessed by ISONET - CH

23、INA STATE BUREAU OF TECHNICAL SUPERVIS on 28 Feb 2006 AVAILABLE SUPERSEDEDAS/NZS 1851.16:1997 4STANDARDS AUSTRALIA/STANDARDS NEW ZEALANDAustralian/New Zealand StandardMaintenance of fire protection equipmentPart 16: Pyrogen fire extinguishing aerosol systemsSECTION 1 SCOPE AND GENERAL1.1 SCOPE This

24、Standard sets out requirements for the regular maintenance of fireextinguishing systems utilizing SOYUZ pyrogenically generated fire extinguishingaerosols, designed and installed in accordance with AS/NZS 4487. Regular maintenanceincludes inspection and testing.The Pyrogen fire extinguishing aerosol

25、 shall be referred to as the extinguishant in thisStandard.NOTE: A Pyrogen fire extinguishing aerosol system is generally referred to in this Standard asa Pyrogen system or the Pyrogen system.1.2 REFERENCED DOCUMENTS The following documents are referred to in thisStandard:AS1603 Automatic fire detec

26、tion and alarm systems1603.4 Part 4: Control and indicating equipment1670 Automatic fire detection and alarm systems System design, installation, andcommissioning1851 Maintenance of fire protection equipment1851.8 Part 8: Automatic fire detection and alarm systems2484 Fire Glossary of terms2484.2 Pa

27、rt 2: Fire protection and firefighting equipmentAS/NZS4487 Pyrogen fire extinguishing aerosol systems1.3 DEFINITIONS For the purpose of this Standard, the definitions given inAS 1603.4, AS 1670, AS 2484.2 and AS/NZS 4487 apply.COPYRIGHTAccessed by ISONET - CHINA STATE BUREAU OF TECHNICAL SUPERVIS on

28、 28 Feb 2006 AVAILABLE SUPERSEDED5 AS/NZS 1851.16:1997SECTION 2 GENERAL REQUIREMENTS2.1 MAINTENANCE It is essential that regular maintenance of Pyrogen systems isundertaken to ensure an operational condition and to prevent inadvertent discharge.NOTE: Maintenance shall be carried out only by persons

29、having qualifications and experiencesuitable for the particular work in which they are engaged.Calibrated test equipment and recognized procedures shall be used.Regular maintenance is classified into three levels which shall be performed as follows:(a) Weekly, only where the appropriate authority de

30、ems it necessary.(b) Monthly on all systems.(c) Yearly on all systems.NOTES:1 The manufacturer may have additional requirements beyond that specified in this Standard.2 The arrangements for maintenance should ensure that a person is available on call at alltimes to provide service in the event of an

31、y fault developing at the installation.2.2 RECORDS All system attendances, e.g. inspection, testing, service andmaintenance procedures shall be systematically recorded by date with signed entries in thelogbook maintained on the site (see Clause 4.2). In addition, a copy of all attendancerecords shou

32、ld be forwarded to the owner or the owners agent. The property owner oroccupier shall maintain a record of maintenance carried out on the Pyrogen systems. Themaintenance record system shall contain the classification (weekly, monthly or yearly)and date of maintenance, any defects and any consequent

33、remedial action or advice givenby the service person, with any additional action taken by the service person.The maintenance record system shall be available at all times.NOTE: The maintenance record system may be in the form of a logbook or a computer-basedrecord system, or other appropriate perman

34、ent record system.2.3 PRECAUTIONS Prior to commencing any inspection, testing or maintenanceprocedures, the service person shall carry out the following precautionary procedures asapplicable:(a) Inform the building owner or agent that maintenance is to be carried out.(b) Advise the fire control stat

35、ion, where testing will transmit a fire alarm signal.(c) Engage the system isolate switch, and in addition, ensure that all extinguishantactuating circuits are isolated to ensure that testing or other maintenance procedurescannot cause discharge of any extinguishant.(d) Set the detection and alarm s

