1、135-2016 Errata October 25, 2016 2016 ASHRAE. All rights reserved 1BACnet Errata ANSI/ASHRAE STANDARD 135-2016 A Data Communication Protocol for Building Automation and Control Networks October 25, 2016 This document lists all known errata to ANSI/ASHRAE Standard 135-2016 as of the above date. Each
2、entry is cited first by clause, then page number, except where an erratum covers more than one clause. The back page marking identifying the electronic publication of Standard 135-2016 is “Product code: D-86451 6/16”. Changes are indicated by using strikeout for text to be removed and italics for te
3、xt to be added, unless noted otherwise. 1) Clause 4.1, p. 12: The list of standard datalink layer options for BACnet is misformatted. Ethernet (ISO 8802-3) Clause 7 ARCNET (ATA 878.1) Clause 8 MS/TP Cause9P l 10 LonTalk (ISO/IEC 14908.1) Clause 11 BACnet/IP Annex J BACnet/IPv6 Annex U ZigBee Annex O
4、 ZigBee Annex O 2) Table 13-7, p. 602: UNSIGNED RANGE is misplaced outside the table. The reference to Clause 13.3.9 is not shown. Table 13-7. Standardized Event Algorithms Event Algorithm Clause NONE 13.3.17. .UNSIGNED_OUT_OF_RANGE 13.3.15 UNSIGNED_RANGE 13.3.9UNSIGNED_RANGE 3) Clause K.2.16, 2nd,
5、p. 1055: Repeated word “the“. K.2.16 BIBB - Alarm and Event Management-View and Modify-A (AE-VM-A) Device A displays and modifies limits and related parameters in standard event-initiating objects. Device A shall support DS-RP-A and DS-WP-A. The A device shall be capable of using ReadProperty to ret
6、rieve and WriteProperty to modify any of the the event and fault algorithm parameters listed in Tables K-11 and K-12. Such parameters may be present in individual properties, in event parameter properties, or in fault parameter properties. See the respective property specifications. Device A may use
7、 alternate services where support for execution of the alternate service is supported by Device B. . 135-2016 Errata October 25, 2016 2016 ASHRAE. All rights reserved 24) Clause K.2.16, 3rd, p. 1055: The word “writing“ is missing. . Devices claiming conformance to AE-VM-A shall be capable of reading
8、, presenting and writing all standard properties in standard objects that are configuration parameters of standard event and/or fault algorithms that have high and low numerical limits, as listed in Tables K-11 and K-12. 5) Clause K.1.25 and K.1.26, p. 1055: The word “Multiple“ is misspelled in the
9、title. K.1.25 BIBB - Data Sharing-Change Of Value Mulitple Multiple-A (DS-COVM-A) K.1.26 BIBB - Data Sharing-Change Of Value Mulitple Multiple-B (DS-COVM-B) 6) Clause L.1, 1st, p. 1079: The second sentence is unclear. L.1 Operator Interface Profiles The following table indicates which BIBBs shall be
10、 supported by the device types of this family, for each interoperability area. The B-XAWS is excluded from this table. The B-XAWS is not shown in this table and is described in Clause L.1.1. . 7) Table 12-71, p. 518, Clause 12.56.32, p. 533, Clause J.4.3.2, p. 1028, and Clause J.4.5, 2nd, p. 1029: T
11、he references to J.7.8 are incorrect. Table 12-71. Properties of the Network Port Object Type Property Identifier Property Datatype Conformance Code Object_Identifier BACnetObjectIdentifier R. . .Profile_Name CharacterString O1 . . 9 Required to be present if the Network_Type is IPV4, Protocol_Level
12、 is BACNET_APPLICATION, and the device is capable of communicating through a NAT router as described in Clause J.7.8 J.7.5. 10 Required if Network_Type is IPV4, Protocol_Level is BACNET_APPLICATION, and the device is configured to communicate through a NAT router as described in Clause J.7.8 J.7.5.
