ASHRAE 170 INT 2-2014 Ventilation of Health Care Facilities.pdf

上传人:wealthynice100 文档编号:454201 上传时间:2018-11-23 格式:PDF 页数:3 大小:132.47KB
下载 相关 举报
ASHRAE 170 INT 2-2014 Ventilation of Health Care Facilities.pdf_第1页
第1页 / 共3页
ASHRAE 170 INT 2-2014 Ventilation of Health Care Facilities.pdf_第2页
第2页 / 共3页
ASHRAE 170 INT 2-2014 Ventilation of Health Care Facilities.pdf_第3页
第3页 / 共3页
亲,该文档总共3页,全部预览完了,如果喜欢就下载吧!
资源描述

1、 Page 1 of 3 2014 ASHRAE. All Rights reserved. Interpretation IC 170-2013-2 of ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of Health Care Facilities Date Approved: July 1, 2014 Request from: Travis English (Travis.R.Englishkp.org), Kaiser Permanente, 1800 Harrision Street, Oakland, CA 94612. Refe

2、rence: This request for interpretation refers to the requirements in ANSI/ASHRAE/ASHE Standard 170-2013, Section 7.1.a.2, regarding providing for comfort. Background: Standard 170 (S170) 7.1.a.2 states that the criteria in Table 7.1 are intended to “provide for comfort”. In ASHRAEs standards, comfor

3、t is also covered by ASHRAE Standard 55- Thermal Comfort for Human Occupancy (S55). The methodologies of the two are notably different. S70 prescribes air temperature, air flow, and relative humidity ranges. S55 predicts comfort by using multiple variables (including but not limited to air temperate

4、, speed and humidity) and comparing combinations of variables to known human comfort responses. Using the S55 methodology: For typical occupant types, assuming compliant air speed and a zero degree difference between radiant and air temperatures, the nominal temperature ranges for S55 compliance are

5、 shown in the table and figure below. Occupant Type Clo Met Op T. Max RH PMV PPD Gowned Healthcare Workers 1.4 1.4 59.9 20 -0.50 10.16 Gowned Healthcare Workers 1.4 1.4 58.3 60-0.50 10.22 Gowned Healthcare Workers 1.4 1.4 71.7 20 0.50 10.22 Gowned Healthcare Workers 1.4 1.4 69.4 600.50 10.22 Healthc

6、are workers 0.5 1.4 73.7 2 -0.50 10.25 Healthcare workers 0.5 1.4 71.5 60 -0.50 10.21 Healthcare workers 0.5 1.4 80.8 2 0.49 10.06 Healthcare workers 0.5 1.4 78.1 60 0.49 10.06 Healthcare workers 1 1.4 66.4 2 -0.50 10.23 Healthcare workers 1 1.4 64.1 60 -0.50 10.17 Healthcare workers 1 1.4 76.4 2 0.

7、50 10.28 Healthcare workers 1 1.4 73.2 60 0.50 10.26 Patients 0.31 0.7 85.7 2 -0.47 9.64 Patients 0.31 0.7 83.3 60 -0.50 10.22 Patients 0.31 0.7 88.4 2 0.50 10.23 Patients 0.31 0.7 85.9 60 0.50 10.23 Workers, patients, or guests 0.5 1 79.6 2 -0.50 10.22 Workers, patients, or guests 0.5 1 77.2 60 -0.

8、50 10.22 Workers, patients, or guests 0.5 1 84.5 2 0.50 10.22 Workers, patients, or guests 0.5 1 81.7 60 0.50 10.22 Workers, patients, or guests 1 1 74.2 2 -0.50 10.22 Workers, patients, or 1 1 71.4 60 -0.50 10.22 Interpretation IC 170-2013-X Page 2 of 3 2014 ASHRAE. All Rights reserved. Classified

9、- Internal use Occupant Type Clo Met Op T. Max RH PMV PPD guests Workers, patients, or guests 1 1 81.0 2 0.50 10.22 Workers, patients, or guests 1 1 77.6 60 0.50 10.22 Table 1: S55 Temperature and Humidity Ranges yielding -0.50.5 Fig. 1: S55 Temperature and Humidity Ranges yielding -0.50.5 Using the