36、ystem in the appropriate test mode and ensure thatancillary facilities, systems and air-handling plant (including smoke exhaust andstairwell pressurization systems, evacuation warning systems, and the like), wherethey are not to be tested, are isolated to avoid inadvertent operation.(e) On completio

37、n of any inspection, testing or maintenance procedure, the serviceperson shall ensure that all controls are returned to the normal condition and re-establish the systems integrity.NOTE: The action to be taken when any function is isolated should be covered by themaintenance contract. It is recommend

38、ed that when any section of an installation is to beisolated, the owner or agent should be notified and in turn should advise the appropriateauthority.COPYRIGHTAccessed by ISONET - CHINA STATE BUREAU OF TECHNICAL SUPERVIS on 28 Feb 2006 AVAILABLE SUPERSEDEDAS/NZS 1851.16:1997 6SECTION 3 MAINTENANCE

39、PROCEDURES3.1 WEEKLY Where required, the weekly maintenance procedure shall be performedas follows:(a) Activate system isolate switch and isolate ancillaries in accordance with Clause 2.3.(b) Check the proper operation of associated visual alarm indicators by initiating asimulated fire alarm on an a

40、larm zone facility.The above test shall be carried out in a manner acceptable to the fire control station.(c) Check the satisfactory operation of the fire alarm bell.(d) Reset alarm zone facility.(e) On completion of testing, re-establish the systems integrity, ensure that all controlsare returned t

41、o the normal condition.(f) Record the results of weekly maintenance procedures in the log, including wherepossible, whether the fire alarm signal from the alarm zone facility was received atthe fire control station (see Clause 4.2).(g) Ensure that all switches are in the correct operating position.

42、Inform the buildingowner or agent of any items requiring corrective action.3.2 MONTHLY The monthly maintenance procedure shall be performed as follows:(a) Activate system isolate switch and isolate ancillaries in accordance with Clause 2.3.(b) Initiate a simulated fire alarm on an alarm zone facilit

43、y so as to transmit an alarm tothe fire control station. Check the proper operation of all associated visual alarmindicators. Where possible check that the alarm was correctly received at the firecontrol station.The above test shall be carried out in a manner acceptable to the fire control station.(

44、c) Check the satisfactory operation of the fire alarm bell.(d) Reset alarm zone facility to normal.(e) Test each alarm zone facility to confirm its ability to operate the master alarmfacility.(f) Check that all visual and audible indicators are operating correctly.(g) Check that all control and indi

45、cating equipment is in a clean and operationalcondition, and effectively dust sealed.(h) Ensure that all fire indicator panels, extinguishant local control stations (LCS),repeater panels and mimic panels are clearly visible and readily accessible (seeAS 1670).(i) Simulate fault conditions on all ala

46、rm zones to ensure that fault indicators, bothaudible and visual, where applicable, are operating correctly from each alarm zonefacility.(j) Check the battery condition by operating the battery test facility for 1 min, andrecord the battery condition in the log.(k) Inspect all extinguishant generato

47、rs, manual mechanical release mechanisms and allother ancillary equipment to ensure they are secure, undamaged and unobstructed.(l) Check the function of all extinguishant manual initiate switches and theextinguishant inhibit switch on each LCS.COPYRIGHTAccessed by ISONET - CHINA STATE BUREAU OF TEC

48、HNICAL SUPERVIS on 28 Feb 2006 AVAILABLE SUPERSEDED7 AS/NZS 1851.16:1997(m) Ensure that all discharge nozzles are not obstructed and are correctly aligned. Carryout a visual inspection on all support and mechanical controls.(n) Ensure that all visual warning devices as required, are correctly displa

49、yed andunobstructed and that all controls, switches and the like are properly identified.(o) Check the operation of all audible alarms and visual warning devices.(p) On completion of testing, re-establish the systems integrity, ensuring that allcontrols are returned to the normal condition.(q) Record the results of monthly maintenance procedures in the log, including all itemsrequiring corrective action, adjustment and the like (see Clause 4.2).(r) Check that items previously recorded as requiring attention have been attended to,or record the reasons why