13、. 12.56.32 BACnet_IP_NAT_Traversal This property, of type BOOLEAN, indicates whether (TRUE) or not (FALSE) this port is configured to operate in a NAT environment, as described in Clause J.7.8 J.7.5, and the global address is indicated by the value of the BACnet_IP_Global_Address property. . 135-201
14、6 Errata October 25, 2016 2016 ASHRAE. All rights reserved 3J.4.3.2 Broadcast Distribution Table Format The BDT consists of one entry for the address of the BBMD for the local IP subnet and an entry for the BBMD on each remote IP subnet to which broadcasts are to be forwarded. Each entry consists of
15、 the 6-octet B/IP address with which the BBMD is accessed and a 4-octet broadcast distribution mask. If the IP router to the subnet performs network address translation (NAT), then the BDT entry shall contain the global IP address of the IP router. The operation of BBMDs in the presence of NAT is de
16、scribed in Clause J.7.8 J.7.5. If messages are to be distributed on the remote IP subnet using directed broadcasts, the broadcast . J.4.5 BBMD Operation - Broadcast Distribution . address as well as to each foreign device currently in the BBMDs FDT. A BBMD on a subnet with no other BACnet devices (s
17、uch as a NAT-supporting BBMD, see Clause J.7.8 J.7.5) may omit the broadcast using the B/IP broadcast address. The method by which a BBMD determines whether or not other BACnet devices are present is a local matter. 8) Clause W.10, 2nd, p. 1209: The word “it“ on first line of 2ndparagraph should be
18、“its“. W.10 Representation of Metadata If metadata items are represented as part of their associated data item, they are represented in a brief “short form“ because their type is fixed and therefore assumed. The “short form“ encodes only the metadata name and its value or children. For example, when
19、 included along with it its associated data item, (e.g., /path/to/example), the minimum metadata is encoded as: 9) Clause 12.56.55, 2nd, p. 537: The reference to Clause 12 is misleading. 12.56.55 Auto_Slave_Discovery . Slave detection shall be accomplished by the proxy device using ReadProperty serv
20、ices to read, at a minimum, the Device objects Protocol_Services_Supported property for each MAC address on the network connected to this port. The ReadProperty service shall use the special object instance of 4194303 as described in Clause 12 Clause 15.5.2. If the device is found to support executi
21、on of the Who-Is service, it is ignored; otherwise, the device shall be added to the Slave_Address_Binding property. The slave detection algorithm shall be repeated periodically. The period at which it is repeated is a local matter. 10) Clause 21, BACnetPropertyIdentifier, p. 845: The word “see“ is
22、missing in the numeric index for the Reliability property. BACnetPropertyIdentifier := ENUMERATED - see below for numerical order absentee-limit (244), . . zone-to (321), - -numerical order reference - see acked-transitions (0), . . - see reliability (103), . . 135-2016 Errata October 25, 2016 2016
23、ASHRAE. All rights reserved 411) Table W-14, p. 1241: The error code WS_ERR_UNINITIALIZED is incorrect. Table W-14. Error Numbers Error Name Error Number HTTP Status Code Example Error Text . . . .WS_ERR_UNINITIALIZED_VALUE 43 403 “Data is uninitialized and has no value“ . . . .12) Clause 12.10.22,
24、Command object type, p. 209, Clause 12.11.68, Device object type, p. 220, Clause 12.12.25, Event Enrollment object type, p. 228, Clause 12.21.20, Notification Class object type, p. 288, Clause 12.25.37, Trend Log object type, p. 307, Clause 12.27.29, Event Log object type, p. 322, Clause 12.28.32, L
25、oad Control object type, p. 332, Clause 12.30.35, Trend Log Multiple object type, p. 346, Clause 12.33.15, Access User object type, p. 375, Clause 12.34.12, Access Rights object type, p. 380, and Clause 12.35.26, Access Credential object type, p. 389: The Reliability_Evaluation_Inhibit property lang
26、uage in these clauses refers to the Out_Of_Service property that does not exist in these object types. 12.X.Y Reliability_Evaluation_Inhibit This property, of type BOOLEAN, indicates whether (TRUE) or not (FALSE) reliability-evaluation is disabled in the object. This property is a runtime override t
27、hat allows temporary disabling of reliability-evaluation. When reliability-evaluation is disabled, the Reliability property shall have the value NO_FAULT_DETECTED unless Out_Of_Service is TRUE and an alternate value has been written to the Reliability property. 13) Clause 15.7.3.1.2, p. 690, Clause