10、 S170 methodology: There are 15 unique comfort criteria indicated in S170 Table 7.1. They are shown in the table below. Temperature (F) Humidity Range (RH) (No of Spaces), e.g. Space A 68 73 20 60 (1) e.g. Gastrointestinal Endoscopy procedure room B 68 75 20 60 (3) e.g. Classes B&C operating rooms C

11、 70 75 20 60 (5) e.g. Recovery Room D 70 75 30 60 (2) e.g. Critical and intensive care E 72 78 30 60 (1) e.g. Newborn intensive care F 70 75 40 60 (1) e.g. Wound intensive care G 70 75 Max 60 (14) e.g. Intermediate care H 72 78 Max 60 (3) e.g. X-ray, diagnostic and treatment I 72 80 Max 60 (1) e.g.

12、Physical therapy J 70 75 Max 60 (1) e.g. ER Waiting Rooms K 68 73 NR (1) e.g. Bronscoscopy, sputum collection and pentamidine administration L 70 75 NR (19) e.g. Resident Room M 72 78 NR (9) e.g. Dialysis treatment room N 72 80 NR (1) e.g. Hydrotherepy O NR NR (28) e.g. Substerile service area Table

13、 1: S170 Temperature and Humidity Ranges, as listed in Table 7-1 Using standard assumptions for clothing insulation and metabolic activity, PPD in these spaces can calculated tested with the S55 methodology. The results are shown in the table below: Interpretation IC 170-2013-X Page 3 of 3 2014 ASHR

14、AE. All Rights reserved. Classified - Internal use Condition Temp. RH. Clo Met Air Speed PMV PPD S55 Result A Min. 68 20 0.5 1.0 30 -2.59 95.17 Does not comply Max. 73 60 1.0 1.4 30 -1.25 37.57 Does not comply B Min. 68 20 0.5 1.0 30 -2.59 95.17 Does not comply Max. 75 60 1.0 1.4 30 -0.81 18.68 Does

15、 not comply C Min. 70 20 0.5 1.0 30 -2.17 83.93 Does not comply Max. 75 60 1.0 1.4 30 -0.81 18.68 Does not comply D Min. 70 30 0.5 1.0 30 -2.11 81.35 Does not comply Max. 75 60 1.0 1.4 30 -0.81 18.68 Does not comply E Min. 72 30 0.5 1.0 30 -1.68 60.81 Does not comply Max. 78 60 1.0 1.4 30 -0.14 5.4

16、Complies F Min. 70 40 0.5 1.0 30 -2.04 78.54 Does not comply Max. 75 60 1.0 1.4 30 -0.81 18.68 Does not comply G Min. 70 2 0.5 1.0 30 -2.29 88.01 Does not comply Max. 75 60 1.0 1.4 30 -0.81 18.68 Does not comply H Min. 72 2 0.5 1.0 30 -1.88 71.1 Does not comply Max. 78 60 1.0 1.4 30 -0.14 5.4 Compli

17、es I Min. 72 2 0.5 1.0 30 -1.88 71.1 Does not comply Max. 80 60 1.0 1.4 30 0.31 6.96 Complies J Min. 70 2 0.5 1.0 30 -2.29 88.01 Does not comply Max. 75 60 1.0 1.4 30 -0.81 18.68 Does not comply K Min. 68 2 0.5 1.0 30 -2.7 96.77 Does not comply Max. 73 60 1.0 1.4 30 -1.25 37.57 Does not comply L Min

18、. 70 2 0.5 1.0 30 -2.29 88.01 Does not comply Max. 75 60 1.0 1.4 30 -0.81 18.68 Does not comply M Min. 72 2 0.5 1.0 30 -1.88 71.1 Does not comply Max. 78 60 1.0 1.4 30 -0.14 5.4 Complies N Min. 72 2 0.5 1.0 30 -1.88 71.1 Does not comply Max. 80 60 1.0 1.4 30 0.31 6.96 Complies Table 3: Predicted PMV

19、 and PPD of S170 Temperature and Humidity Criteria Interpretation: The criteria in Table 7.1 fully provide for comfort. Compliance to Standard 170 yields spaces that comply with the scope, purpose and intent of ASHRAE Standard 55 without further analysis. Question: Is this interpretation correct? Answer: No Comments: Compliance with Standard 170 -2013 does not assure compliance with Standard 55 -2013.

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > 其他

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1