ASTM C1060-1990(2003) Standard Practice for Thermographic Inspection of Insulation Installations in Envelope Cavities of Frame Buildings《框架建筑物外壳内腔的绝热设施的温度记录检验》.pdf

上传人:cleanass300 文档编号:463179 上传时间:2018-11-27 格式:PDF 页数:6 大小:69.15KB
下载 相关 举报
ASTM C1060-1990(2003) Standard Practice for Thermographic Inspection of Insulation Installations in Envelope Cavities of Frame Buildings《框架建筑物外壳内腔的绝热设施的温度记录检验》.pdf_第1页
第1页 / 共6页
ASTM C1060-1990(2003) Standard Practice for Thermographic Inspection of Insulation Installations in Envelope Cavities of Frame Buildings《框架建筑物外壳内腔的绝热设施的温度记录检验》.pdf_第2页
第2页 / 共6页
ASTM C1060-1990(2003) Standard Practice for Thermographic Inspection of Insulation Installations in Envelope Cavities of Frame Buildings《框架建筑物外壳内腔的绝热设施的温度记录检验》.pdf_第3页
第3页 / 共6页
ASTM C1060-1990(2003) Standard Practice for Thermographic Inspection of Insulation Installations in Envelope Cavities of Frame Buildings《框架建筑物外壳内腔的绝热设施的温度记录检验》.pdf_第4页
第4页 / 共6页
ASTM C1060-1990(2003) Standard Practice for Thermographic Inspection of Insulation Installations in Envelope Cavities of Frame Buildings《框架建筑物外壳内腔的绝热设施的温度记录检验》.pdf_第5页
第5页 / 共6页
亲,该文档总共6页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、Designation: C 1060 90 (Reapproved 2003)Standard Practice forThermographic Inspection of Insulation Installations inEnvelope Cavities of Frame Buildings1This standard is issued under the fixed designation C 1060; the number immediately following the designation indicates the year oforiginal adoption

2、 or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice is a guide to the proper use of infraredimaging systems for c

3、onducting qualitative thermal inspectionsof building walls, ceilings, roofs, and floors, framed in wood ormetal, that may contain insulation in the spaces betweenframing members. This procedure allows the detection ofcavities where insulation may be inadequate or missing andallows identification of

4、areas with apparently adequate insula-tion.1.2 This practice offers reliable means for detecting sus-pected missing insulation. It also offers the possibility ofdetecting partial-thickness insulation, improperly installed in-sulation, or insulation damaged in service. Proof of missinginsulation or a

5、 malfunctioning envelope requires independentvalidation. Validation techniques, such as visual inspection orin-situ R-value measurement, are beyond the scope of thispractice.1.3 This practice is limited to frame construction eventhough thermography can be used on all building types.2,31.4 Instrument

6、ation and calibration required under a varietyof environmental conditions are described. Instrumentationrequirements and measurement procedures are considered forinspections from both inside and outside the structure. Eachvantage point offers visual access to areas hidden from theother side.1.5 The

7、values stated in SI units are to be regarded asstandard. The inch-pound units given in parentheses are forinformation only.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro

8、-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. In particular,caution should be taken in the handling of any cryogenicliquids or pressurized gases required for use in this practice.Specific precautionary statements are given in Note 1 and

9、Note3.2. Referenced Documents2.1 ASTM Standards:C 168 Terminology Relating to Thermal Insulation4E 1213 Test Method for Minimum Resolvable TemperatureDifference for Thermal Imaging Systems53. Terminology3.1 DefinitionsDefinitions pertaining to insulation are de-fined in Terminology C 168.3.2 Definit

10、ions of Terms Specific to This Standard:3.2.1 anomalous thermal imagean observed thermal pat-tern of a structure that is not in accordance with the expectedthermal pattern.3.2.2 envelopethe construction, taken as a whole or inpart, that separates the indoors of a building from the outdoors.3.2.3 fie

11、ld-of-view (FOV)the total angular dimensions,expressed in degrees or radians, within which objects can beimaged, displayed, and recorded by a stationary imagingdevice.3.2.4 framing spacingdistance between the centerlines ofjoists, studs, or rafters.3.2.5 infrared imaging systeman instrument that con

12、vertsthe spatial variations in infrared radiance from a surface into atwo-dimensional image of that surface, in which variations inradiance are displayed as a range of colors or tones.3.2.6 infrared thermographythe process of generatingthermal images that represent temperature and emittance varia-ti

13、ons over the surfaces of objects.3.2.7 instantaneous field of view (IFOV)the smallestangle, in milliradians, that can be instantaneously resolved bya particular infrared imaging system.1This practice is under the jurisdiction of ASTM Committee C16 on ThermalInsulation and is the direct responsibilit