28、21, ReadAccessResult production, p. 870: The language on what to return for property identifier OPTIONAL misses the case of no optional properties are present, and no other properties were requested, so that no property value is returned for the object. 15.7.3.1.2 List of Property References . The p
29、roperty identifier REQUIRED means that only those standard properties having a conformance code of “R“ or “W“ shall be returned. The property identifier OPTIONAL means that only those standard properties present in the object that have a conformance code “O“ shall be returned. If no optional propert
30、ies are present then no entries associated with the OPTIONAL property identifier shall be in the List of Results and if no other properties were requested, then the List of Results shall be present and empty. The Property_List property shall not be returned when properties ALL or REQUIRED are reques
31、ted. See the specification for the particular object type in Clause 12. If the property identifier ALL, REQUIRED, or OPTIONAL is specified and any of the selected properties is not readable by this service, then a Property Access Error for that property shall be returned in the List of Read Access R
32、esults as specified by Clause 15.7.3.2. 135-2016 Errata October 25, 2016 2016 ASHRAE. All rights reserved 5ReadAccessResult := SEQUENCE object-identifier 0 BACnetObjectIdentifier, list-of-results 1 SEQUENCE OF SEQUENCE property-identifier 2 BACnetPropertyIdentifier, property-array-index 3 Unsigned O
33、PTIONAL, - used only with array datatype - if omitted with an array the entire - array is referenced read-result CHOICE property-value 4 ABSTRACT-SYNTAX.&Type, property-access-error 5 Error OPTIONAL 14) Clause 21, BACnetPropertyIdentifier, p. 846: “base-device-security-policy (327),“ is misplaced. B
34、ACnetPropertyIdentifier := ENUMERATED - see below for numerical order . bacnet-ipv6-udp-port (438), bacnet-ipv6-multicast-address (440), base-device-security-policy (327), base-device-security-policy (327), bbmd-accept-fd-registrations (413), . 15) Table 12-15, p. 223: There are missing lines in Tab
35、le 12-15. Table 12-15. Event Algorithm, Event Parameters and Event Algorithm Parameters Event Algorithm Event Parameters Event Algorithm Parameters NONE none none ACCESS_EVENT List_Of_Access_Events Access_Event_Time_Reference pAccessEvents Referents value is pAccessEventTime . . . OUT_OF_RANGE Time_
36、Delay Low_Limit High_Limit Deadband pTimeDelay pLowLimit pHighLimit pDeadband SIGNED_OUT_OF_RANGE Time_Delay Low_Limit High_Limit Deadband pTimeDelay pLowLimit pHighLimit pDeadband . . . 135-2016 Errata October 25, 2016 2016 ASHRAE. All rights reserved 616) Clauses L.2, L.3 and L.6, p. 1082, 1084 an
37、d 1091: The device profiles B-ALSWS, B-LSWS, B-AACWS, and B-AACC erroneously require NM-CE-A, which was removed from all device profiles with addendum 135-2008v. L.2 Life Safety Operator Interface Profiles The following table indicates which BIBBs shall be supported by the device types of this famil
38、y, for each interoperability area. Device & Network Management B-ALSWS B-LSWS B-LSAP DM-DDB-A,B DM-DDB-A,B DM-DDB-A,B DM-ANM-A DM-ADM-ADM-DOB-B DM-DOB-B DM-DOB-B DM-DCC-A DM-DCC-A DM-MTS-A DM-MTS-A DM-OCD-A DM-RD-A DM-RD-A DM-BR-A DM-BR-A NM-CE-A NM-CE-A L.2.1 BACnet Advanced Life Safety Workstation
39、 (B-ALSWS) . Device and Network Management . Ability to command half-routers to establish and terminate connections L.2.2 BACnet Life Safety Workstation (B-LSWS) . Device and Network Management . Ability to command half-routers to establish and terminate connections L.3 Access Control Operator Inter
40、face Profiles The following table indicates which BIBBs shall be supported by the device types of this family, for each interoperability area. Device & Network Management B-AACWS B-ACWS B-ACSD DM-DDB-A,B DM-DDB-A,B DM-DDB-A,B DM-ANM-A DM-ADM-ADM-DOB-B DM-DOB-B DM-DOB-B DM-DCC-A DM-DCC-A DM-MTS-A DM-
41、MTS-A DM-OCD-A DM-OCD-A DM-RD-A DM-BR-A NM-CE-A . L.3.1 BACnet Advanced Access Control Workstation (B-AACWS) . Device and Network Management . 135-2016 Errata October 25, 2016 2016 ASHRAE. All rights reserved 7 Ability to command half-routers to establish and terminate connections L.6 Access Control
42、 Controller Profiles The following table indicates which BIBBs shall be supported by the device types of this family, for each interoperability area. Device & Network Management B-AACC B-ACCDM-DDB-A,B DM-DDB-A,B DM-DOB-B DM-DOB-BDM-DCC-B DM-DCC-B DM-TS-B or DM-UTC-B DM-TS-B or DM-UTC-B DM-RD-B DM-RD-B DM-BR-BNM-CE-A L.6.1 BACnet Advanced Access Control Controller (B-AACC) . Device and Network Management . Ability to command half-routers to establish and terminate connections