14、y of Subcommittee C16.30 on ThermalMeasurement.Current edition approved April 10, 2003. Published August 2003. Originallyapproved in 1986. Last previous edition approved in 1997 as C 1060 90 (1997)e1.2ISO/TC 163/SC 1/WG N31E Thermal InsulationQualitative Detection ofThermal Irregularities in Buildin

15、g EnvelopesInfrared Method, available fromAmerican National Standards Institute, 25 W. 43rd St., 4th Floor, New York, NY10036.3Guidelines for Specifying and Performing Infrared Inspections, InfraspectionInstitute, Shelburne, VT, 1988.4Annual Book of ASTM Standards, Vol 04.06.5Annual Book of ASTM Sta

16、ndards, Vol 03.03.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2.8 masonry veneerframe construction with a non-loadbearing exterior masonry surface.3.2.9 minimum resolvable temperature difference(MRTD)a measure of the ability of

17、 the operators of aninfrared imaging system to discern temperature differenceswith that system. The MRTD is the minimum temperaturedifference between a four-slot test pattern of defined shape andsize and its blackbody background at which an averageobserver can discriminate the pattern with that infr

18、ared imag-ing system at a defined distance.3.2.10 thermal patterna representation of colors or tonesthat indicate surface temperature and emittance variation.3.2.11 thermograma recorded image that maps the appar-ent temperature pattern of an object or scene into a correspond-ing contrast or color pa

19、ttern.3.2.12 zonea volume of building served by a singleventilation system. For buildings with natural ventilation only,the whole building shall be considered a zone with all interiordoors open.4. Summary of Practice4.1 This practice is a guide to the proper use of infraredimaging systems for conduc

20、ting qualitative thermal inspectionsof building walls, ceilings, roofs, and floors, framed in wood ormetal, that may contain insulation in the spaces betweenframing members. Imaging system performance is defined interms of instantaneous field of view (IFOV) and minimumresolvable temperature differen

21、ce (MRTD). Conditions underwhich information is to be collected and compiled in a reportare specified. Adherence to this standard practice requires afinal report of the investigation. This practice defines thecontents of the report.5. Significance and Use5.1 Although infrared imaging systems have th

22、e potential todetermine many factors concerning the thermal performance ofa wall, roof, floor, or ceiling, the emphasis in this practice is ondetermining whether insulation is missing or whether aninsulation installation is malfunctioning. Anomalous thermalimages from other apparent causes may also

23、be recorded assupplemental information, even though their interpretationmay require procedures and techniques not presented in thispractice.6. Instrumentation Requirements6.1 Environmental FactorsThe environment has a signifi-cant impact on the heat flow through the envelope. As a result,the require

24、ments on thermal imaging instrumentation vary withthe interior to exterior air temperature gradient for both interiorand exterior inspections and also vary with wind speed forexterior inspections.6.2 Infrared Imaging System PerformanceThe ability ofan observer to detect thermal anomalies depends on

25、theimagers powers of thermal and spatial resolution. The practi-cal test for these qualities is whether the operator can distin-guish the framing from the envelope cavities under theprevailing thermal conditions with the infrared imaging systemat a distance that permits recognition of thermal anomal

26、ies. Forplanning an equipment purchase or a site visit, the followingqualities may be considered: The minimum resolvable tem-perature difference (MRTD) defines temperature resolution.Instantaneous field of view (IFOV) is an indicator of spatialresolution. Appendix X1 explains how to calculate IFOV a

27、ndhow to measure MRTD.6.2.1 Spectral RangeThe infrared thermal imaging sys-tem shall operate within a spectral range between 2 and 14 m.6.2.2 Field of View (FOV)The critical minimum dimen-sions for discriminating missing insulation in frame construc-tion is two framing spacings wide and one framing

28、spacinghigh. Outdoors, it is typically convenient to view at least onefloor-to-ceiling height across and one-half that distance high.The FOV of the chosen imaging system should encompassthese minimum dimensions from the chosen indoor viewingdistance, di, and outdoor viewing distance, do. For plannin

29、gpurposes, the angular value of FOV may be calculated foreither d (m) by the following equations:FOVvertical$ 2 tan21h/2d! (1)FOVhorizontal$ 2 tan21w/2d! (2)where:h = vertical distance viewed, m, andw = horizontal distance viewed, m.7. Knowledge Requirement7.1 This practice requires operation of the

30、 imaging systemand interpretation of the data obtained. The same person mayperform both functions. The operator of the infrared imagingsystem shall have thorough knowledge of its use throughtraining, the manufacturers manuals, or both. The interpretorof the thermographic data shall be knowledgeable

31、about heattransfer through building envelopes and about thermography,including the effects of stored heat, wind, and surface moisture.7.2 The instrument shall be operated in accordance with thepublished instructions of the manufacturer.8. Preferred Conditions8.1 The criterion for satisfactory therma

32、l conditions is theability to distinguish framing members from cavities. Appen-dix X2 gives some guidelines for determining whether theweather conditions are likely to be suitable.9. Procedure9.1 Preliminary InspectionA preliminary thermographicinspection may be performed to determine whether a thor

33、oughinspection, and report, is warranted.9.2 Background InformationPrepare for the report bycollecting information on the building. In order to evaluate thestructure, collect the following preliminary data where practi-cal and necessary:9.2.1 Note each type of building cross section, using visualins

34、pection, construction drawings, or both, to determine whatthermal patterns to expect.9.2.2 Additions or modifications to the structure.9.2.3 Thermal problems reported by the building owner/occupant.9.2.4 Note differences in surface materials or conditions thatmay affect emittance, for example, metal

35、lic finishes, polishedC 1060 90 (2003)2surfaces, stains, or moisture. Such differences in emittancecause thermal patterns that are independent of temperaturedifferences.9.2.5 Orientation of the building with respect to the pointsof the compass.9.2.6 Heat sources, such as light fixtures, mounted in o

36、rclose to the exterior construction.9.3 Performing On-Site Equipment Check and Settings:9.3.1 Set the instrument gain or contrast to allow theobserver to distinguish a framing member from the envelopearea around it. In addition, set the imagers sensitivity so thatany anomalies or areas to which they

37、 are referenced are not insaturation (maximum brightness or white) or in suppression(minimum brightness or black) on the display.9.3.2 Verify proper operation of the recording system, ifany.9.3.3 Make a sketch or photograph of each envelope areawith references for locating framing members.9.4 Perfor

38、ming the Inspection:9.4.1 A complete thermographic inspection of a buildingmay consist of an exterior or interior inspection of the completeenvelope, or both. Both types of inspection are recommendedbecause each offers access to areas that may be difficult for theother.9.4.2 Inspect all surfaces of

39、interest from an angle as closeto normal to the surface as possible, but at least at an angle thatpermits distinguishing framing members. Make inspectionsfrom several angles, perpendicular, if possible, and at twoopposite oblique angles in order to detect the presence ofreflected radiation.9.4.3 Mak

40、e scans from a position that allows a field of viewthat encompasses at least two framing spacings wide and oneframing spacing high for an interior inspection and a floor-to-ceiling height wide and one-half that distance high for anexterior inspection.9.4.4 Effective corrective action requires a prec

41、ise definitionof the areas with apparent defects. Record each anomaly withannotation regarding the location of all recognizable buildingcharacteristics such as windows, doors, and vents. The recordmay accommodate any requirement for calculations of enve-lope areas with anomalies.10. Thermographic In

42、terpretation10.1 If apparent defects in insulation are not confirmed,corrected, and reinspected at the time of the thermographicsurvey, then thermograms or other precise identification of thelocations and types of apparent defects are required. Theinterpretation of the thermogram allows determinatio

43、n of thefollowing information:10.1.1 Locations of the regions where insulation is appar-ently missing or defective and their total area.10.1.2 Locations of the regions where the insulation isapparently intact and their total area.10.1.3 Location and total area of added insulation (if 10.1.1and 10.1.

44、2 were performed in a thermographic inspection priorto adding insulation).10.1.4 Estimated total area of surfaces that cannot beinspected.10.2 Interpretation of thermographic images requires aware-ness of the following types of patterns:10.2.1 Intact InsulationAs seen from the warm side of theconstr

45、uction: dark parallel lines, representing the framing;uniformly lighter areas between the framing lines, representingthe insulation. As seen from the cool side of the construction:the framing lines are light. The areas containing insulation areuniformly dark.NOTE 1Metal framing with no insulation ma

46、y fit this description. SeeNote 2.NOTE 2Metal framing conducts heat better than both air and insula-tion. If insulation is present, the thermal contrast between metal framingand the spaces between may be very strong. Independent verification maybe needed for metal-framed buildings to establish typic

47、al patterns forinsulated and uninsulated areas.10.2.2 Insulation Missing CompletelyAs seen from thewarm side of the construction: light parallel lines, representingthe framing; darker areas between the framing lines, represent-ing the empty space between framing members. Convectionmay be visible in

48、vertical framing, as evidenced by a gradientfrom dark (cooler) at the bottom of the space to light (warmer)at the top. As seen from the cool side of the construction: theframing lines are dark, the areas between framing are light andconvection is still lighter at the top of vertical spaces.NOTE 3Met

49、al framing with no insulation may not fit this description.See Note 2.10.2.3 Insulation Partially MissingThe dominant effect isas described in 10.2.1, except that missing insulation shows asa well-defined dark region, as seen from the warm side and asa light region as seen from the cool side.10.2.4 Other Thermal PatternsIrregular variation of thethermal pattern in the spaces between framing members mayindicate a combination of possible causes, including varyingdensity of insulation, convection or air leakage, moisture, orthermal bridges. A partial list

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ASTM

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1